You can insert an input element in the visualization which the operator can use to delete the previously recorded alarm history at runtime. The history displayed until then is removed and the display starts over.
-
In the application (example: in the program
PLC_PRG), implement the following code:itfAlarmConfiguration : AlarmManager.IAlarmConfiguration; itfAlarmConfiguration7 : AlarmManager.IAlarmConfiguration7; xKeepActiveAlarms : BOOL := TRUE; xClearHistory: BOOL; IF xClearHistory THEN FOR i := 0 TO AlarmGlobals.g_AlarmHandler.AlarmConfigurationCount - 1 DO itfAlarmConfiguration := AlarmGlobals.g_AlarmHandler.GetAlarmConfiguration(i); IF __QUERYINTERFACE(itfAlarmConfiguration, itfAlarmConfiguration7) THEN itfAlarmConfiguration7.ClearHistory(xKeepActiveAlarms := xKeepActiveAlarms); END_IF END_FOR END_IFWhen
xClearHistorygets the valueTRUE, the current history will be deleted. Recommendation:xKeepActiveAlarmsshould beTRUEso that active alarms are excluded from the delete operation. If this does not happen, then it does not interrupt the continued recording, but log outputs can be changed for the additional state transitions. -
In the alarm visualization, add a button for deleting the history. Configure its Toggle property with the variable
PLC_PRG.xClearHistory.