OPC UA Server capabilities
The Lenze OPC UA Server on the controller supports the following service capabilities. The individually listed capabilities have the limit named here. Depending on the combination and utilization of these capabilities, as well as the utilization of the CPU due to the PLC application and other processes on the controller, the controller may reach its performance limit.
This must be considered during project engineering.
|
Service |
c4xx Controller |
c5xx Controller |
|---|---|---|
|
Max. Number of instance nodes (in instance model per namespace) |
No limit (in the PLCopen instance model) |
|
|
Max. Number of nodes (in type model per namespace) |
12010 |
|
|
Max. Number of variables (in type model per namespace) |
10008 |
|
|
Max. Number of references (in type model per namespace) |
20020 |
|
|
Max. Number of dimensions (in type model per namespace) |
10008 |
|
|
Max. Number of User Sessions |
4 1) |
c520 = 61) c550 = 121) |
|
SessionTimeOut |
min 10sec and max 15min |
|
|
Max. No. of subscriptions per session |
10 |
16 |
|
Max. Number of Monitored Items per Subscription |
2000 |
4000 |
|
Max. Sum Number of Monitored Items |
4000 ±200 for Engineering Access |
8000 ±400 for Engineering Access |
|
Max. Sum Number of Subscriptions |
10 +2 for Engineering Access |
16 +4 for Engineering Access |
|
Min. publishing interval |
200ms |
100ms |
|
Min. sampling interval |
200ms |
100ms |
|
Max. Queue size |
1 |
|
|
Max. Monitored items per call |
1000 |
2000 |
|
Max. Nodes per browse |
100 |
|
|
Max. Nodes per read |
100 |
|
|
Max. Nodes per write |
100 |
|
|
Max. Nodes per register nodes |
100 |
|
|
Max. Nodes per trans.Bro.PathToID |
100 |
|
|
Max. Array Length |
65535 |
|
|
Max Number of Nodesets |
10 |
|
|
Max. Event Queue |
10 |
|
|
Max. Mapping Base Model Nodesets |
10 |
|
|
GDS - Client pull - error retry |
60sec |
|
|
GDS - Client pull - update intervall |
1h |
|
|
SKS - Client pull - error retry |
5sec. |
|
|
1) |
One client connection (session) is included in the basic setup of the OPC UA Server. Additional sessions are subject to license |
The Lenze OPC UA server on the controller can be reached under the Ethernet TCP port 4840 of the controller.
It can be identified in the system under the following ApplicationUri:
-
Lenze Controller OPC UA Server@<host name of the controller>