Causes and remedies

671155580
0x2801057C
SD card was removed during runtime
Cause
Remedy
Severity/response
The SD card was removed during operation.
Insert the SD card back into the device.
Fault
 
671159298
0x28011402
Opening the parameter description failed
Cause
Remedy
Severity/response
Parameter description is missing or faulty.
No or incorrect parameter description on the device.
Update boot project or device firmware.
–
Update boot project. This also updates the parameter set description.
 
–
If updating the boot project does not fix the error, update the device firmware. The device parameters are also updated as a result.
 
Fault
 
671159299
0x28011403
Opening the parameter set failed
Cause
Remedy
Severity/response
Parameter set file is missing or faulty.
No or faulty parameter set file on the device.
Update boot project or restart device.
–
Update boot project. This also updates the parameter set.
 
–
Restart the device if necessary.
 
Fault
 
671159300
0x28011404
Loading parameter set is failed
Cause
Remedy
Severity/response
Loading the parameter set has failed.
Save the parameter set and restart the device.
Fault
 
671162931
0x28012233
CRC in "IdenCom.ini" file is incorrect
Cause
Remedy
Severity/response
Internal error in the fieldbus configuration.
Restart the device. If the error persists, contact the manufacturer.
Fault
 
671162932
0x28012234
Action not allowed when PLC is running
Cause
Remedy
Severity/response
The action must not be executed as the PLC application is running. (The status of the PLC application is displayed in 0x5810:001.)
Stop the PLC application and then perform the action again.
Fault
 
671162933
0x28012235
Unsupported Fieldbus system
Cause
Remedy
Severity/response
Invalid fieldbus configuration.
Adapt the fieldbus configuration.
Fault
 
671162934
0x28012236
Network module changed (Change active after restart)
Cause
Remedy
Severity/response
A change has been made to the network module through parameter settings or a changed parameter set. These changes only take effect after the device has been restarted.
For information only. No remedy necessary.
Information
 
671421185
0x28051301
Boot application - More Application Credit required
Cause
Remedy
Severity/response
The loaded application requires more "Application Credit" than is available on the SD card.
Use SD card with sufficient "Application Credit".
Trouble
 
671421186
0x28051302
Application requires dual-use license
Cause
Remedy
Severity/response
The application requires a device with "dual use license".
Use device with "dual use license".
Trouble
 
671421187
0x28051303
Powercaps not fully charged
Cause
Remedy
Severity/response
As long as the buffer capacitors are not charged, the start of an application is prevented.
Take into account the charging time of the buffer capacitors during the boot process.
Trouble
 
671421188
0x28051304
SD card is write protected - Running application is prevented
Cause
Remedy
Severity/response
Write protection is activated for the SD card. This makes it impossible to start an application.
Remove write protection from the SD card and restart the device.
Trouble
 
671444993
0x28057001
Application Credit - Application Credit exceeded
Cause
Remedy
Severity/response
The Application Credit configured for an area has been exceeded.
Analyze detailed error message in the logbook.
Fault
 
671444994
0x28057002
Application Credit - Configuration exceeded
Cause
Remedy
Severity/response
More Application Credit has been distributed to the individual areas than are available on the SD card.
–
Check your available Application Credit.
 
–
Check the configuration of the use of Application Credit.
 
–
If necessary, use an SD card with more Application Credit.
 
Fault
 
671444995
0x28057003
Application Credit - Information of maximum used Application Credit was corrupted
Cause
Remedy
Severity/response
The license manager automatically saves the information on the maximum Application Credit used with the current PLC project in a fail-safe manner. This information is incorrect. There may have been an attempt at manipulation.
–
Restart the device (the information is rewritten).
 
–
Download PLC project again.
 
Fault
 
671444996
0x28057004
Application Credit - Available Application Credit has been exceeded during the last power cycle
Cause
Remedy
Severity/response
During the current boot cycle, it was detected that the available Application Credit was exceeded during the previous operation of the controller.
–
Analyze detailed error message in the logbook.
 
–
Adapt the PLC application so that fewer Application Credit is required.
 
–
If necessary, use an SD card with more Application Credit.
 
Fault
 
671444997
0x28057005
Application Credit - License Manager monitoring activated (bootproject active)
Cause
Remedy
Severity/response
Monitoring of the Application Credit used by the license manager has been activated, as there is a persistently stored boot project.
For information only. No remedy necessary.
Information
 
671444998
0x28057006
Application Credit - License Manager monitoring deactivated (NO bootproject active)
Cause
Remedy
Severity/response
Monitoring of the Application Credit used by the license manager has been deactivated, as there is no persistently stored boot project.
For information only. No remedy necessary.
Information
 
671444999
0x28057007
Application Credit - Budget configuration was corrupted
Cause
Remedy
Severity/response
The file that is used to split the Application Credit into individual areas is defective.
Download PLC project again and create boot project if necessary.
Warning
 
671445000
0x28057008
Application Credit - Budget configuration was created, total available Application Credit was assigned to FAST-Toolbox
Cause
Remedy
Severity/response
The file that is used to split the Application Credit into individual areas has been created. The FAST toolbox was assigned the amount of Application Credit specified in the logbook entry.
For information only. No remedy necessary.
Information
 
671445001
0x28057009
Application Credit - Configuration violation during the last power cycle
Cause
Remedy
Severity/response
During the current boot cycle, it was determined that more Application Credit was used during the previous operation of the controller than was distributed to the individual areas or was available.
–
Change the distribution of the Application Credit to the individual areas so that it is no longer exceeded.
 
–
If necessary, use an SD card with more Application Credit.
 
Fault
 
671445002
0x2805700A
Application Credit - Start of the application is delayed due to insufficient Application Credit
Cause
Remedy
Severity/response
The start of the PLC application was delayed because there is not enough Application Credit on the SD card. The logbook entry shows which delay time is effective.
–
Adapt the PLC application so that fewer Application Credit is required.
 
–
If necessary, use an SD card with more Application Credit.
 
Fault
 
671445003
0x2805700B
Application Credit - Usage higher than configured (additional Application Credit on SD-card available)
Cause
Remedy
Severity/response
More Application Credit was used than was distributed to the individual areas. However, as there is additional Application Credit on the SD card, this could be used.
Change the distribution of the Application Credit to the individual areas so that it is no longer exceeded. The Application Credit available on the SD card is sufficient for this.
Warning
 
671445004
0x2805700C
Application Credit - Change of configuration was refused
Cause
Remedy
Severity/response
The license manager has rejected the newly downloaded distribution of the Application Credit for the individual areas, as at least one area already uses more Application Credit than is configured in the new distribution.
Change the distribution of the Application Credit to the individual areas so that it is no longer exceeded.
Warning
 
671481857
0x28060001
SD card is write protected
Cause
Remedy
Severity/response
The inserted SD card is write-protected.
For the SD card, slide the lock switch to the "Unlock" position to remove the physical write protection.
Fault
 
671481904
0x28060030
PowerDown detected
Cause
Remedy
Severity/response
Device is shutting down.
For information only. No remedy necessary.
Information
 
671482880
0x28060400
PowerDown - Retain data not persistent
Cause
Remedy
Severity/response
The soft PLC is working incorrectly or is not active. The retain data of the PLC may not have been saved.
–
Restart the device or update the firmware.
 
–
If the error persists, contact the manufacturer.
 
Fault
 
671547411
0x28070013
Initialization of the real-time clock failed
Cause
Remedy
Severity/response
Error initializing the real-time function. Time may not be usable.
Restart device and check logbook.
Fault
 
671547418
0x2807001A
Charge state of buffer capacitors Real-time clock is low
Cause
Remedy
Severity/response
Device was disconnected from the power supply for too long.
Supply the device with power and set the system time.
Warning
 
671612938
0x2808000A
Device starts without SD card
Cause
Remedy
Severity/response
Device starts without SD card.
If appropriate, insert SD card.
Fault
 
671678788
0x28090144
Firmware is not compatible with this device
Cause
Remedy
Severity/response
The selected firmware does not match the device.
Ensure that the selected firmware exactly matches the target device.
Example: A c550 controller can only be updated with a c550 firmware.
Fault
 
671678814
0x2809015E
SD card is not from this device - abort backup
Cause
Remedy
Severity/response
Internal reviews are performed prior to implementation. Result: The inserted SD card was not recognized by the device. The backup was canceled.
Start device with a new/empty SD card.
Note: If there is no new/empty SD card, you can also delete data from the existing SD card. However, do not delete the license data! (Directory "Licenses_do_not_delete" including content)
Fault
 
671678815
0x2809015F
Backup is not compatible with this device - abort restore
Cause
Remedy
Severity/response
The present backup does not match the device.
Ensure that the backup at hand exactly matches the target device.
Example: A backup from the c550 controller can only be restored to a c550 controller.
Fault
 
671678816
0x28090160
SD card is not from this device - abort Up/Downgrade
Cause
Remedy
Severity/response
Internal reviews are performed prior to implementation. Result: The inserted SD card was not recognized by the device. The upgrade/downgrade was canceled.
Start device with a new/empty SD card.
Note: If there is no new/empty SD card, you can also delete data from the existing SD card. However, do not delete the license data! (Directory "Licenses_do_not_delete" including content)
Fault
 
671678817
0x28090161
SD card not mounted
Cause
Remedy
Severity/response
The inserted SD card was not recognized by the device.
–
Check whether the SD card is inserted/engaged correctly.
 
