GDS registration
Manual
For this approach no further configuration is needed on the OPC UA Server side. All the configuration is done on GDS side. In case of the UaGDS (from Unified Automation) the UaGDSConfiguration tool can be used.
For the manual registration the GDS Client Mode parameter 0x2471:150 has to be set to 0:Disabled (default).
Automatic
The OPC UA server also offers the option of automatically registering with a GDS server. For this purpose, there is an internal client implementation in the OPC UA Server application that establishes a connection with the GDS server.
For the automatic registration the GDS Client Mode parameter 0x2471:150 has to be set to 1:Enabled Registration or to 2:Enabled Registration and Pull.
|
Index |
Sub |
Name |
Default |
Note |
|---|---|---|---|---|
|
0x2471 |
150 |
GDS Client Mode |
0: Disabled |
0: Disabled 1: Enabled Registration 2: Enabled Registration and Pull |
|
0x2471 |
156 |
GDS Endpoint URL |
GDS Server address, e.g. opc.tcp://192.168.91.48:48060 |
|
|
0x2471 |
157 |
GDS User |
User name for authentication at GDS Server |
|
|
0x2471 |
158 |
GDS Password |
Password for authentication at GDS Server Use the password dialogue in PLC Designer and EASY Starter for encrypted storage on the device. |
|
|
0x2471 |
159 |
GDS Hostname Check |
0: Enabled |
0: Disabled 1: Enabled |
For diagnosis purposes following parameters are provided:
|
Index |
Sub |
Name |
Default |
Note |
|---|---|---|---|---|
|
0x2473 |
190 |
GDS Client State |
0: Disabled |
0: Disabled 1: Disconnected 2: Connecting 3: Register Application 4: Get Certificate Status 5: Start Signing Request 6: Finish Signing Request 7: Update Tustlist 8: Disconnecting 9: Reconnecting |
|
0x2473 |
191 |
GDS Client Registration State |
|
This parameter gives information about the registration state of the server in the GDS. It´s independent of the exchange of trust list and CA-signed certificates. 0: Unregistered 1: Registered 2: Registration Failed |
It is recommended to use encrypted transport and encrypted storage whenever the Password parameter in 0x2471:158 is changed. To establish an encrypted communication with the target device use either the PLC Designer or the EasyStarter, both require a forced encryption. To edit the parameters, after a secure connection is established, only use the password dialogue on the OPC UA Client Settings tab in the PLC Designer or EASY Starter. If this method is used, the password is only stored in encrypted form on the controller. The password will not be stored in the offline parameter set.
If the parameter is set using other methods, e.g. the "Parameter list” of the tool, the password is also stored unencrypted in the offline parameter set created by the tool.
The certificate check during connection establishment between the internal GDS client and the GDS Server includes a check of the hostname in the GDS server certificate and the GDS Endpoint Url in parameter 0x2471:156. Normally this should match, because otherwise an attacker could use any trusted certificate to fake a server's identity.
Nevertheless, the check can be disabled by the parameter 0x2471:159. It´s useful if the IT infrastructure is not able to resolve hostnames via DNS server and an IP address has to be used for the GDS Endpoint Url in parameter 0x2471:156.
From a security point of view, it is not recommended to disable the hostname check.
To grant the GDS access to the OPC UA Server in case of manual or automatic registration or in case of pushing certificates, the GDS must be trusted on OPC UA Server side. This can be done manually with the Security Screen in the PLC Designer or automatically with the provisioning mode.
When registering manually in GDS and using the certificate push management, the GDS acts as an external Client. The number of external Clients is subject of license. One session is for free.