With an HMI project, you can display the trend recording of a remote PLC in the "trend" visualization element. Requirement: Trend recording is defined in the remote PLC and a symbol configuration is added.
-
Open the initially created HMI project.
-
Select the Data Sources Manager object.
-
Click .
-
Specify a name for the data source. Example:
Data_Source_Trendand click Add.The Initialize Data Source Wizard – Provider settings dialog opens.
The
V3connection type is set by default. -
In Name or address of device, specify the network name of the active controller whose data should be displayed in a visualization. Example:
Device_AThe connection from the development system to the controller is established and the available variables are read. The Initialize Data Source Wizard – Browse data items dialog opens. The variables of the
Device_Acontroller that can be accessed are listed in a table. -
For the visualization of data from a remote trend recording, you have to activate non-explicit variables. The required data is exchanged between the HMI and the remote device via internal communications services.
Click Finish.
The data source is created initially and inserted below the data source manager.
-
Now create your visualization as usual. Open the editor for the visualization and add the Trend element.
The Trend Configuration dialog opens.
-
Select a task for trend visualization.
-
Select the element.
-
Configure the following settings in the Properties view:
:
Data_Source_Trend:
Application -
Select the trend display and click .
-
Activate all actions and close the dialog.
Additional buttons are added to the trend recording.