–
Test another SD card.
 
Fault
 
671678818
0x28090162
SD card is write protected
Cause
Remedy
Severity/response
The inserted SD card is write-protected.
For the SD card, slide the lock switch to the "Unlock" position to remove the physical write protection.
Fault
 
671678819
0x28090163
SD card does not have enough free space
Cause
Remedy
Severity/response
There is not enough free space on the SD card.
Remove unneeded data from the SD card until at least 200 MB of free space is available.
Fault
 
671678820
0x28090164
USB stick not mounted
Cause
Remedy
Severity/response
The inserted USB stick was not recognized by the device.
–
Check if the USB stick is inserted correctly.
 
–
Only use USB sticks approved by the manufacturer.
 
Fault
 
671678821
0x28090165
USB stick does not have correct backup structure
Cause
Remedy
Severity/response
Backup file on the USB stick does not exist, is duplicated or is in the wrong directory.
Check the content of the USB stick. To do this, copy the corresponding data backup on the USB stick from the "firmware\archive__" to "firmware\active" directory. However, the directory "firmware\active" may only contain one file at a time.
Fault
 
671678822
0x28090166
USB stick does not have enough free space
Cause
Remedy
Severity/response
There is not enough free space on the USB stick.
Use a USB stick with at least 365 MB free space.
Fault
 
671678825
0x28090169
SD card contains too much stored project data
Cause
Remedy
Severity/response
The SD card is used to store project data of the controller. The sum of the project data stored on the SD card is too large (>165 MB).
Remove unneeded project data from the SD card until the value falls below the maximum size for project data (165 MB).
Fault
 
671678826
0x2809016A
Backup succeeded
Cause
Remedy
Severity/response
The backup was created successfully.
Remove USB stick from controller and restart controller.
Information
 
671678827
0x2809016B
Device command is blocked by a running PLC application
Cause
Remedy
Severity/response
Device command/setting is blocked by a running PLC application.
Execute device command/setting if the status of the application (display in 0x5810:001) is not equal to "1: Running".
Fault
 
671678830
0x2809016E
Firmware is not compatible with this hardware version
Cause
Remedy
Severity/response
The firmware is not released for this device. The hardware version is too low.
Select firmware version that is compatible with the hardware version of the device.
Fault
 
671744011
0x280A000B
Too many I/Os for task cycle time (I/O module msg. 11)
Cause
Remedy
Severity/response
Too many I/O modules for the selected task cycle time.
Increase task cycle time.
Fault
 
671744012
0x280A000C
Parameter access I/O modules is restricted (I/O module msg. 12)
Cause
Remedy
Severity/response
The controller could not access all parameters of the I/O modules. Process data communication (PDO) is not restricted.
a.
When the controller is started, the task load is close to the cycle time and there are very many configurable I/O modules connected to the backplane bus of the controller.
 
b.
During operation the task load is close to the cycle time and at the same time the tabs of configurable I/O modules are displayed in the "PLC Designer".
 
Increase cycle time of bus cycle tasks.
Fault
 
671744032
0x280A0020
Internal error (I/O module msg. 32)
Cause
Remedy
Severity/response
Internal error
Restart device. If the error persists, contact the manufacturer.
Fault
 
671744033
0x280A0021
Internal error (I/O module msg. 33)
Cause
Remedy
Severity/response
Internal error
Restart device. If the error persists, contact the manufacturer.
Fault
 
671744099
0x280A0063
Too many I/Os for task cycle time (I/O module msg. 99)
Cause
Remedy
Severity/response
Error while creating the task assigned to the backplane bus. The number of I/O modules or the size of the process image cannot be processed by the controller. The error occurs when starting the PLC application.
Reduce the number of I/O modules.
Fault
 
671744100
0x280A0064
Too many I/Os for task cycle time (I/O module msg. 100)
Cause
Remedy
Severity/response
Error during processing of backplane bus telegrams. This error occurs during operation.
a.
Error in the PLC application: The task runtime is longer than the set task interval. The jitter of the backplane bus task is too high (>120 µs).
 
b.
EMC influences (transmission interference): The telegrams are transmitted in insufficient quality.
 
c.
Mechanical influences: Short circuits of the signal cables due to jammed sockets. Missing or dirty contacts. The telegrams are transmitted in insufficient quality.
 
d.
An I/O module is defective.
 
e.
The number of I/O modules or the size of the process image cannot be processed by the controller.
 
f.
Controller is defective. The MF LEDs light up on all modules.
 
a.
Check PLC application for possible causes of runtime extension or jitter and correct if necessary.
 
b.
Check the shielding. Check whether the error is related to special events (e.g. switching on the drives).
 
c.
Check and clean contacts between I/O modules and sockets.
 
d.
Replace I/O modules one by one to find the defective module.
 
e.
Reduce the number of I/O modules.
 
f.
The MF LEDs light up for all modules: Measure the voltage at the 5 V contacts of the last module at the backplane bus (pin 3 and 5). Replace controller.
 
Fault
 
671744101
0x280A0065
Too many I/Os for task cycle time (I/O module msg. 101)
Cause
Remedy
Severity/response
Error during processing of backplane bus telegrams. This error occurs during operation.
a.
Error in the PLC application: The task runtime is longer than the set task interval. The jitter of the backplane bus task is too high (>120 µs).
 
b.
EMC influences (transmission interference): The telegrams are transmitted in insufficient quality.
 
c.
Mechanical influences: Short circuits of the signal cables due to jammed sockets. Missing or dirty contacts. The telegrams are transmitted in insufficient quality.
 
d.
An I/O module is defective.
 
e.
The number of I/O modules or the size of the process image cannot be processed by the controller.
 
f.
Controller is defective. The MF LEDs light up on all modules.
 
a.
Check PLC application for possible causes of runtime extension or jitter and correct if necessary.
 
b.
Check the shielding. Check whether the error is related to special events (e.g. switching on the drives).
 
c.
Check and clean contacts between I/O modules and sockets.
 
d.
Replace I/O modules one by one to find the defective module.
 
e.
Reduce the number of I/O modules.
 
f.
The MF LEDs light up for all modules: Measure the voltage at the 5 V contacts of the last module at the backplane bus (pin 3 and 5). Replace controller.
 
Fault
 
671744102
0x280A0066
Too many I/Os for task cycle time (I/O module msg. 102)
Cause
Remedy
Severity/response
Error during processing of backplane bus telegrams. This error occurs during operation.
a.
Error in the PLC application: The task runtime is longer than the set task interval. The jitter of the backplane bus task is too high (>120 µs).
 
b.
EMC influences (transmission interference): The telegrams are transmitted in insufficient quality.
 
c.
Mechanical influences: Short circuits of the signal cables due to jammed sockets. Missing or dirty contacts. The telegrams are transmitted in insufficient quality.
 
d.
An I/O module is defective.
 
e.
The number of I/O modules or the size of the process image cannot be processed by the controller.
 
f.
Controller is defective. The MF LEDs light up on all modules.
 
a.
Check PLC application for possible causes of runtime extension or jitter and correct if necessary.
 
b.
Check the shielding. Check whether the error is related to special events (e.g. switching on the drives).
 
c.
Check and clean contacts between I/O modules and sockets.
 
d.
Replace I/O modules one by one to find the defective module.
 
e.
Reduce the number of I/O modules.
 
f.
The MF LEDs light up for all modules: Measure the voltage at the 5 V contacts of the last module at the backplane bus (pin 3 and 5). Replace controller.
 
Fault
 
671744103
0x280A0067
Too many I/Os for task cycle time (I/O module msg. 103)
Cause
Remedy
Severity/response
Error during processing of backplane bus telegrams. This error occurs during operation.
a.
Error in the PLC application: The task runtime is longer than the set task interval. The jitter of the backplane bus task is too high (>120 µs).
 
b.
EMC influences (transmission interference): The telegrams are transmitted in insufficient quality.
 
c.
Mechanical influences: Short circuits of the signal cables due to jammed sockets. Missing or dirty contacts. The telegrams are transmitted in insufficient quality.
 
d.
An I/O module is defective.
 
e.
The number of I/O modules or the size of the process image cannot be processed by the controller.
 
f.
Controller is defective. The MF LEDs light up on all modules.
 
a.
Check PLC application for possible causes of runtime extension or jitter and correct if necessary.
 
b.
Check the shielding. Check whether the error is related to special events (e.g. switching on the drives).
 
c.
Check and clean contacts between I/O modules and sockets.
 
d.
Replace I/O modules one by one to find the defective module.
 
e.
Reduce the number of I/O modules.
 
f.
The MF LEDs light up for all modules: Measure the voltage at the 5 V contacts of the last module at the backplane bus (pin 3 and 5). Replace controller.
 
Fault
 
671744104
0x280A0068
Timeout backplane bus communication (I/O module msg. 104)
Cause
Remedy
Severity/response
The data exchange between the backplane bus and the PLC application is not possible within the specified time.
a.
Follow-up error of the "Too many I/O modules..." error (I/O module messages 100 ... 103).
 
b.
Error in the PLC application: The task runtime is violated.
 
c.
Backplane bus structure: Many passive modules are plugged in between the I/O modules (EPM-S7xx/EPM-S9xx).
 
a.
Check the error sequence in the logbook and eliminate the errors "Too many I/O modules...". (I/O module message 100 ... 103).
 
b.
Correct PLC application.
 
c.
Remove passive I/O modules, change structure.
 
