Adding online devices

After clicking the Add device button, a dialogue window opens containing the Online tab.

Establish a communication path

If an online device is to be inserted, a connection path to it must first be established. To do this, the tab contains a prompt to select a communication path to this device:

Depending on the selected combination of communication media, the tab adapts itself with regard to the entry of the data required to set up communication.

The following communication media (PC-side / device-side ) can be selected:

USB

Diagnostics via adapter E94AZCUS

USB with module i5MADU0000000S

USB onboard

CAN via adapter EMF2177IB

Parallel port

CAN via adapter EMF2173IB * )

Telephone network

CAN via modem CAN EMF2181IB * )

Ethernet / WLAN

Ethernet - CAN via adapter EMF2180IB

Ethernet - CAN via gateway EL 100 * )

Ethernet - CAN via Lenze Controller c3xx/c32xx

Ethernet

Ethernet to the Lenze Controller c3xx/c32xx

Ethernet to the Lenze Controller c4xx, c5xx

Ethernet - EtherCAT via Lenze Controller c3xx

Ethernet - EtherCAT via Lenze Controller c4xx, c5xx

Ethernet - EtherCAT via Beckhoff controller (TwinCAT 2)

Ethernet - EtherCAT via Beckhoff controller (TwinCAT 3)

Ethernet - EtherCAT via ESD slave bridge ECX-EC

PROFINET

Ethernet / IP

Modbus TCP

WLAN with module i5MADU0000000S

CAN

CAN with PC expansion card Lenze MC-CAN2 * )

CAN with PC expansion card Peak ISA CAN * )

CAN with PC expansion card Peak PCI CAN * )

CAN with PC expansion card Lenze FC-CAN * )

COM

COM port - Lecom * )

COM port - PROFIBUS via Siemens S7 * )

*)This connection is only offered if "Show outdated connections" is ticked in "Settings / Tool".

Example: Setting up a diagnostic connection

  • How to establish a diagnostic connection:

  1. Select "USB / Diagnostics" as the communication medium in / .

  2. Select connection "USB diagnostics via USB diagnostic adapter E94AZCUS".

  3. Press the Insert button.

If several diagnostic adapters are connected to the PC, the first adapter is always used. A selection is not provided.

Example: Setting up an Ethernet connection

Observe the notes on automatic identification in the section

  • How to set up an Ethernet connection:

  1. Select "Ethernet/WLAN" as the communication medium in .

  2. Select "Ethernet" as the communication medium in .

  3. Select Ethernet connection.

    The interface that opens contains additional information that is displayed when you move the mouse pointer over the icon.

  4. Define devices to be inserted.

    • All devices found

      A search takes place within the segment boundaries for locally accessible devices.

      Continue with step 6.

    • Browse

      A search takes place within the segment boundaries for locally accessible devices.

      Continue with step 5.

    • IP address range

      Manual specification of a defined address range.

      Continue with step 6.

    • IP address

      Manual specification of a defined IP address. PING can be used to check whether the address entered is responding.

      Continue with step 6.

  5. Press the Browse button.

    A selection list appears in a new window, in which all devices found within the segment limits are displayed accordingly. These devices can be selected for insertion into the device list.

    It is also possible to set IP addresses on the devices found, see 'Set IP address'. If a device does not yet have an IP address, this step is necessary in order to be able to add it afterwards.

  6. Press the Insert button.

    Clicking the Insert button inserts the devices specified by the user into the device list.

Set IP address for Ethernet-based interfaces, e.g. PROFINET

  • It is possible to set up IP addresses using the Browse button. The prerequisite for this is that the interface of the device supports this function.

  • The following applies to PROFINET: The IP address may only be assigned manually in the "EASY Starter" if the PROFINET network is not yet being operated on the IO controller (IP address has not yet been assigned by the IO controller). No simultaneous PROFINET communication with the IO controller may take place while the IP parameters are being set in the "EASY Starter".

  • How to configure the IP settings for a PROFINET interface:

  1. Select "Ethernet / WLAN" and "PROFINET" as the communication medium in / .

  2. Select "PROFINET" connection.

  3. Press the Browse button.

    A selection list appears in a new window, in which all devices found within the segment limits are displayed accordingly.

  4. Select a device and enter the IP settings.

  5. Press the Transfer button.

    The IP settings defined by the user are transferred to the device.

Option "Automatically identify devices"

The Automatically identify devices option on the tab can be deactivated if, for example, you want to save time when adding a large number of online devices. All devices found are then added as unknown devices.

Devices can be identified at a later time using the Identify unknown devices button (for example, after the scope of the device list has been reduced by devices that should not be edited).