Define V/f characteristic shape

Various characteristic shapes are available which are described in detail in the following subchapters.
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2B00
(P302.00)
V/f characteristic shape
(V/f charac.shape)
–
Setting can only be changed if the inverter is disabled.
 
Selection of the V/f characteristic shape for the adaptation to different load profiles.
0
Linear
Linear characteristic for drives with constant load torque over the speed.
1
Quadratic
Square-law characteristic for drives with a square-law load torque over the speed.
–
Square-law V/f characteristics are preferably used for centrifugal pumps and fan drives.
 
–
Please always check whether the corresponding application is suitable for operation with a square-law V/f characteristic!
 
–
If your pump drive or fan drive is not suitable for operation with a square-law V/f characteristic, use the linear V/f characteristic instead.
 
2
Multipoint  
Multipoint characteristic for the purpose of adaptation to specific load profiles.
Linear characteristic with additional characteristic point for adaptation to applications with special torque characteristics.
3
Eco  
Linear characteristic with energy optimisation in the partial load operational range.
4
Adaptive  
User-definable characteristic - adaptive curve.
Freely definable characteristic curve with 11 parameterizable grid points (voltage/frequency values).