OPC UA Server capabilities

The Lenze OPC UA Server on the controller supports the following service capabilities. The individually listed capabilities have the limit named here. Depending on the combination and utilization of these capabilities, as well as the utilization of the CPU due to the PLC application and other processes on the controller, the controller may reach its performance limit.

This must be considered during project engineering.

Service

c4xx Controller

c5xx Controller

Max. Number of instance nodes

(in instance model per namespace)

No limit

(in the PLCopen instance model)

Max. Number of nodes

(in type model per namespace)

12010

Max. Number of variables

(in type model per namespace)

10008

Max. Number of references

(in type model per namespace)

20020

Max. Number of dimensions

(in type model per namespace)

10008

Max. Number of User Sessions

4 1)

c520 = 61)

c550 = 121)

SessionTimeOut

min 10sec and max 15min

Max. No. of subscriptions per session

10

16

Max. Number of

Monitored Items per Subscription

2000

4000

Max. Sum Number of Monitored Items

4000

±200 for Engineering Access

8000

±400 for Engineering Access

Max. Sum Number of Subscriptions

10

+2 for Engineering Access

16

+4 for Engineering Access

Min. publishing interval

200ms

100ms

Min. sampling interval

200ms

100ms

Max. Queue size

1

Max. Monitored items per call

1000

2000

Max. Nodes per browse

100

Max. Nodes per read

100

Max. Nodes per write

100

Max. Nodes per register nodes

100

Max. Nodes per trans.Bro.PathToID

100

Max. Array Length

65535

Max Number of Nodesets

10

Max. Event Queue

10

Max. Mapping Base Model Nodesets

10

GDS - Client pull - error retry

60sec

GDS - Client pull - update intervall

1h

SKS - Client pull - error retry

5sec.

1)

One client connection (session) is included in the basic setup of the OPC UA Server. Additional sessions are subject to license

The Lenze OPC UA server on the controller can be reached under the Ethernet TCP port 4840 of the controller.

It can be identified in the system under the following ApplicationUri:

  • Lenze Controller OPC UA Server@<host name of the controller>