Controller.USB-Interface

This functionality has been available since Controller firmware version 1.13.0. Using a USB stick is a critical attack vector for hackers and cyberattacks. The USB interface is therefore deactivated by default.

As of V1.13 of the controller firmware, a plugged-in USB stick is not mounted by default so that no malicious code can be executed on the controller in this way.

For Controllers in factory default, mounting a USB stick is initially active to enable initial commissioning.

This state is indicated by a flashing RDY LED every second.

After installing a firmware update, mounting the USB stick is deactivated.

The mounting of the USB stick is also deactivated as soon as a boot project is loaded onto the Controller.

If a boot project is already available during the initial startup of a Controller in factory default, mounting the USB stick will be deactivated.

The USB interface can be parametrized in two different states:

- Deactivated [0]

- Activated [1]

This is done by the parameter 0x5902.

A diagram of a customer service

Description automatically generated with medium confidence

USB-Interface

Activating the USB interface deactivates the security functionality, leaving the PLC vulnerable to cyberattacks.

  • The USB interface must be disabled to fulfill the CR 3.2 of the IEC 62443 which is the standard for the Cyber Resilience Act of the EU.Activating the USB interface deactivates the security functionality, leaving the PLC vulnerable to cyberattacks.

Backup & Restore

The backup and restore functionality is not included in version 2.0.0 and will be added in a future release.

Controller.USB-Stick:Security functionality verification

To verify that the USB deactivation is functioning correctly, you must use a FAT- or FAT32-formatted USB stick. Plug the USB stick and restart the Controller. Login with PLC Designer, open and refresh the "Files" editor for the controller. If the files editor does not show a placeholder "$UsbStorage$" the deactivation is working correctly. This security feature only works on a Controller with a non-flashing RDY LED.

  • When a Controller is first started, the RDY LED flashes every second for 100 ms. If it is not flashing, then the Controller is not in factory default state and has been used by someone else.