Outputs
|
Designator Data type |
Description |
|
|---|---|---|
|
xInternalControlActive BOOL |
TRUE |
The internal control of the technology module is activated via the visualisation. (xEnableInternalControl input = TRUE) |
|
eTMState |
Current state of the technology module
|
|
|
210 |
CONTROL |
|
|
211 |
REGULATION |
|
|
212 |
IDENTIFICATION |
|
|
xError BOOL |
TRUE |
There is an error in the technology module. |
|
xWarning BOOL |
TRUE |
There is a warning in the technology module. |
|
eErrorID |
ID of the error or warning message if xError = TRUE or xWarning = TRUE. |
|
|
Here you can find information on further error and warning messages: |
||
|
scSignalFlow |
Structure of the signal flow |
|
|
lrActTemp LREAL |
Actual temperature value
|
|
|
xPWMOut BOOL |
TRUE |
Output signal of the internal PWM module for triggering a (solid state) relay |
|
xDiffPositiveOut BOOL |
Positive output signal for actuators (mixing valves) with a differential control |
|
|
TRUE |
Open mixing valve / increase heating power |
|
|
xDiffNegativeOut BOOL |
Negative output signal for actuators (mixing valves) with a differential control |
|
|
TRUE |
Close mixing valve / reduce heating power |
|
|
lrHeatingPowerPct LREAL |
Current correcting variable for the heating power
|
|
|
lrHeatingPowerScaled LREAL |
Current correcting variable for the heating power
|
|
|
wIdentPhase LREAL |
Display of the active phase during the parameter identification Possible values: |
|
|
0 |
Parameter identification is inactive |
|
|
1 |
Parameter identification phase 1 active |
|
|
2 |
Parameter identification phase 2 active |
|
|
3 |
Parameter identification phase 3 active |
|
|
4 |
Parameter identification phase 4 active |
|
|
5 |
Parameter identification is completed |
|
|
xIdentBusy BOOL |
TRUE |
Parameter identification is active |
|
xIdentDone BOOL |
TRUE |
The parameter identification has been completed successfully. |
|
xTempMax BOOL |
TRUE |
Warning signal "Overtemperature" The current actual temperature exceeds the setpoint temperature by more than the value set in the lrTempMaxWindow (parameter structure L_TP2P_scPar_TemperatureControlBase ) parameter. |
|
xTempMin BOOL |
TRUE |
Warning signal "Undertemperature" The current actual temperature falls below the setpoint temperature by more than the value set in the lrTempMinWindow parameter ( L_TP2P_scPar_TemperatureControlBase parameter structure). |
|
xSetTempReached BOOL |
TRUE |
Information signal "Setpoint temperature reached"
|