Fault
 
671744105
0x280A0069
Timeout backplane bus communication (I/O module msg. 105)
Cause
Remedy
Severity/response
The data exchange between the backplane bus and the PLC application is not possible within the specified time.
a.
Follow-up error of the "Too many I/O modules..." error (I/O module messages 100 ... 103).
 
b.
Error in the PLC application: The task runtime is violated.
 
c.
Backplane bus structure: Many passive modules are plugged in between the I/O modules (EPM-S7xx/EPM-S9xx).
 
a.
Check the error sequence in the logbook and eliminate the errors "Too many I/O modules...". (I/O module message 100 ... 103).
 
b.
Correct PLC application.
 
c.
Remove passive I/O modules, change structure.
 
Fault
 
671744106
0x280A006A
Timeout backplane bus communication (I/O module msg. 106)
Cause
Remedy
Severity/response
The data exchange between the backplane bus and the PLC application is not possible within the specified time.
a.
Follow-up error of the "Too many I/O modules..." error (I/O module messages 100 ... 103).
 
b.
Error in the PLC application: The task runtime is violated.
 
c.
Backplane bus structure: Many passive modules are plugged in between the I/O modules (EPM-S7xx/EPM-S9xx).
 
a.
Check the error sequence in the logbook and eliminate the errors "Too many I/O modules...". (I/O module message 100 ... 103).
 
b.
Correct PLC application.
 
c.
Remove passive I/O modules, change structure.
 
Fault
 
671744107
0x280A006B
Timeout backplane bus communication (I/O module msg. 107)
Cause
Remedy
Severity/response
The data exchange between the backplane bus and the PLC application is not possible within the specified time.
a.
Follow-up error of the "Too many I/O modules..." error (I/O module messages 100 ... 103).
 
b.
Error in the PLC application: The task runtime is violated.
 
c.
Backplane bus structure: Many passive modules are plugged in between the I/O modules (EPM-S7xx/EPM-S9xx).
 
a.
Check the error sequence in the logbook and eliminate the errors "Too many I/O modules...". (I/O module message 100 ... 103).
 
b.
Correct PLC application.
 
c.
Remove passive I/O modules, change structure.
 
Fault
 
671744108
0x280A006C
Timeout backplane bus communication (I/O module msg. 108)
Cause
Remedy
Severity/response
The data exchange between the backplane bus and the PLC application is not possible within the specified time.
a.
Follow-up error of the "Too many I/O modules..." error (I/O module messages 100 ... 103).
 
b.
Error in the PLC application: The task runtime is violated.
 
c.
Backplane bus structure: Many passive modules are plugged in between the I/O modules (EPM-S7xx/EPM-S9xx).
 
a.
Check the error sequence in the logbook and eliminate the errors "Too many I/O modules...". (I/O module message 100 ... 103).
 
b.
Correct PLC application.
 
c.
Remove passive I/O modules, change structure.
 
Fault
 
671744109
0x280A006D
Timeout backplane bus communication (I/O module msg. 109)
Cause
Remedy
Severity/response
The data exchange between the backplane bus and the PLC application is not possible within the specified time.
a.
Follow-up error of the "Too many I/O modules..." error (I/O module messages 100 ... 103).
 
b.
Error in the PLC application: The task runtime is violated.
 
c.
Backplane bus structure: Many passive modules are plugged in between the I/O modules (EPM-S7xx/EPM-S9xx).
 
a.
Check the error sequence in the logbook and eliminate the errors "Too many I/O modules...". (I/O module message 100 ... 103).
 
b.
Correct PLC application.
 
c.
Remove passive I/O modules, change structure.
 
Fault
 
671744111
0x280A006F
Internal error (I/O module msg. 110)
Cause
Remedy
Severity/response
Internal error
Restart device. If the error persists, contact the manufacturer.
Fault
 
671744112
0x280A0070
Powerfail backplane bus detected (I/O module msg. 112)
Cause
Remedy
Severity/response
Voltage interruption detected.
-
Fault
 
671744116
0x280A0074
Timeout backplane bus communication (I/O module msg. 116)
Cause
Remedy
Severity/response
The data exchange between the backplane bus and the PLC application is not possible within the specified time.
a.
Follow-up error of the "Too many I/O modules..." error (I/O module messages 100 ... 103).
 
b.
Error in the PLC application: The task runtime is violated.
 
c.
Backplane bus structure: Many passive modules are plugged in between the I/O modules (EPM-S7xx/EPM-S9xx).
 
a.
Check the error sequence in the logbook and eliminate the errors "Too many I/O modules...". (I/O module message 100 ... 103).
 
b.
Correct PLC application.
 
c.
Remove passive I/O modules, change structure.
 
Fault
 
671744117
0x280A0075
Timeout backplane bus communication (I/O module msg. 117)
Cause
Remedy
Severity/response
The data exchange between the backplane bus and the PLC application is not possible within the specified time.
a.
Follow-up error of the "Too many I/O modules..." error (I/O module messages 100 ... 103).
 
b.
Error in the PLC application: The task runtime is violated.
 
c.
Backplane bus structure: Many passive modules are plugged in between the I/O modules (EPM-S7xx/EPM-S9xx).
 
a.
Check the error sequence in the logbook and eliminate the errors "Too many I/O modules...". (I/O module message 100 ... 103).
 
b.
Correct PLC application.
 
c.
Remove passive I/O modules, change structure.
 
Fault
 
671744118
0x280A0076
Timeout backplane bus communication (I/O module msg. 118)
Cause
Remedy
Severity/response
The data exchange between the backplane bus and the PLC application is not possible within the specified time.
a.
Follow-up error of the "Too many I/O modules..." error (I/O module messages 100 ... 103).
 
b.
Error in the PLC application: The task runtime is violated.
 
c.
Backplane bus structure: Many passive modules are plugged in between the I/O modules (EPM-S7xx/EPM-S9xx).
 
a.
Check the error sequence in the logbook and eliminate the errors "Too many I/O modules...". (I/O module message 100 ... 103).
 
b.
Correct PLC application.
 
c.
Remove passive I/O modules, change structure.
 
Fault
 
671744119
0x280A0077
Timeout backplane bus communication (I/O module msg. 119)
Cause
Remedy
Severity/response
The data exchange between the backplane bus and the PLC application is not possible within the specified time.
a.
Follow-up error of the "Too many I/O modules..." error (I/O module messages 100 ... 103).
 
b.
Error in the PLC application: The task runtime is violated.
 
c.
Backplane bus structure: Many passive modules are plugged in between the I/O modules (EPM-S7xx/EPM-S9xx).
 
a.
Check the error sequence in the logbook and eliminate the errors "Too many I/O modules...". (I/O module message 100 ... 103).
 
b.
Correct PLC application.
 
c.
Remove passive I/O modules, change structure.
 
Fault
 
671744120
0x280A0078
Timeout backplane bus communication (I/O module msg. 120)
Cause
Remedy
Severity/response
The data exchange between the backplane bus and the PLC application is not possible within the specified time.
a.
Follow-up error of the "Too many I/O modules..." error (I/O module messages 100 ... 103).
 
b.
Error in the PLC application: The task runtime is violated.
 
c.
Backplane bus structure: Many passive modules are plugged in between the I/O modules (EPM-S7xx/EPM-S9xx).
 
a.
Check the error sequence in the logbook and eliminate the errors "Too many I/O modules...". (I/O module message 100 ... 103).
 
b.
Correct PLC application.
 
c.
Remove passive I/O modules, change structure.
 
Fault
 
671744121
0x280A0079
Timeout backplane bus communication (I/O module msg. 121)
Cause
Remedy
Severity/response
The data exchange between the backplane bus and the PLC application is not possible within the specified time.
a.
Follow-up error of the "Too many I/O modules..." error (I/O module messages 100 ... 103).
 
b.
Error in the PLC application: The task runtime is violated.
 
c.
Backplane bus structure: Many passive modules are plugged in between the I/O modules (EPM-S7xx/EPM-S9xx).
 
a.
Check the error sequence in the logbook and eliminate the errors "Too many I/O modules...". (I/O module message 100 ... 103).
 
b.
Correct PLC application.
 
c.
Remove passive I/O modules, change structure.
 
Fault
 
671744136
0x280A0088
Configuration error I/O module topology (I/O module msg. 136)
Cause
Remedy
Severity/response
The I/O modules configured in the PLC application were not found on the backplane bus.
a.
The bus structure in the PLC application does not match the actual bus structure.
 
b.
There is no contact between the electronic module and the base module of the I/O module.
 
c.
There is no contact between two adjacent base modules of the I/O system.
 
d.
An I/O module is defective.
 
e.
The voltage supply to the I/O modules has been interrupted.
 
f.
Controller is defective. The MF LEDs light up on all modules.
 
a.
Compare PLC application with the actual bus structure.
 
b.
Plug the electronic module firmly onto the base module.
 
c.
Plug in base modules correctly.
 
d.
Replace defective I/O module (the MF LEDs of the affected module light up).
 
e.
When using EPM-S702 modules, check and restore the power supply to the modules.
 
f.
The MF LEDs light up for all modules: Measure the voltage at the 5 V contacts of the last module at the backplane bus (pin 3 and 5). Replace controller.
 
