Inputs

Designator

Data type

Description

xEnableInternalControl

BOOL

TRUE

In the visualisation, the internal control of the axis can be selected via the "Internal Control" axis.

xEnable

BOOL

Execution of the function block

TRUE

The function block is executed.

FALSE

The function block is not executed.

xResetError

BOOL

FALSE ä TRUE

Resetting errors of the "Temperature Control" technology module.

xStop

BOOL

TRUE

The technology module is stopped, i.e. the temperature control is stopped.

  • The output xPWMOut is permanently set to FALSE.

  • The state changes to "STOP".

  • TThe "STOP" state is left when the input xStop = FALSE is set.

  • The input is also switched through with "Internal Control" from the application.

xTemperatureCtrl

BOOL

TRUE

Activate the " Temperature control " or " Control with constant correcting variable " operating mode.

The operating mode is selected via the eModeTempCtrl parameter of the L_TP2P_scPar_TemperatureControlBase

xIdentCtrlPar

BOOL

TRUE

Activate the " Parameter identification " operating mode.

The values to be used are selected via the xIdentAuto parameter of the L_TP2P_scPar_TemperatureControlBase

lrSetTemp

LREAL

Temperature setpoint for the "Temperature control" operating mode

scPar

L_TP2P_scPar_TemperatureControlBase

The parameter structure contains the parameters of the technology module.

scAccessPoints

L_TP2P_scAP_TemperatureControlBase

Structure of the access points

nActSensorIn

INT

Input for coupling the thermal sensor (usually PT100 with interface connection via EPM module)