Data Access authorization

The OPC UA PubSub functionality requires data access to the variables which shall be communicated. In case of data access to the PLC, the IEC variables must be enabled for OPC UA communication via the Symbol Configuration.

In case of a Publisher, read access rights are required for the IEC variable.

In case of a Subscriber, write access rights are required for the target IEC variable.

If the user management of the device is activated, an additional permission for this data access is needed.

Controller FW >= V2.0

The OPC UA PubSub functionality itself connects always to this data source as an "PubSub_OPCUAServer" user. This user and a corresponding user group is generated automatically in the device user management if PubSub is enabled. The user name and password are generated by the FW internally thus no interaction with the user management is needed. It´s similar to the "Anonymous_OPCUAServer" user for anonymous access.

If the user management is active, the access rights for PubSub (the PubSub_OPCUAServer group) have to be configured.

This can be done in the "Access Rights" dialog of the »PLC Designer« or on the "Symbol Rights" dialog if symbol sets are used.

Controller FW < V2.0

The OPC UA PubSub functionality itself connects always to the data source as an "anonymous user".

Thus, only IEC variables can be accessed which are granted to the Anonymous_OPCUAServer group.