Fault
 
671744137
0x280A0089
Too many tasks for I/O module operation (I/O module msg. 137)
Cause
Remedy
Severity/response
Too many tasks for I/O module processing.
Reduce the number of tasks for processing I/O modules.
Fault
 
671744138
0x280A008A
Internal error (I/O module msg. 138)
Cause
Remedy
Severity/response
Internal error
Restart device. If the error persists, contact the manufacturer.
Fault
 
671744139
0x280A008B
Internal error (I/O module msg. 139)
Cause
Remedy
Severity/response
Internal error
Restart device. If the error persists, contact the manufacturer.
Fault
 
671744140
0x280A008C
Internal error (I/O module msg. 140)
Cause
Remedy
Severity/response
Internal error
Restart device. If the error persists, contact the manufacturer.
Fault
 
671744181
0x280A00B5
Internal error (I/O module msg. 181)
Cause
Remedy
Severity/response
Internal error
Restart device. If the error persists, contact the manufacturer.
Fault
 
671744200
0x280A00C8
Internal error (I/O module msg. 200)
Cause
Remedy
Severity/response
Internal error
Restart device. If the error persists, contact the manufacturer.
Fault
 
671744220
0x280A00DC
Internal error (I/O module msg. 220)
Cause
Remedy
Severity/response
Internal error
Restart device. If the error persists, contact the manufacturer.
Fault
 
671744221
0x280A00DD
Internal error (I/O module msg. 221)
Cause
Remedy
Severity/response
Internal error
Restart device. If the error persists, contact the manufacturer.
Fault
 
671744222
0x280A00DE
I/O system driver could not be opened (I/O module msg. 222)
Cause
Remedy
Severity/response
The I/O system driver (backplane bus driver) could not be started after an update of the controller firmware or due to a defective device.
–
Update or restore the controller again.
 
–
Replace controller.
 
Fault
 
671809806
0x280B010e
Faulty system units
Cause
Remedy
Severity/response
Faulty system components were detected when the device was started.
Restart the device. If the error persists, contact the manufacturer.
Fault
 
671810816
0x280B0500
PLC buffer overflow
Cause
Remedy
Severity/response
In the "PLC Designer" not all log messages could be displayed in the log dialog.
Open the log dialog in the "PLC Designer" only in situations where there is not a high volume of log messages.
Warning
 
671813633
0x280B1001
Application cannot be started
Cause
Remedy
Severity/response
The boot application cannot be started due to faulty system components.
Restart the device. If the error persists, contact the manufacturer.
Fault
 
805307009
0x30000281
Init cmd response error - Slave not present
Cause
Remedy
Severity/response
The following error occurred during the execution of the slave init cmd for initializing the slave: Slave no longer available.
–
Check whether the slave is available.
 
–
Check features.
 
Fault
 
805307010
0x30000282
Init cmd response error - Erron in AL Status
Cause
Remedy
Severity/response
The following error occurred during the execution of the slave init cmd for initializing the slave: Setting the EtherCAT status was not successful.
–
Check whether the slave is available.
 
–
Check features.
 
Fault
 
805307011
0x30000283
Init cmd response error - Mailbox Error
Cause
Remedy
Severity/response
The following error occurred during the execution of the slave init cmd for initializing the slave: Setting the mailbox features was not successful.
–
Check whether the slave is available.
 
–
Check mailbox features.
 
Fault
 
805307012
0x30000284
Init cmd response error - PDI Watchdog expired
Cause
Remedy
Severity/response
The following error occurred during the execution of the slave init cmd for initializing the slave: Problem with PDI watchdog.
Check PDI watchdog features.
Fault
 
805311432
0x300013C8
CoE - SDO Abort 'Toggle bit not alternated (0x05030000)'
Cause
Remedy
Severity/response
The status of the toggle bit has not changed.
For information only. No remedy necessary.
Information
 
805311433
0x300013C9
CoE - SDO Abort 'SDO protocol time-out (0x05040000)'
Cause
Remedy
Severity/response
SDO protocol timeout
Check if timeout is set too low.
Warning
 
805311434
0x300013CA
CoE - SDO Abort 'Client/server command specifier not valid or unknown (0x05040001)'
Cause
Remedy
Severity/response
Invalid or unknown specification symbol for the client/server command.
Check access authorization.
Check object properties.
Information
 
805311435
0x300013CB
CoE - SDO Abort 'Invalid block size (block mode only) (0x05040002)'
Cause
Remedy
Severity/response
Invalid block size (only in "block mode")
Check access authorization.
Check object properties.
Information
 
805311436
0x300013CC
CoE - SDO Abort 'Invalid sequence number (block mode only) (0x05040003)'
Cause
Remedy
Severity/response
Invalid sequence number (only in "block mode")
Check access authorization.
Check object properties.
Information
 
805311437
0x300013CD
CoE - SDO Abort 'CRC error (block mode only) (0x05040004)'
Cause
Remedy
Severity/response
CRC error (only in "block mode")
Check access authorization.
Check object properties.
Information
 
805311438
0x300013CE
CoE - SDO Abort 'Out of memory (0x05040005)'
Cause
Remedy
Severity/response
Too little free space in the main memory.
Check access authorization.
Check object properties.
Information
 
805311439
0x300013CF
CoE - SDO Abort 'Unsupported access to an object (0x06010000)'
Cause
Remedy
Severity/response
Access denied.
Check access authorization.
Check object properties.
Information
 
805311440
0x300013D0
CoE - SDO Abort 'Attempt to read a write only object (0x06010001)'
Cause
Remedy
Severity/response
Access denied.
Check access authorization.
Information
 
805311441
0x300013D1
CoE - SDO Abort 'Attempt to write a read only object (0x06010002)'
Cause
Remedy
Severity/response
Access denied.
Check access authorization.
Information
 
805311442
0x300013D2
CoE - SDO-Abort 'Object does not exist in the object dictionary (0x06020000)'
Cause
Remedy
Severity/response
Access denied.
Check access authorization.
Check if object exists.
Information
 
805311443
0x300013D3
CoE - SDO Abort 'Object cannot be mapped to the PDO (0x06040041)'
Cause
Remedy
Severity/response
Access denied.
Check access authorization.
Check if object exists.
Information
 
805311444
0x300013D4
CoE - SDO Abort 'Number and length of objects to be mapped exceed PDO length (0x06040042)'
Cause
Remedy
Severity/response
Access denied.
Check the length of the objects to be mapped.
Information
 
805311445
0x300013D5
CoE - SDO Abort 'General parameter incompatibility (0x06040043)'
Cause
Remedy
Severity/response
Access denied.
Check access authorization.
Information
 
805311446
0x300013D6
CoE - SDO Abort 'General internal incompatibility in the device (0x06040047)'
Cause
Remedy
Severity/response
Access denied.
Check access authorization.
Information
 
805311447
0x300013D7
CoE - SDO Abort 'Access failed due to an hardware error (0x06060000)'
Cause
Remedy
Severity/response
Access denied.
Check access authorization.
Check object properties.
Information
 
805311448
0x300013D8
CoE - SDO Abort 'Data type or length of service parameters do not match (0x06070010)'
Cause
Remedy
Severity/response
Access denied.
Check access authorization.
Check object properties.
Information
 
805311449
0x300013D9
CoE - SDO Abort 'Data type does not match, service parameter too high (0x06070012)'
Cause
Remedy
Severity/response
Access denied.
Check access authorization.
Check object properties.
Information
 
805311450
0x300013DA
CoE - SDO Abort 'Data type does not match, service parameter too low (0x06070013)'
Cause
Remedy
Severity/response
Access denied.
Check access authorization.
Check object properties.
Information
 
805311451
0x300013DB
CoE - SDO Abort 'Subindex does not exist (0x06090011)'
Cause
Remedy
Severity/response
Access denied.
Check access authorization.
Check object properties.
Information
 
805311452
0x300013DC
CoE - SDO Abort 'Write access - Parameter value exceeds limits (0x06090030)'
Cause
Remedy
Severity/response
Access denied.
Check access authorization.
Check object properties.
Information
 
805311453
0x300013DD
CoE - SDO Abort 'Write access - Parameter value too high (0x06090031)'
Cause
Remedy
Severity/response
Access denied.
Check access authorization.
Check object properties.
Information
 
805311454
0x300013DE
CoE - SDO Abort 'Write access - Parameter value too low (0x06090032)'
Cause
Remedy
Severity/response
Access denied.
Check access authorization.
Check object properties.
Information
 
805311455
0x300013DF
CoE - SDO Abort 'Maximum value less than minimum value (0x06090036)'
Cause
Remedy
Severity/response
Access denied.
Check access authorization.
Check object properties.
Information
 
805311456
0x300013E0
CoE - SDO Abort 'General error (0x08000000)'
Cause
Remedy
Severity/response
Access denied.
Check access authorization.
Check object properties.
Information
 
805311457
0x300013E1
CoE - SDO Abort 'Data cannot be transferred/stored in application (0x08000020)'
Cause
Remedy
Severity/response
Access denied.
Check access authorization.
Check object properties.
Information
 
805311458
0x300013E2
CoE - SDO Abort 'Local control - Data cannot be transferred/stored in application (0x08000021)'
Cause
Remedy
Severity/response
Access denied.
Check access authorization.
Check object properties.
Information
 
