Outputs

Designator

Data type

Description

xInternalControlActive

BOOL

TRUE

The internal control of the technology module is activated via the visualisation.

(xEnableInternalControl input = TRUE)

eTMState

L_TP2P_States

Current state of the technology module

  • State Machine

210

CONTROL

211

REGULATION

212

IDENTIFICATION

xError

BOOL

TRUE

There is an error in the technology module.

xWarning

BOOL

TRUE

There is a warning in the technology module.

eErrorID

ID of the error or warning message if xError = TRUE or xWarning = TRUE.

Here you can find information on further error and warning messages:

scSignalFlow

L_TP2P_scSF_TemperatureControlBase

Structure of the signal flow

lrActTemp

LREAL

Actual temperature value

xPWMOut

BOOL

TRUE

Output signal of the internal PWM module for triggering a (solid state) relay

xDiffPositiveOut

BOOL

Positive output signal for actuators (mixing valves) with a differential control

TRUE

Open mixing valve / increase heating power

xDiffNegativeOut

BOOL

Negative output signal for actuators (mixing valves) with a differential control

TRUE

Close mixing valve / reduce heating power

lrHeatingPowerPct

LREAL

Current correcting variable for the heating power

  • Unit: %

lrHeatingPowerScaled

LREAL

Current correcting variable for the heating power

  • Value range: 0.0 ... 1.0 (1.0 = 100 %)

wIdentPhase

LREAL

Display of the active phase during the parameter identification

Possible values:

0

Parameter identification is inactive

1

Parameter identification phase 1 active

2

Parameter identification phase 2 active

3

Parameter identification phase 3 active

4

Parameter identification phase 4 active

5

Parameter identification is completed

xIdentBusy

BOOL

TRUE

Parameter identification is active

xIdentDone

BOOL

TRUE

The parameter identification has been completed successfully.

xTempMax

BOOL

TRUE

Warning signal "Overtemperature"

The current actual temperature exceeds the setpoint temperature by more than the value set in the lrTempMaxWindow (parameter structure L_TP2P_scPar_TemperatureControlBase ) parameter.

xTempMin

BOOL

TRUE

Warning signal "Undertemperature"

The current actual temperature falls below the setpoint temperature by more than the value set in the lrTempMinWindow parameter ( L_TP2P_scPar_TemperatureControlBase parameter structure).

xSetTempReached

BOOL

TRUE

Information signal "Setpoint temperature reached"

  • The temperature setpoint (lrSetTemp input) has been reached.

  • The deviation between the setpoint temperature and the actual temperature does not exceed the tolerance set in the lrSetTempReachedTolerance parameter ( L_TP2P_scPar_TemperatureControlBase parameter structure).