Monitoring

Time-out monitoring
The response to the missing Modbus messages can be configured via the following parameters.
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2858:001
(P515.01)
Modbus monitoring: Response to time-out
(Modbus monit.: Resp. Time-out)
Selection of the response executed if no valid messages have been received via the Modbus for a longer time than the time-out period set in 0x2858:002 (P515.02).
Associated event ID:
–
33185 | 0x81A1 - Modbus: network time-out
 
0
No response
1
Warning
2
Trouble
3
Fault
0x2858:002
(P515.02)
Modbus monitoring: Time-out time
(Modbus monit.: Time-out time)
0.0 ... [2.0] ... 300.0 s
Time-out period for monitoring the message reception via Modbus.