L_TP2P_scPar_TemperatureControlBase

L_TP2P_scPar_TemperatureControlBase

The L_TP2P_scPar_TemperatureControlBase structure contains the parameters of the technology module.

Designator

Data type

Description

lrSensorValueGain

LREAL

Gain factor for the sensor signal.

Set this value so that the sensor used provides a correct mapping to the temperature unit °C.

  • Unit: -

  • Initial value: 0.1

lrSensorValueOffset

LREAL

Offset for the scaled sensor signal.

Set this value so that the sensor used and the configured gain factor provide a correct zero point mapping (absolute position) to the temperature unit °C.

  • Unit: -

  • Initial value: 0.0

xTempUnitIsCelsius

BOOL

Unit of temperature values

  • Initial value: TRUE

TRUE

All temperature values (setpoint / actual value / configuration) are based on the Celsius [°C] unit.

FALSE

All temperature values (setpoint / actual value / configuration) are based on the Fahrenheit [°F] unit.

lrTempMaxCritical
Absolute

LREAL

Absolute temperature limit for the system. If this value is reached, the correcting variable is set to 0 % and an error is reported.

  • Unit: °C (°F)

  • Initial value: 120.0

lrSetTempReached
Tolerance

LREAL

As long as the deviation between the target and actual temperature does not exceed the value configured here, the status signal xSetTempReached = TRUE is set.

  • Unit: °C (°F)

  • Initial value: 1.0

lrTempMinWindow

LREAL

If the actual value exceeds the setpoint value by more than the difference specified here, the warning signal is set to xTempMin = TRUE.

  • Unit: °C (°F)

  • Initial value: 5.0

lrTempMinHysteresis

LREAL

Hysteresis for the xTempMin warning signal.

  • Unit: °C (°F)

  • Initial value: 1.0

lrTempMaxWindow

LREAL

If the actual value exceeds the setpoint value by more than the difference specified here, the warning signal is set to xTempMax = TRUE.

  • Unit: °C (°F)

  • Initial value: 5.0

lrTempMaxHysteresis

LREAL

Hysteresis for the xTempMax warning signal.

  • Unit: °C (°F)

  • Initial value: 1.0

lrSensorMonitoring
ValueMin

LREAL

If the sensor delivers a resulting temperature value of less than this parameter value, this is recognised as a probe error and an error is reported.

  • Value -1000.0 deactivates this monitoring.

  • Unit: °C (°F)

  • Initial value: -1000.0

lrSensorMonitoring
ValueMax

LREAL

If the sensor provides a resulting temperature value greater than this parameter value, this is recognised as a probe error and an error is reported.

  • Value 1000.0 deactivates this monitoring.

  • Unit: °C (°F)

  • Initial value: 1000.0

lrSensorMonitoringChange
Max

LREAL

If the change of the resulting temperature value within a cycle is greater than the value specified here, this is recognised as a probe error and an error is reported.

  • Value 0.0 deactivates this monitoring.

  • Unit: °C (°F)

  • Initial value: 0.0

xCtrlIntegralClamping

BOOL

Controller behaviour

  • Initial value: TRUE

TRUE

As long as the temperature controller is within the correcting variable limitation, the added-up I component is frozen.

lrControlValueMinPct

LREAL

Minimum value for the correcting variable limitation of the temperature controller.

  • Unit: %

  • Initial value: 0.0

lrControlValueMaxPct

LREAL

Maximum value for the correcting variable limitation of the temperature controller.

  • Unit: %

  • Initial value: 100.0

lrPWMPeriod

LREAL

Period of the PWM signal generated in the TM.

  • Unit: s

  • Initial value: 1.0

lrDiffCtrlActuatingTime

LREAL

Runtime of a connected differential actuator.

The runtime is the time period required by the control valve from full closing to full opening with permanent activation.

lrDiffCtrlSignalTimeMin

LREAL

Minimum pulse duration at the xDiffPositiveOut and xDiffNegativeOut outputs; for reducing the strain on the electromechanical valve control components.

lrDiffCtrlBreakTimeMin

LREAL

Minimum break duration at the xDiffPositiveOut and xDiffNegativeOut outputs for reducing the strain on the electromechanical valve components. This break duration is also complied with when switching over from positive to negative.

eModeTempCtrl

ENUM

CONTROL setting: A constant correcting variable for the heat section is set, all temperature monitoring is deactivated, cf. parameter lrControlValueFixedPct

REGULATION setting: The heat section is controlled and operated with the controller.

  • Unit: -

  • Initial value: REGULATION

lrControlValueFixedPct

LREAL

Constant correcting variable for the "CONTROL" operating mode.

  • Unit: %

  • Initial value: 10.0

xIdentAuto

BOOL

Sequence of the identification process

  • Initial value: TRUE

TRUE

For the identification process, standard values and automatically calculated values are used.