805311459
0x300013E3
CoE- SDO Abort 'Actual device state - Data cannot be transferred/stored in application (0x08000022)'
Cause
Remedy
Severity/response
Access denied.
Check access authorization.
Check object properties.
Information
 
805311460
0x300013E4
CoE - SDO Abort 'Object dictionary - Dynamic generation fails or object dictionary is missing (0x08000023)'
Cause
Remedy
Severity/response
Access denied.
Check access authorization.
Check object properties.
Information
 
805311461
0x300013E5
CoE - SDO Abort 'Unknown abort code'
Cause
Remedy
Severity/response
Access denied.
Check access authorization.
Check object properties.
Information
 
805311462
0x300013E6
CoE - Invalid parameter
Cause
Remedy
Severity/response
Access denied.
Check access authorization.
Check object properties.
Check transfer properties.
Information
 
805311463
0x300013E7
CoE - CoE protocol not supported
Cause
Remedy
Severity/response
Access denied.
Check access authorization.
Check object properties.
Check transfer properties.
Information
 
805311464
0x300013E8
CoE - Unknown FoE error
Cause
Remedy
Severity/response
Access denied.
Check access authorization.
Check file.
Check transfer properties.
Information
 
805311465
0x300013E9
CoE - FoE error 'Not found'
Cause
Remedy
Severity/response
Access denied.
Check access authorization.
Check file.
Check transfer properties.
Information
 
805311466
0x300013EA
CoE - FoE error 'Access denied'
Cause
Remedy
Severity/response
Access denied.
Check access authorization.
Check file.
Check transfer properties.
Information
 
805311467
0x300013EB
CoE - FoE error 'Disk full'
Cause
Remedy
Severity/response
Access denied.
Check access authorization.
Check file.
Check transfer properties.
Information
 
805311468
0x300013EC
CoE - FoE error 'Illegal'
Cause
Remedy
Severity/response
Access denied.
Check access authorization.
Check file.
Check transfer properties.
Information
 
805311469
0x300013ED
CoE - FoE error 'Wrong packet number'
Cause
Remedy
Severity/response
Access denied.
Check access authorization.
Check object properties.
Information
 
805311470
0x300013EE
CoE - FoE error 'Already existing'
Cause
Remedy
Severity/response
Access denied.
Check access authorization.
Check file.
Check transfer properties.
Information
 
805311471
0x300013EF
CoE - FoE error 'User missing'
Cause
Remedy
Severity/response
Access denied.
Check access authorization.
Check file.
Check transfer properties.
Information
 
805311472
0x300013F0
CoE - FoE error 'Only possible in bootstrap'
Cause
Remedy
Severity/response
Access denied.
Check access authorization.
Check file.
Check transfer properties.
Information
 
805311473
0x300013F1
CoE - FoE error 'No bootstrap'
Cause
Remedy
Severity/response
Access denied.
Check access authorization.
Check file.
Check transfer properties.
Information
 
805311474
0x300013F2
CoE - FoE error 'No access rights'
Cause
Remedy
Severity/response
Access denied.
Check access authorization.
Check file.
Check transfer properties.
Information
 
805311475
0x300013F3
CoE - FoE error 'Program error'
Cause
Remedy
Severity/response
Access denied.
Check access authorization.
Check object properties.
Information
 
805311476
0x300013F4
CoE - FoE error 'Invalid parameter'
Cause
Remedy
Severity/response
Access denied.
Check access authorization.
Check file.
Check transfer properties.
Information
 
805311477
0x300013F5
FoE error - Timeout
Cause
Remedy
Severity/response
A timeout has occurred during the FoE transfer (read or write).
If possible, increase the timeout setting or reduce the bus and CPU load.
Fault
 
805311881
0x30001589
EtherCAT - State change of master successful
Cause
Remedy
Severity/response
EtherCAT - State change of master successful
For information only. No remedy necessary.
Fault
 
805311882
0x3000158A
EtherCAT - Bus scan successful
Cause
Remedy
Severity/response
EtherCAT - Bus scan successful
For information only. No remedy necessary.
Fault
 
805311883
0x3000158B
EtherCAT - Bus scan error
Cause
Remedy
Severity/response
Error in the network topology
Check network topology.
Fault
 
805311892
0x30001594
CoE - Emergency request
Cause
Remedy
Severity/response
Internal error during transmission of emergency messages.
Check the documentation of the slave device for this emergency message.
Note: "data: ..." shows by codes which error has occurred in which slave device/module. Detailed information about the coding of error messages can be found in the documentation of the corresponding slave device/module.
Information
 
805311893
0x30001595
Cyclic command WKC error
Cause
Remedy
Severity/response
WKC error
Check slave status.
Check network topology.
Fault
 
805311894
0x30001596
Master init command WKC error
Cause
Remedy
Severity/response
WKC error
Check slave status.
Check network topology.
Warning
 
805311895
0x30001597
Slave init command WKC error
Cause
Remedy
Severity/response
WKC error
Check slave status.
Check network topology.
Warning
 
805311896
0x30001598
EoE receive WKC error
Cause
Remedy
Severity/response
WKC error
Check slave status.
Check network topology.
Warning
 
805311897
0x30001599
CoE receive WKC error
Cause
Remedy
Severity/response
WKC error
Check slave status.
Check network topology.
Warning
 
805311898
0x3000159A
FoE receive WKC error
Cause
Remedy
Severity/response
WKC error
Check slave status.
Check network topology.
Fault
 
805311900
0x3000159C
EoE send WKC error
Cause
Remedy
Severity/response
WKC error
Check slave status.
Check network topology.
Warning
 
805311901
0x3000159D
CoE send WKC error
Cause
Remedy
Severity/response
WKC error
Check slave status.
Check network topology.
Warning
 
805311902
0x3000159E
FoE send WKC error
Cause
Remedy
Severity/response
WKC error
Check slave status.
Check network topology.
Warning
 
805311909
0x300015A5
Init command response error - No response
Cause
Remedy
Severity/response
Internal error
Restart the device. If the error persists, contact the manufacturer.
Warning
 
805311910
0x300015A6
Init command response error - Validation error
Cause
Remedy
Severity/response
Internal error
Restart the device. If the error persists, contact the manufacturer.
Warning
 
805311911
0x300015A7
Init command response error - Failed
Cause
Remedy
Severity/response
Internal error
Restart the device. If the error persists, contact the manufacturer.
Warning
 
805311912
0x300015A8
Master init command response error - No response
Cause
Remedy
Severity/response
Internal error
Restart the device. If the error persists, contact the manufacturer.
Warning
 
805311913
0x300015A9
Master init command response error - Validation error
Cause
Remedy
Severity/response
Internal error
Restart the device. If the error persists, contact the manufacturer.
Warning
 
805311915
0x300015AB
Mailbox init command timeout
Cause
Remedy
Severity/response
Internal error
Restart the device. If the error persists, contact the manufacturer.
Warning
 
805311916
0x300015AC
At least one EtherCAT slave not in 'Operational'
Cause
Remedy
Severity/response
Master is "Operational".
At least one slave is not "Operational".
Check slave status.
Check network topology.
Warning
 
805311917
0x300015AD
EtherCAT cable connected
Cause
Remedy
Severity/response
EtherCAT cable connected
For information only. No remedy necessary.
Information
 
805311918
0x300015AE
EtherCAT cable not connected
Cause
Remedy
Severity/response
Network cabling is faulty.
Check network cabling.
Information
 
805311921
0x300015B1
At least one slave is in state 'Error'
Cause
Remedy
Severity/response
At least one slave is in the "Error" state.
Check slave status.
Check network topology.
Warning
 
805311922
0x300015B2
Slave error
Cause
Remedy
Severity/response
A slave reports an error.
Analyze detailed error message in the logbook.
Check slave status.
Check network topology.
Warning
 
805311923
0x300015B3
Communication to device interrupted
Cause
Remedy
Severity/response
The connection to the slave is interrupted.
The slave does not respond.
The slave is no longer available.
Check slave status.
Check network topology.
Warning
 
805311924
0x300015B4
SDO abort
Cause
Remedy
Severity/response
CoE access denied.
Analyze detailed error message in the logbook.
Check object properties.
Check transfer properties.
Warning
 
805311925
0x300015B5
DC slaves are 'in-sync'
Cause
Remedy
Severity/response
DC slaves are 'in-sync'
For information only. No remedy necessary.
Information
 
805311926
0x300015B6
DC slaves are 'out-of-sync'
Cause
Remedy
Severity/response
The DC deviation is outside the permissible limits.
Check slave status.
Check slave properties.
Check network topology.
Warning
 
805312086
0x30001656
Communication to device interrupted
Cause
Remedy
Severity/response
Communication interruption
Check slave status.
Check network topology.
Information
 
805312087
0x30001657
Slave is not in expected status
Cause
Remedy
Severity/response
Detected slave status differs from expected slave status.
Analyze detailed error message in the logbook.
Check slave status.
Check network topology.
Warning
 
805312112
0x30001670
Bus scan timeout
Cause
Remedy
Severity/response
The bus scan was aborted due to timeout.
Analyze detailed error message in the logbook.
Check network topology.
Warning
 
805312568
0x30001838
Configuration error - Check of VendorID failed
Cause
Remedy
Severity/response
The vendor ID could not be checked.
Analyze detailed error message in the logbook.
Check network topology.
Warning
 
