Bus-related information
|
|||||
|
|
Name
|
|
PROFINET RT
|
|
|
|
Communication medium
|
|
Ethernet 100 Mbps/s, full duplex
|
|
||
|
Application
|
|
Connection as a PROFINET-IO-Device
|
|
||
|
Status display
|
|
2 LEDs (BUS RDY, BUS ERR)
|
|
||
|
Connection designation
|
|
X256 (IN)
X257 (OUT)
|
|
||
|
Technical data
|
|||||
|
|
Communication profile
|
|
PROFINET
|
|
|
|
PNO identification number
|
|
0x0106
|
|
||
|
Device identification (Device ID)
|
|
Device-dependent:
–
Controller c430: 0xC430
–
Controller c520: 0xC520
–
Controller c550: 0xC550
|
|
||
|
Network topology
|
|
Line, tree, ring
|
|
||
|
Device
|
|
|
|
||
|
|
Type
|
|
IO device with real-time communication properties (RT)
|
Conformance Class B, NetloadClass III
|
|
|
Max. number
|
|
255
|
Per subnetwork
|
||
|
Address
|
|
Station name
|
|
||
|
Max. cable length
|
m
|
Not limited
|
The decisive factor is the length between the devices.
|
||
|
Max. cable length between two devices
|
m
|
100
|
|
||
|
Process data
|
|
–
Max. 244 PDOs: freely configurable, regardless of their direction (In, Out, In/Out)
–
Max. 1440 input bytes and max. 1440 output bytes
–
Scaling:
bytes: 1, 2, 4, 8, 12, 16, 24, 32, 48, 64, 80, 96, 128, 160, 192, 224, 250 Word: 1, 2, 4, 6, 8, 12, 16, 24, 32, 40, 48, 64, 80, 96, 112, 125 |
|
||
|
Cycle time
|
ms
|
1, 2, 3, 4, ...
|
|
||
|
Switching method
|
|
Cut-through
|
|
||
|
Optional functions
|
|
–
MRP (Media Redundancy Protocol)
–
Diagnostics
–
Acyclic services; parameter channel
–
Support I&M0..3
–
Exchangeable disk storage
|
|
||
|
Other data
|
|
Additional TCP/IP channel
|
|
||
|
Communication time
|
|||||
|
|
Communication time depending on
|
|
processing time in the controller
|
time between the start of a request and the arrival of the response
|
|
|
|
telegram runtime (transmission rate, telegram length)
|
||||
|
|
nesting depth of the network
|
||||
|
|
bus load
|
||||
|
Processing time of process data
|
|||||
|
|
Update cycle
|
ms
|
1
|
In the controller
|
|
|
Processing time
|
ms
|
0 ... 1
|
|||
|
Runtime of the application task of the technology application used (tolerance)
|
ms
|
1 ... x
|
|||