Use of the access points

The use of the access points is only required in exceptional cases.

The following application example explains the use of the access points for correcting values of the controller parameters.

Application example

Due to path-specific features, the value of the lrTempCtrlGain controller parameter detected by the parameter identification shall not be used directly for the heat section but shall be reduced by the factor '2' (scaling to 50 %).

The required additional external wiring of the L_TP2P_TemperatureControlBase function block is shown here:

  • In network 1, the controller parameter value is adapted. Here, the MP07_lrTempCtrlGain measuring point which provides the value detected by the parameter identification (see Signal flow diagram: Thermostat ) is multiplied by the factor '0.5' and is switched to the AP07_lrTempCtrlGain access point.

  • In network 2, the AP07_lrTempCtrlGain is activated by setting the AP07_xTempCtrlGain signal to TRUE.

  • In network 3, the implementation of the "FB_TCB" module instance is included with minimum circuitry.