805312569
0x30001839
Configuration error - Check of ProductCode failed
Cause
Remedy
Severity/response
The product code could not be checked.
Analyze detailed error message in the logbook.
Check network topology.
Information
 
805312570
0x3000183A
Configuration error - Check of Revision failed
Cause
Remedy
Severity/response
The revision could not be checked.
Analyze detailed error message in the logbook.
Check network topology.
Information
 
805312571
0x3000183B
Configuration error - Check of VendorID failed
Cause
Remedy
Severity/response
The vendor ID could not be checked.
Analyze detailed error message in the logbook.
Check network topology.
Information
 
805312572
0x3000183C
Configuration error - Odd device at bus end
Cause
Remedy
Severity/response
A surplus device was detected at the end of the bus.
Analyze detailed error message in the logbook.
Check network topology.
Information
 
805312578
0x30001842
Internal error counter resetted
Cause
Remedy
Severity/response
Internal error counter resetted
For information only. No remedy necessary.
Information
 
805312580
0x30001844
All slaves 'Operational' again
Cause
Remedy
Severity/response
All slaves 'Operational' again
For information only. No remedy necessary.
Information
 
805312581
0x30001845
Cyclic command WKC error
Cause
Remedy
Severity/response
WKC error
Analyze detailed error message in the logbook.
Check slave status.
Check network topology.
Warning
 
805312582
0x30001846
Frame response error
Cause
Remedy
Severity/response
Frame response error
Analyze detailed error message in the logbook.
Check slave status.
Check network topology.
Warning
 
805312583
0x30001847
Not all slaves are 'Operational'
Cause
Remedy
Severity/response
Not all slaves have been set to 'Operational'.
Analyze detailed error message in the logbook.
Check slave status.
Check network topology.
Information
 
805312584
0x30001848
Emergency message - Overflow, further messages blocked
Cause
Remedy
Severity/response
Too many emergency messages.
Check if slave sends too many emergency messages.
Eliminate cause.
Warning
 
805312588
0x3000184C
New configuration loaded
Cause
Remedy
Severity/response
New configuration loaded
For information only. No remedy necessary.
Information
 
805312589
0x3000184D
New configuration loaded, no slaves defined
Cause
Remedy
Severity/response
New configuration loaded, no slaves defined
For information only. No remedy necessary.
Information
 
805312590
0x3000184E
Master - Start failed, configuration error
Cause
Remedy
Severity/response
Internal error
Check slave status.
Check network topology.
Information
 
805312591
0x3000184F
New configuration loaded from slaves EEPROM
Cause
Remedy
Severity/response
A new configuration has been loaded from the EEPROMs of the slaves.
For information only. No remedy necessary.
Information
 
805312598
0x30001856
Master - Start failed
Cause
Remedy
Severity/response
Internal error
Check slave status.
Check network topology.
Warning
 
805312599
0x30001857
Master - Start failed, bus configuration error
Cause
Remedy
Severity/response
Bus configuration error
Check network topology.
Warning
 
805312600
0x30001858
Master - Start failed, EtherCAT cable disconnected
Cause
Remedy
Severity/response
Network cabling is faulty.
Check network cabling.
Warning
 
805312601
0x30001859
Master - Start failed, DC/DCM configuration
Cause
Remedy
Severity/response
The master cannot be started due to a faulty DC/DCM configuration.
Check slave configuration.
Warning
 
805312602
0x3000185A
Master - Start failed, cannot set slaves to 'Pre-Operational'
Cause
Remedy
Severity/response
Slaves cannot be set to 'Pre-Operational'.
Check slave configuration.
Warning
 
805312608
0x30001860
Master - Set 'Operational' failed
Cause
Remedy
Severity/response
Operational' could not be set.
Check slave configuration.
Warning
 
805312610
0x30001862
Master - Set 'Operational' failed, EtherCAT cable disconnected
Cause
Remedy
Severity/response
Network cabling is faulty.
Check network cabling.
Warning
 
805312613
0x30001865
Master - Set 'Operational' takes some time...
Cause
Remedy
Severity/response
Master - Set 'Operational' takes some time...
For information only. No remedy necessary.
Warning
 
805312614
0x30001866
Master - Set 'Operational' failed, time-out
Cause
Remedy
Severity/response
Internal error
Check slave status.
Check network topology.
Warning
 
805312615
0x30001867
Master - Set 'Operational' failed, slave error
Cause
Remedy
Severity/response
Slave error
Analyze previous error message (slave error) in the logbook.
Check slave status.
Check network topology.
Warning
 
805312616
0x30001868
Master - Set 'Operational' aborted by reset command
Cause
Remedy
Severity/response
Master - Set 'Operational' aborted by reset command
For information only. No remedy necessary.
Warning
 
805312618
0x3000186A
Master - Stopping failed
Cause
Remedy
Severity/response
Master cannot be stopped.
For information only. No remedy required.
Warning
 
805312619
0x3000186B
Master - Stopping failed, cannot set Slaves 'Pre-Operational'
Cause
Remedy
Severity/response
Slave error
For information only. No remedy required.
Warning
 
805312628
0x30001874
Master - Shutdown failed
Cause
Remedy
Severity/response
Master - Shutdown failed
For information only. No remedy necessary.
Warning
 
805312638
0x3000187E
Remote API Server - Start failed
Cause
Remedy
Severity/response
Internal error
Restart the device. If the error persists, contact the manufacturer.
Warning
 
805312648
0x30001888
Start Download Service
Cause
Remedy
Severity/response
Start Download Service
For information only. No remedy necessary.
Information
 
805312649
0x30001889
Download Service done
Cause
Remedy
Severity/response
Download Service done
For information only. No remedy necessary.
Information
 
805312668
0x3000189C
MMC - Internal error
Cause
Remedy
Severity/response
Internal error
Restart the device. If the error persists, contact the manufacturer.
Warning
 
805312669
0x3000189D
MMC - 'Modular Machine Configuration' is active
Cause
Remedy
Severity/response
MMC - "Modular Machine Configuration" is active.
For information only. No remedy necessary.
Information
 
805312670
0x3000189E
MMC - Service started
Cause
Remedy
Severity/response
MMC - Service started
For information only. No remedy necessary.
Information
 
805312671
0x3000189F
MMC - Service stopped
Cause
Remedy
Severity/response
MMC - Service stopped
For information only. No remedy necessary.
Information
 
805312672
0x300018A0
MMC - Error in configuration files
Cause
Remedy
Severity/response
MMC configuration file is faulty.
Check MMC configuration file.
Warning
 
805312673
0x300018A1
MMC - File does not exist
Cause
Remedy
Severity/response
MMC - File does not exist
For information only. No remedy necessary.
Warning
 
805312674
0x300018A2
MMC - Parsing error
Cause
Remedy
Severity/response
MMC configuration file is faulty.
Check MMC configuration file.
Warning
 
805312675
0x300018A3
MMC - parsing of file successful
Cause
Remedy
Severity/response
MMC - parsing of file successful
For information only. No remedy necessary.
Warning
 
805312676
0x300018A4
MMC - Devices not sorted in ascending order or devices missing
Cause
Remedy
Severity/response
MMC configuration file is faulty.
Check MMC configuration file.
Warning
 
805312677
0x300018A5
MMC - Number of devices in device tree differs
Cause
Remedy
Severity/response
MMC configuration file is faulty.
Check MMC configuration file.
Check network topology.
Warning
 
805312678
0x300018A6
MMC - Device type mismatch for Alias Address
Cause
Remedy
Severity/response
MMC configuration file is faulty.
Check MMC configuration file.
Analyze detailed error message in the logbook.
Warning
 
805312679
0x300018A7
MMC - Invalid Alias Address
Cause
Remedy
Severity/response
Incorrect alias address.
Check SSA addresses of the slaves.
Analyze detailed error message in the logbook.
Warning
 
805312680
0x300018A8
MMC - Duplicated Alias Address
Cause
Remedy
Severity/response
Double alias address.
Check SSA addresses of the slaves.
Analyze detailed error message in the logbook.
Warning
 
805312681
0x300018A9
MMC - No configuration checks
Cause
Remedy
Severity/response
MMC - No configuration checks
For information only. No remedy necessary.
Information
 
805312682
0x300018AA
MMC - Invalid configuration
Cause
Remedy
Severity/response
Internal error
Restart the device. If the error persists, contact the manufacturer.
Warning
 
805312683
0x300018AB
MMC - Mandatory slave missing
Cause
Remedy
Severity/response
MMC configuration file is faulty.
Network topology is faulty.
Check MMC configuration file.
Check network topology.
Warning
 
805312684
0x300018AC
MMC - Optional slave is present, but not allowed
Cause
Remedy
Severity/response
MMC configuration file is faulty.
Network topology is faulty.
Check MMC configuration file.
Check network topology.
Warning
 
805312685
0x300018AD
MMC - No valid service active
Cause
Remedy
Severity/response
MMC - No valid service active
For information only. No remedy necessary.
Warning
 
805312686
0x300018AE
MMC - Address assignment error, less slaves connected than configured
Cause
Remedy
Severity/response
MMC configuration file is faulty.
Network topology is faulty.
Analyze detailed error message in the logbook.
Check MMC configuration file.
Check network topology.
Warning
 
