Persistent data

L_TP2P_scPD_TemperatureControlBase

The L_TP2P_scPD_TemperatureControlBase parameter structure contains the controller characteristic values calculated in the course of the parameter identification process ( xIdentCtrlPar input = TRUE).

Designator

Data type

Description

scPersistentData

L_TP2P_scPD

Persistent data contain the controller characteristic values calculated in the course of the parameter identification process (xIdentCtrlPar input = TRUE).

Designator

Data type

Description

lrTempSetFilterTime

LREAL

PT1 filter time constant for the temperature setpoint

With the value '0', filtering is deactivated.

  • Unit: s

  • Initial value: 30.0

lrTempActFilterTime

LREAL

PT1 filter time constant for the actual temperature value

With the value '0', filtering is deactivated.

  • Unit: s

  • Initial value: 5.0

Example:

A task cycle time of 10 ms and the common factor of 500 result in a filter time constant of 5 seconds.

lrTempCtrlGain

BOOL

P parameter of the PID controller

  • Unit: %/°C / %/°F

  • Initial value: 0.0

lrTempCtrlResetTime

LREAL

Reset time (I parameter) of the PID controller

  • Unit: s

  • Initial value: 100.0

lrTempCtrlRateTime

LREAL

Rate time (D parameter) of the PID controller

  • Unit: s

  • Initial value: 100.0

dwIdentVersionInfo

DWORD

Version identifier of the parameters detected by the parameter identification

  • This serves to detect whether valid parameters are available (dwIdentVersionInfo > 0).

  • Moreover, an external persistence mechanism can detect whether new parameters have been identified since the value of dwIdentVersionInfo is increased by 1 each time.

  • Initial value: 0