Controller.ReactionManager : EventsAndReactions

The Reaction Manager is described in chapter Controller.ReactionManager. Since Controller firmware v2.0.0, the following reactions are included:

Event

PLC stop

LED

LEM

SysLog

Device Stop

Manual PLC start

Replace

During boot process:

The Controller has detected that application data has been changed without authorization. An attempt is automatically made to perform an internal restore.

 

yes

 

yes

 

yes

 

During boot process:

An error was detected during an update or downgrade and the base partition was changed.

 

yes

yes

yes

 

yes

 

During runtime:

An data integrity error was detected. The PLC is stopped and on the next boot an attempt is automatically made to perform an internal restore.

yes

yes

yes

yes

 

yes

 

During boot process and during runtime:

Validation error during the signing check of basic device settings.

 

yes

 

 

yes

yes

(*1)

yes

(*1)

During boot process and during runtime:

Error in the internal file directory tree and on the next boot an attempt is automatically made to perform an internal restore.

yes

yes

yes

yes

 

yes

 

  • If a security error is detected, the error must always be acknowledged (PLC RUN command).

  • If the error occurs during the boot phase, the system will attempt an automatic recovery, except in the case of hardware errors.

  • If the error occurs during operation, an automatic recovery will begin the next time the controller is started.

  • (*1) Information about Validation Error during the signing check.

    • If the Controller itself (i.e. the basic device) or one of the modules (i.e. the PROFINET module) displays a validation error, the user should have a look on the SD Card in the "SeriousError.txt" file. This file indicates whether the base unit caused the problem (in which case it must be sent to Lenze Service) or whether the module caused the problem (in which case it must be replaced with one that is functioning properly).

    • If the communication module of the controller displays a validation error, the communication module must be sent to Lenze Service. It can be replaced in the system with a correct communication module. After replacing it with a correct module, the controller must be restarted and the error acknowledged by the customer. The controller can then be operated again. The defective module must then be sent to Lenze Service.

PLC stop

During boot process:
The check is carried out when the controller is booting. At this point, the controller application is not yet running and therefore does not need to be stopped.
During runtime:
The check takes place during the runtime of the controller. If errors occur, the application is stopped.
Reset Error:
The errors must always be acknowledged (PLC RUN command).

LED

If the controller is available again after a successful restore, the LED "ERR" (red) flashes red and indicates the status "WARNING".

If the LED displays "WARNING" or "TROUBLE" after a recovery, check the logbook and, if necessary, restart the system, install the firmware, or restore a backup.

If the Controller or one of its modules cannot be repaired by a restore, they must be sent to Lenze Service.

LEM

The Controller has an LEM (Lenze Error Management) in which error messages are stored for the application engineer and machine operator. There will be an entry here, but without a detailed description of the error pattern.

SysLog

The controller has a SysLog mechanism that has a logbook in the controller and can also send messages via a SysLog client (see chapter Controller.SysLog). If a corresponding error occurs, a message will appear here with further information about the cause.

Manual PLC start

After an internal security error and a subsequent restore of the data, the PLC program does not start automatically but must be set to RUN manually once to reset the error. The user is recommended to check the corresponding data stock before switching the machine back on.

In addition, a file named "SeriousError.txt" is written to the SD Card, providing the user with more information about the problem.

Replace

After an internal security error, it is determined that the problem is so serious that the components must be replaced. These must be sent to Lenze Service for this purpose. It is recommended to check the "SeriousError.txt" on the SD Card. Normally this file point out exactly what device or module is malfunctionus. The syslog could also be checked to derive more informations. If necessary, only the malfunctionus module can be sent to Lenze Service and not the complete device.