805312687
0x300018AF
MMC - Address assignment error, more slaves connected than configured
Cause
Remedy
Severity/response
MMC configuration file is faulty.
Network topology is faulty.
Analyze detailed error message in the logbook.
Check MMC configuration file.
Check network topology.
Fault
 
805312688
0x300018B0
MMC - Address assignment error, invalid device
Cause
Remedy
Severity/response
MMC configuration file is faulty.
Network topology is faulty.
Analyze detailed error message in the logbook.
Check MMC configuration file.
Check network topology.
Fault
 
805312689
0x300018B1
MMC - Address assignment successful
Cause
Remedy
Severity/response
MMC - Address assignment successful
For information only. No remedy necessary.
Information
 
805312690
0x300018B2
MMC - Address assignment failed
Cause
Remedy
Severity/response
MMC configuration file is faulty.
Network topology is faulty.
Analyze detailed error message in the logbook.
Check MMC configuration file.
Check network topology.
Information
 
805312691
0x300018B3
MMC - Address assignment done
Cause
Remedy
Severity/response
MMC - Address assignment done
For information only. No remedy necessary.
Information
 
805312692
0x300018B4
MMC - Address assignment error, writing address by CoE
Cause
Remedy
Severity/response
MMC - Address assignment error, writing address by CoE
For information only. No remedy necessary.
Warning
 
805312693
0x300018B5
MMC - Slave identification error
Cause
Remedy
Severity/response
MMC configuration file is faulty.
Network topology is faulty.
Analyze detailed error message in the logbook.
Check MMC configuration file.
Check network topology.
Warning
 
805312694
0x300018B6
MMC - Slave identification error, slave ident data failed
Cause
Remedy
Severity/response
MMC configuration file is faulty.
Network topology is faulty.
Analyze detailed error message in the logbook.
Check MMC configuration file.
Check network topology.
Warning
 
805312695
0x300018B7
MMC - Service state cannot be changed, set bus to 'INIT' first
Cause
Remedy
Severity/response
Service request rejected because master not in "Init" status
Check status of the master.
Set status of the master to "Init".
Information
 
805312768
0x30001900
CoE - Emergency request
Cause
Remedy
Severity/response
Internal error during transmission of emergency messages.
Check the documentation of the slave device for this emergency message.
Note: "data: ..." shows by codes which error has occurred in which slave device/module. Detailed information about the coding of error messages can be found in the documentation of the corresponding slave device/module.
Information
 
805312769
0x30001901
Topology check results ignored
Cause
Remedy
Severity/response
A topology check was performed, but the results were ignored. An attempt is made to drive the bus up anyway.
For information only. No remedy necessary.
Warning
 
805312770
0x30001902
Simultaneous use of MMC and Hotconnect is not permitted
Cause
Remedy
Severity/response
The obsolete function blocks L_ETC_MMCController and L_ETC_MMCControllerBus (MMC0) cannot be used simultaneously with the creation of HotConnect groups in the "PLC Designer" tab "HotConnect" (MMC1).
Remove function block L_ETC_MMCController (or the library that uses this FB) or delete all HotConnect groups in the "PLC Designer" project.
Fault
 
805312771
0x30001903
Number of configured HC-Groups exceeds limit
Cause
Remedy
Severity/response
More HotConnect groups have been created in the PLC application than are supported by the target system.
Reduce HotConnect groups in the PLC application.
Fault
 
805312772
0x30001904
Unexpected Identification Value
Cause
Remedy
Severity/response
In the physical bus structure, at least one slave has been assigned an identification value by SSA or ID switch that has not been configured in the PLC application.
–
Analyze detailed error message in the logbook.
 
–
Connected slaves check whether an identification value has been assigned by the SSA or ID switch that does not match the configuration.
 
Fault
 
805312773
0x30001905
Slave missing
Cause
Remedy
Severity/response
The specified slave is missing in a HotConnect group.
Check topology.
Fault
 
805312774
0x30001906
Unexpected Slave
Cause
Remedy
Severity/response
An unconfigured slave is present in a HotConnect group after the slave specified in the logbook entry.
–
Analyze detailed error message in the logbook.
 
–
Check topology.
 
Fault
 
805312775
0x30001907
Same Identification Value available multiple times
Cause
Remedy
Severity/response
In the physical bus structure, at least two slaves have the same identification value assigned by SSA or ID switch.
Check the topology, in particular the SSAs and/or ID switches set.
Fault
 
805312776
0x30001908
Identification Value is incorrect
Cause
Remedy
Severity/response
During the topology check, an undefined error has occurred with regard to the identification value of the slave specified in the logbook entry.
–
Analyze detailed error message in the logbook.
 
–
Check the topology, in particular the SSAs and/or ID switches set.
 
Fault
 
805312784
0x30001910
HC-Group - setting timeout
Cause
Remedy
Severity/response
A timeout has occurred when changing the status of a HotConnect group.
If possible, increase the timeout setting.
Fault
 
805314560
0x30002000
BusCycleTask is 'out-of-sync'
Cause
Remedy
Severity/response
Internal error
Restart the device. If the error persists, contact the manufacturer.
Fault
 
822310534
0x31037686
Network - Configuration error
Cause
Remedy
Severity/response
Network option incorrectly plugged in or not plugged in.
Network option in PLC project does not match configured network option.
–
Use the type code to check whether the network option used is correct.
 
–
Compare the network option configured in the PLC project with the network option configured in the controller (see parameter 0x231F:xxx).
 
Fault
 
822313360
0x31038190
Network - Watchdog time-out
Cause
Remedy
Severity/response
Permanent interruption of communication to the PLC.
–
Check wiring of the network.
 
–
Eliminate EMC interferences.
 
–
Check cables and connections.
 
–
Plug Ethernet cable into RJ45 sockets X2x6/X2x7.
 
Warning (configurable)
Setting parameters: 0x2859:001
 
822313361
0x31038191
Network - Disruption of cyclic data exchange
Cause
Remedy
Severity/response
Permanent interruption of communication to the PLC.
–
Check cables and connections.
 
–
Plug Ethernet cable into RJ45 sockets X2x6/X2x7.
 
No response (configurable)
Setting parameters: 0x2859:002
 
822313362
0x31038192
Network - Initialization error
Cause
Remedy
Severity/response
Network option was parameterized with wrong values.
–
Check station name.
 
–
Check IP configuration.
 
–
Check other parameters of the network option.
 
Warning (configurable)
Setting parameters: 0x2859:004
 
822313363
0x31038193
Network - Invalid cyclic process data
Cause
Remedy
Severity/response
Process data marked invalid by the network option is sent.
–
Check whether the PLC is in the "STOP" state.
 
–
Check cables and connections.
 
–
Plug Ethernet cable into RJ45 sockets X2x6/X2x7.
 
Warning (configurable)
Setting parameters: 0x2859:005
 
822313607
0x31038287
Network - Invalid configuration
Cause
Remedy
Severity/response
A module or submodule does not correspond to the configuration of the IO controller.
Check/correct configuration.
Warning (configurable)
Setting parameters: 0x2859:003
 
822313608
0x31038288
Network - Max. count of supported process data reached
Cause
Remedy
Severity/response
The maximum supported number/size of configurable PDOs has been exceeded.
Decrease the number or size of the configured PDOs.
The maximum number and size of PDOs can be found in the documentation.
Fault
 
822313609
0x31038289
Network - Too few Application Credit for network operation
Cause
Remedy
Severity/response
The network module cannot be operated because the required Application Credit is not sufficient or no Application Credit is available.
–
Check your available Application Credit.
 
–
Check the configuration of the use of Application Credit.
 
–
If necessary, use an SD card with more Application Credit.
 
Fault
 
827331073
0x31501201
Address space update failed
Cause
Remedy
Severity/response
The address area could not be updated.
In the "PLC Designer" reduce the number of symbols in the symbol configuration.
Warning
 
827331074
0x31501202
Client user authentification failed
Cause
Remedy
Severity/response
Client user authentication has failed.
Check in the "PLC Designer" in the user management whether user and associated password are available.
Warning
 
827331075
0x31501203
Client operation failed
Cause
Remedy
Severity/response
The client operation has failed.
Check client operation and its arguments against the meaning of the present OPC UA status code.
Warning
 
827331078
0x31501206
Client has been rejected because the certificate is not trusted
Cause
Remedy
Severity/response
A client connection was not established because the client certificate is not trusted.
Open the security screen in the "PLC Designer" and check the certificates. Trust or update certificate
Warning
 
827331079
0x31501207
Needed element for mapping is missing or erroneous
Cause
Remedy
Severity/response
The mapping file contains incorrect entries (e.g. missing elements or incorrect values such as data type or node ID).
Correct mapping file (add missing elements/enter correctly).
Warning
 
827331080
0x31501208
Namespace-ID for namespace-URI could not be found
Cause
Remedy
Severity/response
The namespace URI for a mapping element is incorrect and cannot be assigned to the namespaces of the server.
Check and correct namespace URI.
Warning
 
827331081
0x31501209
Node-ID for CSV name could not be found
Cause
Remedy
Severity/response
The placeholder keyword for the node ID is incorrect and could not be found.
Check the placeholder keyword and update the CSV file if necessary.
Warning
 
827331088
0x31501210
Node-ID of element not valid
Cause
Remedy
Severity/response
The node ID is either empty or has an incorrect value that does not correspond to the OPC UA specification (e.g. incorrect identifier type).
Check the node ID and compare it with the nodeset if necessary.
Warning
 