FALSE

For the identification process, the values stored in the following parameters are used.

lrIdentStep1Temp
ChangeMax

LREAL

Maximum permissible temperature change so that reaching the stationary (ambient) temperature is detected in identification step 1 and step 1 can be terminated.

  • If the parameter xIdentAuto = TRUE, this parameter is not used.

  • Unit: °C/min (°F/min)

  • Initial value: 0.5

lrIdentStep2Control
StepPct

LREAL

Initial correcting variable injection in identification step 2.

  • If the parameter xIdentAuto = TRUE, this parameter is not used.

  • Unit: %

  • Initial value: 4

lrIdentStep2Temp
ChangeMax

LREAL

Maximum permissible temperature change so that reaching the stationary temperature is detected in identification step 2 and step 2 can be terminated.

  • If the parameter xIdentAuto = TRUE, this parameter is not used.

  • Unit: °C/min (°F/min)

  • Initial value: 0.5

lrIdentStep2Temp
DiffMin

LREAL

Minimum value of the temperature increase to be reached in identification step 2 before switching over to identification step 3.

  • If the parameter xIdentAuto = TRUE, this parameter is not used.

  • Unit: °C/min (°F/min)

  • Initial value: 10.0

lrIdentStep2Wait
TimeMin

LREAL

If the stationary temperature ( lrIdent-Step2TempChangeMax parameter) has been reached after this time has elapsed but not the minimum temperature increase from the lrIdentStep2TempDiffMin parameter, the correcting variable will be doubled and the time will be restarted.

  • If the parameter xIdentAuto = TRUE, this parameter is set to value 15.

  • Unit: min

  • Initial value: 10

lrIdentStep2Control
ValueMaxPct

LREAL

If the correcting variable exceeds this value without the minimum temperature increase configured in the lrIdentStep2TempDiffMin parameter having been reached, the identification ends with an error.

  • If the parameter xIdentAuto = TRUE, this parameter is not used.

  • Unit: %

  • Initial value: 50

lrIdentStep3Control
StepPct

LREAL

Value of the correcting variable step for accepting the heat section step response in identification step 3.

If the value is "-1", the correcting variable step for identification step 3 is automatically calculated from the heating process of identification step 2.

  • Unit: %

  • Initial value: -1

lrIdentStep3Temp
DiffMin

LREAL

Minimum value of the temperature increase to be reached in identification step 3 in order for the detected parameters to be regarded as valid.

  • Unit: °C/min (°F/min)

  • Initial value: 20.0

lrIdentStep3Regression
Time

LREAL

A linear regression is used to determine the slope of the heating curve. This parameter defines the time length of the regression interval.

If the parameter xIdentAuto = TRUE, this parameter is not used.

The value must be at least one hundred times the task cycle time. If this is not fulfilled, error no. 17171 (TaskCycleRegressionTimeMismatch) is triggered when the parameter identification is started.

  • Unit: s

  • Initial value: 2.0

xActivateParameter
Switchung

BOOL

Control process

  • Initial value: FALSE

TRUE

Control process with parameter switching active

FALSE

Control process with parameter switching inactive

lrDeviationConstraintA

LREAL

When this system deviation limit value is not reached, the parameter set is activated for optimal disturbance behaviour for the control process with parameter switching.

  • This parameter is only effective for xActivateParameterSwitching = TRUE

  • Unit: °C [°F]

  • Initial value: 1.0

lrDeviationConstraintB

LREAL

When this system deviation limit value is exceeded, the parameter set is activated for optimal guidance behaviour for the control process with parameter switching.

  • This parameter is only effective for xActivateParameterSwitching = TRUE

  • Unit: °C [°F]

  • Initial value: 3.0

lrGainFactorDisturbance
Control

LREAL

Assessment factor for controller gain relating to K crit (for Ziegler-Nichols) for the parameter set for optimal disturbance behaviour for the control process with parameter switching.

  • This parameter is only effective for xActivateParameterSwitching = TRUE

  • Unit: -

  • Initial value: 2.0

lrFilterTimeFactor
DisturbanceControl

LREAL

Assessment factor for the time constant of the setpoint filter relating to dead time of the control section for the parameter set for optimal disturbance behaviour for the control process with parameter switching.

  • This parameter is only effective for xActivateParameterSwitching = TRUE

  • Unit: -

  • Initial value: 6.0

lrGainFactor
ReferenceControl

LREAL

Assessment factor for controller gain relating to K crit (for Ziegler-Nichols) for the parameter set for optimal guidance behaviour for the control process with parameter switching.

  • This parameter is only effective for xActivateParameterSwitching = TRUE

  • Unit: -

  • Initial value: 0.5

lrFilterTimeFactor
ReferenceControl

LREAL

Assessment factor for time constant of the setpoint filter relating to dead time of the control section for the parameter set for optimal guidance behaviour for the control process with parameter switching.

  • This parameter is only effective for xActivateParameterSwitching = TRUE

  • Unit: -

  • Initial value: 3.0