L_TP2P_scPar_TemperatureControlBase
The L_TP2P_scPar_TemperatureControlBase structure contains the parameters of the technology module.
|
Designator Data type |
Description |
|
|---|---|---|
|
lrSensorValueGain LREAL |
Gain factor for the sensor signal. Set this value so that the sensor used provides a correct mapping to the temperature unit °C.
|
|
|
lrSensorValueOffset LREAL |
Offset for the scaled sensor signal. Set this value so that the sensor used and the configured gain factor provide a correct zero point mapping (absolute position) to the temperature unit °C.
|
|
|
xTempUnitIsCelsius BOOL |
Unit of temperature values
|
|
|
TRUE |
All temperature values (setpoint / actual value / configuration) are based on the Celsius [°C] unit. |
|
|
FALSE |
All temperature values (setpoint / actual value / configuration) are based on the Fahrenheit [°F] unit. |
|
|
lrTempMaxCritical
LREAL |
Absolute temperature limit for the system. If this value is reached, the correcting variable is set to 0 % and an error is reported.
|
|
|
lrSetTempReached
LREAL |
As long as the deviation between the target and actual temperature does not exceed the value configured here, the status signal xSetTempReached = TRUE is set.
|
|
|
lrTempMinWindow LREAL |
If the actual value exceeds the setpoint value by more than the difference specified here, the warning signal is set to xTempMin = TRUE.
|
|
|
lrTempMinHysteresis LREAL |
Hysteresis for the xTempMin warning signal.
|
|
|
lrTempMaxWindow LREAL |
If the actual value exceeds the setpoint value by more than the difference specified here, the warning signal is set to xTempMax = TRUE.
|
|
|
lrTempMaxHysteresis LREAL |
Hysteresis for the xTempMax warning signal.
|
|
|
lrSensorMonitoring
LREAL |
If the sensor delivers a resulting temperature value of less than this parameter value, this is recognised as a probe error and an error is reported.
|
|
|
lrSensorMonitoring
LREAL |
If the sensor provides a resulting temperature value greater than this parameter value, this is recognised as a probe error and an error is reported.
|
|
|
lrSensorMonitoringChange
LREAL |
If the change of the resulting temperature value within a cycle is greater than the value specified here, this is recognised as a probe error and an error is reported.
|
|
|
xCtrlIntegralClamping BOOL |
Controller behaviour
|
|
|
TRUE |
As long as the temperature controller is within the correcting variable limitation, the added-up I component is frozen. |
|
|
lrControlValueMinPct LREAL |
Minimum value for the correcting variable limitation of the temperature controller.
|
|
|
lrControlValueMaxPct LREAL |
Maximum value for the correcting variable limitation of the temperature controller.
|
|
|
lrPWMPeriod LREAL |
Period of the PWM signal generated in the TM.
|
|
|
lrDiffCtrlActuatingTime LREAL |
Runtime of a connected differential actuator. The runtime is the time period required by the control valve from full closing to full opening with permanent activation.
|
|
|
lrDiffCtrlSignalTimeMin LREAL |
Minimum pulse duration at the xDiffPositiveOut and xDiffNegativeOut outputs; for reducing the strain on the electromechanical valve control components.
|
|
|
lrDiffCtrlBreakTimeMin LREAL |
Minimum break duration at the xDiffPositiveOut and xDiffNegativeOut outputs for reducing the strain on the electromechanical valve components. This break duration is also complied with when switching over from positive to negative.
|
|
|
eModeTempCtrl ENUM |
CONTROL setting: A constant correcting variable for the heat section is set, all temperature monitoring is deactivated, cf. parameter lrControlValueFixedPct REGULATION setting: The heat section is controlled and operated with the controller.
|
|
|
lrControlValueFixedPct LREAL |
Constant correcting variable for the "CONTROL" operating mode.
|
|
|
xIdentAuto BOOL |
Sequence of the identification process
|
|
|
TRUE |
For the identification process, standard values and automatically calculated values are used. |
|
|
FALSE |
For the identification process, the values stored in the following parameters are used. |
|
|
lrIdentStep1Temp
LREAL |
Maximum permissible temperature change so that reaching the stationary (ambient) temperature is detected in identification step 1 and step 1 can be terminated.
|
|
|
lrIdentStep2Control
LREAL |
Initial correcting variable injection in identification step 2.
|
|
|
lrIdentStep2Temp
LREAL |
Maximum permissible temperature change so that reaching the stationary temperature is detected in identification step 2 and step 2 can be terminated.
|
|
|
lrIdentStep2Temp
LREAL |
Minimum value of the temperature increase to be reached in identification step 2 before switching over to identification step 3.
|
|
|
lrIdentStep2Wait
LREAL |
If the stationary temperature ( lrIdent-Step2TempChangeMax parameter) has been reached after this time has elapsed but not the minimum temperature increase from the lrIdentStep2TempDiffMin parameter, the correcting variable will be doubled and the time will be restarted.
|
|
|
lrIdentStep2Control
LREAL |
If the correcting variable exceeds this value without the minimum temperature increase configured in the lrIdentStep2TempDiffMin parameter having been reached, the identification ends with an error.
|
|
|
lrIdentStep3Control
LREAL |
Value of the correcting variable step for accepting the heat section step response in identification step 3. If the value is "-1", the correcting variable step for identification step 3 is automatically calculated from the heating process of identification step 2.
|
|
|
lrIdentStep3Temp
LREAL |
Minimum value of the temperature increase to be reached in identification step 3 in order for the detected parameters to be regarded as valid.
|
|
|
lrIdentStep3Regression
LREAL |
A linear regression is used to determine the slope of the heating curve. This parameter defines the time length of the regression interval. If the parameter xIdentAuto = TRUE, this parameter is not used. The value must be at least one hundred times the task cycle time. If this is not fulfilled, error no. 17171 (TaskCycleRegressionTimeMismatch) is triggered when the parameter identification is started.
|
|
|
xActivateParameter
BOOL |
Control process
|
|
|
TRUE |
Control process with parameter switching active |
|
|
FALSE |
Control process with parameter switching inactive |
|
|
lrDeviationConstraintA LREAL |
When this system deviation limit value is not reached, the parameter set is activated for optimal disturbance behaviour for the control process with parameter switching.
|
|
|
lrDeviationConstraintB LREAL |
When this system deviation limit value is exceeded, the parameter set is activated for optimal guidance behaviour for the control process with parameter switching.
|
|
|
lrGainFactorDisturbance
LREAL |
Assessment factor for controller gain relating to K crit (for Ziegler-Nichols) for the parameter set for optimal disturbance behaviour for the control process with parameter switching.
|
|
|
lrFilterTimeFactor
LREAL |
Assessment factor for the time constant of the setpoint filter relating to dead time of the control section for the parameter set for optimal disturbance behaviour for the control process with parameter switching.
|
|
|
lrGainFactor
LREAL |
Assessment factor for controller gain relating to K crit (for Ziegler-Nichols) for the parameter set for optimal guidance behaviour for the control process with parameter switching.
|
|
|
lrFilterTimeFactor
LREAL |
Assessment factor for time constant of the setpoint filter relating to dead time of the control section for the parameter set for optimal guidance behaviour for the control process with parameter switching.
|
|