827331089
0x31501211
Element is missing for mapping
Cause
Remedy
Severity/response
The mapping file contains a mapping element for which the parameter element or variable element is missing.
Correct mapping file (add missing element).
Warning
 
827331090
0x31501212
CSV file could not be found
Cause
Remedy
Severity/response
The CSV file was not found in the expected location.
Store the CSV file under "/sdcard/plc/prg/pta/opc_ua_server/".
Warning
 
827331091
0x31501213
CSV file is errornous
Cause
Remedy
Severity/response
The CSV format of the CSV file is incorrect.
Check and correct CSV file with CSV validator.
Warning
 
827331092
0x31501214
Name collision in CSV file
Cause
Remedy
Severity/response
There are several entries with the same name in the CSV file.
Fix name collision in the CSV file.
Warning
 
827331093
0x31501215
The arguments of the node of the mapping file do not match the arguments of the nodeset file
Cause
Remedy
Severity/response
The mapping file does not correspond to the nodesets. Different versions may have been used here in which the arguments do not match.
Synchronize mapping file and nodeset file and check methods/events.
Warning
 
827331094
0x31501216
The notifier for the node could not be found. Setting notifier to server node
Cause
Remedy
Severity/response
The node ID of the notifier could not be found in the nodeset.
Synchronize mapping file and nodeset file and check OptionalPlaceholder/Events.
Warning
 
827331095
0x31501217
The method was called again, before the current execution was finalised
Cause
Remedy
Severity/response
A mapped method was called again before the first call was completed.
Wait until method has been finalized. If necessary, increase the client timeout.
Warning
 
827331096
0x31501218
Out of memory
Cause
Remedy
Severity/response
Not enough memory.
Reduce number of sessions, monitored items, ....
Warning
 
827331105
0x31501221
GDS - Client could not connect
Cause
Remedy
Severity/response
Connection problems between GDS client and GDS server.
–
Check network configuration.
 
–
Test hostname resolution.
 
–
Check whether the GDS server is running.
 
Warning
 
827331106
0x31501222
GDS - Client could not finish operation.
Cause
Remedy
Severity/response
Error in communication between GDS client and GDS server.
Check whether the server and client configuration match. For example, evaluate date, credentials, trace and WarningGdsClientInternal.
Warning
 
827331108
0x31501224
SKS - Pull client could not connect to SKS
Cause
Remedy
Severity/response
Connection problems between SKS pull client and SKS.
–
Check network configuration.
 
–
Test hostname resolution.
 
–
Check whether SKS is running.
 
Warning
 
827331109
0x31501225
SKS - Pull client could not retrieve valid keys
Cause
Remedy
Severity/response
Error during key rolling.
Check whether the configuration of the keys and security groups is correct.
Warning
 
827331110
0x31501226
Client failed to verify server certificate
Cause
Remedy
Severity/response
The GDS/SKS server certificate is currently not trusted or contains invalid fields.
Trust the certificate, set the correct time on the controller if necessary.
Warning
 
827331329
0x31501301
Out of memory
Cause
Remedy
Severity/response
Not enough memory.
In the "PLC Designer" reduce the number of symbols in the symbol configuration.
Fault
 
827331330
0x31501302
Failed to update address space
Cause
Remedy
Severity/response
The address area could not be updated.
In the "PLC Designer" reduce the number of symbols in the symbol configuration.
Fault
 
827331332
0x31501304
Nodeset file could not be found
Cause
Remedy
Severity/response
The nodeset file could not be found.
Check the file and name of the MappingModel.xml.
Fault
 
827331333
0x31501305
Mapping file is erroneous
Cause
Remedy
Severity/response
The content of the mapping file is incorrect.
Check and correct mapping file with XML validator.
Fault
 
827331334
0x31501306
Mapping file includes more nodesets than supported
Cause
Remedy
Severity/response
More nodesets are configured in the mapping file than are supported by the device.
Reduce the number of nodesets used.
Fault
 
827396609
0x31511201
PubSub - PubSub module activation failed
Cause
Remedy
Severity/response
The PubSub module could not be started. Possibly due to an internal error or a corrupt PubSub configuration.
Check the PubSub configuration and create a new one if necessary.
Warning
 
827396610
0x31511202
PubSub - PubSub module activation failed because of missing credit points
Cause
Remedy
Severity/response
The PubSub module could not be started. The license check has failed.
–
Check your available Application Credit.
 
–
Check the configuration of the use of Application Credit.
 
–
If necessary, use an SD card with more Application Credit.
 
Warning
 
827396613
0x31511205
PubSub - The keyfile was deleted
Cause
Remedy
Severity/response
PubSub could not start due to the incorrect time stamp of the key file.
Check the system time of the device and the NTP functionality.
Warning
 
827396865
0x31511301
PubSub - The configuration is invalid
Cause
Remedy
Severity/response
The PubSub configuration could not be loaded without errors.
Check PubSub configuration.
Fault
 
827396866
0x31511302
PubSub - Data access has been denied for the user
Cause
Remedy
Severity/response
The current user does not have the necessary data access rights for PubSub.
Assign the required rights to the user.
Fault
 
827396867
0x31511303
PubSub - The configuration size limit was exceeded
Cause
Remedy
Severity/response
The encoded PubSub configuration is larger than permitted.
Reduce the size of the PubSub configuration.
Fault
 
827396868
0x31511304
PubSub - Configuration contains too many connections
Cause
Remedy
Severity/response
The PubSub configuration contains more connections than the maximum permitted.
Reduce the number of configured connections.
Fault
 
827396869
0x31511305
PubSub - Configuration contains too many WriterGroups
Cause
Remedy
Severity/response
The PubSub configuration contains more WriterGroups than the maximum permitted.
Reduce the number of configured WriterGroups.
Fault
 
827396870
0x31511306
PubSub - Configuration contains too many ReaderGroups
Cause
Remedy
Severity/response
The PubSub configuration contains more ReaderGroups than the maximum permitted.
Reduce the number of configured ReaderGroups.
Fault
 
827396871
0x31511307
PubSub - Configuration contains too many Writers
Cause
Remedy
Severity/response
The PubSub configuration contains more writers than the maximum permitted.
Reduce the number of configured writers.
Fault
 
827396872
0x31511308
PubSub - Configuration contains too many Readers
Cause
Remedy
Severity/response
The PubSub configuration contains more readers than the maximum permitted.
Reduce the number of configured readers.
Fault
 
827396873
0x31511309
PubSub - Configuration contains too many published DataSets
Cause
Remedy
Severity/response
The PubSub configuration contains more published DataSets than the maximum permitted.
Reduce the number of configured published DataSets.
Fault
 
827396880
0x31511310
PubSub - Configuration contains too many subscribed DataSets
Cause
Remedy
Severity/response
The PubSub configuration contains more subscribed DataSets than the maximum permitted.
Reduce the number of configured subscribed DataSets.
Fault
 
827396881
0x31511311
Internal error
Cause
Remedy
Severity/response
Internal error
Restart the device. If the error persists, contact the manufacturer.
Fault
 
827396882
0x31511312
PubSub - The XML configuration could not be parsed
Cause
Remedy
Severity/response
The PubSub XML configuration could not be parsed.
Check the PubSub XML configuration for errors.
Fault
 
827396883
0x31511313
PubSub - The keyfile is invalid
Cause
Remedy
Severity/response
The PubSub key file is incorrect/invalid.
Check the system time of the device and the NTP functionality.
Fault
 
827397121
0x31511401
PubSub - The PubSub module was started and is running on connections
Cause
Remedy
Severity/response
Information only
Information
 
827462149
0x31521205
Session with handle disconnected because of external connection error
Cause
Remedy
Severity/response
An event led to the termination of an incoming connection.
Common faults can be localized/eliminated by the following checks:
–
Is the network connection available?
 
–
Is the server ready for operation?
 
–
Are server and client compatible? (Safety requirements/capabilities)
 
–
Is the security configuration valid? (Certificates renewed/accepted, users changed, connection guidelines, etc.)
 
Warning
 
827462150
0x31521206
Session with handle disconnected because of connection error
Cause
Remedy
Severity/response
An event led to the termination of an incoming connection.
–
The error number coded in accordance with the PLCopen specification "OPC UA Client Function Blocks for IEC 61131-3" provides information on the specific cause.
 
–
A list of possible error numbers is documented in "L_IOCP_OPCUAClient".
 
The remedy depends on the specific error number.
Common faults can be localized/eliminated by the following checks:
–
Is the network connection available?
 
–
Is the server ready for operation?
 
–
Are server and client compatible? (Safety requirements/capabilities)
 
–
Is the security configuration valid? (Certificates renewed/accepted, users changed, connection guidelines, etc.)
 
Warning
 
827462401
0x31521301
Execution stopped due to Error
Cause
Remedy
Severity/response
A fatal error prevents the OPC UA client from running.
–
The error number coded in accordance with the PLCopen specification "OPC UA Client Function Blocks for IEC 61131-3" provides information on the specific cause.
 
–
A list of possible error numbers is documented in "L_IOCP_OPCUAClient".
 
The remedy depends on the specific error number.
Due to the degree of severity, the following measures may be necessary:
–
New firmware installation
 
–
New application program
 
Fault