Procedure after activating the parameter identification
Phase 1: Waiting for the ambient temperature
The identification needs to be started at ambient temperature. For this purpose, the change of the current temperature is monitored while the heating element is switched off (correcting variable = 0%). Only when the change rate falls below a limit value (stationary ambient temperature is reached), phase 1 is completed.
Status diagram for step 1
Measuring points in the signal flow:
|
Designator Data type |
Description |
|
|---|---|---|
|
MP13_lrIdentS1ElapsedTime LREAL |
Time elapsed since the start of phase 1 of the parameter identification.
|
|
|
MP14_lrIdentS1TempActGradient LREAL |
Current time rate of change of the actual temperature.
|
|
Phase 2: Applying a small correcting variable
The heating element is applied with a small correcting variable and is it waited until a stationary temperature has been reached. This action is required to detect the fundamental heating capacity of the heat section and calculate the correcting variable step that is optimal for phase 3.
The current correcting variable for the heating element can be read at the lrHeatingPowerPct output (scaled in percent).
Status diagram for step 2
Measuring points in the signal flow:
|
Designator Data type |
Description |
|
|---|---|---|
|
MP15_lrIdentS2TempStart LREAL |
Start temperature for transition phase 2
|
|
|
MP16_lrIdentS2ElapsedTime LREAL |
Time elapsed since the last manipulated variable jump in phase 2.
|
|
|
MP17_lrIdentS2TempActGradient LREAL |
Current time rate of change of the actual temperature.
|
|
Phase 3: Determining the behaviour of the heat section
The heating element is connected with the optimum control value step calculated in phase 2. The relevant characteristic values of the heating section are determined by a regression analysis of the equivalent dead time constant of the heating section.
Signal flow for step 3
Measuring points in the signal flow:
|
Designator Data type |
Description |
|
|---|---|---|
|
MP18_lrIdentS3TauDeadAct LREAL |
Current value of the substitute dead time constant of the heating section.
|
|
|
MP19_lrIdentS3TauDeadMax LREAL |
Maximum value of the substitute dead time constant of the heating section.
|
|
Phase 4: Calculating the values for the controller parameters and terminating the identification
The heating element is switched off (correcting variable = 0 %). The characteristic values detected in phase 3 serve to calculate the optimum values for the controller parameters which are saved in the persistent data.
The termination of the parameter identification is signalled: xIdentDone output = TRUE
Signal flow for step 4