L_TP2P_scAP_TemperatureControlBase
Structure of the access points
The access points (AP) can be used to influence signals. In the initial state, the access points do not have any effect.
Each access point acts as an alternative branch and is activated via an OR operation or a switch.
|
Designator Data type |
Description |
|
|---|---|---|
|
AP01_xActSensorIn BOOL |
Selection of the sensor input signal for the temperature detection
|
|
|
TRUE |
The value of the AP01_lrActSensorIn access point is used for the temperature detection. |
|
|
FALSE |
The sensor input signal of the technology module (nActSensorIn input) is used for the temperature detection. |
|
|
AP01_lrActSensorIn LREAL |
Alternative value for the sensor input signal, activation with AP01_xActSensorIn = TRUE
|
|
|
AP02_xFilteredTempSet BOOL |
Selection of the temperature setpoint signal for the control
|
|
|
TRUE |
The value of the AP02_lrFilteredTempSet access point is used for the control. |
|
|
FALSE |
The original temperature setpoint from the technology module is used for the control. |
|
|
AP02_lrFilteredTempSet LREAL |
Alternative value for the temperature setpoint signal, activation with AP02_xFilteredTempSet = TRUE
|
|
|
AP03_xFilteredTempAct BOOL |
Selection of the actual temperature value signal for the control
|
|
|
TRUE |
The value of the AP03_lrFilteredTempAct access point is used for the control. |
|
|
FALSE |
The original actual temperature value from the technology module is used for the control. |
|
|
AP03_lrFilteredTempAct LREAL |
Alternative value for the actual temperature value signal, activation with AP03_xFilteredTempAct = TRUE
|
|
|
AP04_xControlValuePct BOOL |
Selection of the correcting variable signal for the control
|
|
|
TRUE |
The value of the AP04_lrControlValuePct access point is used for the control. |
|
|
FALSE |
The original correcting variable value from the technology module is used for the control. |
|
|
AP04_lrControlValuePct LREAL |
Alternative value for the correcting variable signal, activation with AP04_xControlValuePct = TRUE
|
|
|
AP05_xTempSetFilterTime BOOL |
Selection of the PT1 filter time constant for the temperature setpoint
|
|
|
TRUE |
The value of the AP05_lrTempSetFilterTime access point is used for the control. |
|
|
FALSE |
The PT1 filter time constant from the technology module (lrTempSetFilterTime from L_TP2P_scPD_TemperatureControlBase ) is used for the control. |
|
|
AP05_lrTempSetFilterTime LREAL |
Alternative value for the PT1 filter time constant, activation with AP05_xTempSetFilterTime = TRUE
|
|
|
AP06_xTempActFilterTime BOOL |
Selection of the PT1 filter time constant for the actual temperature value
|
|
|
TRUE |
The value of the AP06_lrTempActFilterTime access point is used for the control. |
|
|
FALSE |
The PT1 filter time constant from the technology module (lrTempActFilterTime from L_TP2P_scPD_TemperatureControlBase ) is used for the control. |
|
|
AP06_lrTempActFilterTime LREAL |
Alternative value for the PT1 filter time constant, activation with AP06_xTempActFilterTime = TRUE
|
|
|
AP07_xTempCtrlGain BOOL |
Selection of the P parameter of the PID controller
|
|
|
TRUE |
The value of the AP07_lrTempCtrlGain access point is used for the control. |
|
|
FALSE |
The P parameter of the PID controller from the technology module (lrTempCtrlGain from L_TP2P_scPD_TemperatureControlBase ) is used for the control. |
|
|
AP07_lrTempCtrlGain LREAL |
Alternative value for the P parameter of the PID controller, activation with AP07_xTempCtrlGain = TRUE
|
|
|
AP08_xTempCtrlResetTime BOOL |
Selection of the reset time (I parameter) of the PID controller
|
|
|
TRUE |
The value of the AP08_lrTempCtrlResetTime access point is used for the control. |
|
|
FALSE |
The reset time (I parameter) of the PID controller from the technology module (lrTempCtrlResetTime from L_TP2P_scPD_TemperatureControlBase ) is used for the control. |
|
|
AP08_lrTempCtrlResetTime LREAL |
Alternative value for the reset time (I parameter) of the PID controller, activation with AP08_xTempCtrlResetTime = TRUE
|
|
|
AP09_xTempCtrlRateTime BOOL |
Selection of the rate time (D parameter) of the PID controller
|
|
|
TRUE |
The value of the AP09_lrTempCtrlRateTime access point is used for the control. |
|
|
FALSE |
The rate time (D parameter) of the PID controller from the technology module (lrTempCtrlRateTime from L_TP2P_scPD_TemperatureControlBase ) is used for the control. |
|
|
AP09_lrTempCtrlRateTime LREAL |
Alternative value for the rate time (D parameter) of the PID controller, activation with AP09_xTempCtrlRateTime = TRUE
|
|
| AP_xDisableInternalControl BOOL | TRUE | Disable the InternalControl functionality of the technology module. If TRUE, the technology module cannot be controlled by the visualization template. |