Creating an Alarm Table

You can use the alarm table created in the following example to visualize the alarms of a specific alarm group.

Requirement: In your project, alarms are defined in alarm groups and they are assigned to an alarm class. The following instructions are based on the example that is described in the "Configuring Alarm Management" chapter.

  1. Open the visualization editor.

  2. Drag the Alarm Table element from the Alarm Manager group to the visualization editor.

    The Alarm Table visualization element is visible in the editor.

  3. In the Alarm configuration / Alarm groups property, define the alarm groups that you want to visualize. Click into the value field.

    The Select Alarm Group dialog opens.

  4. Clear the All option and select the PartsShortage alarm group. Click the _visu_img_add_selected_alarm_group.png button to add the group to the selected alarm groups.

  5. In the Alarm configuration / Alarm classes property, define the alarm classes that you want to visualize. Click into the value field.

    The Select Alarm Class dialog opens.

  6. Clear the All option and select the PartsShortage alarm class. Click the _visu_img_add_selected_alarm_group.png button to add the alarm class to the selected alarm classes.

  7. Add an additional column. Click the Columns / Create new button.

    adds the [2] column to the properties. The Symbol column is added to the table.

  8. Select the State data type for column [2].

    The default State column heading is shown in the table.

  9. Name the Column heading column "Status".

  10. Specify the appearance of the selected table cell. Set the Selection / Selection color property to Green.

  11. In the Control variables / Confirm selection property, specify the variable bQuitAlarm for confirming messages.

  12. Adapt the other properties to their requirements. For a complete description of the properties, see the help for the Alarm Table visualization element.

Inserting elements for alarm acknowledgement

In , predefined buttons are available for controlling the alarms in an alarm table.

Requirement: An Alarm Table element exists in the visualization.

  1. Select the visualization element in the editor.

  2. Click Visualization → Insert Elements for Acknowledging Alarms.

    The Alarm Table Wizard dialog opens.

  3. Click OK to accept all settings.

    Four buttons are added to control the alarm table.

    _visu_alarm_table_online.png