Monitoring

The parameters for setting network monitoring functions are described below.
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2859:001
Network monitoring: Watchdog elapsed
Selection of the response to a permanent interruption of the communication to the IO controller.
Associated event ID:
–
822313360 | 0x31038190 - Network - Watchdog time-out
 
0
No response
1
Trouble
2
Warning
0x2859:002
Network monitoring: Data exchange exited
Selection of the reaction when leaving the "Data Exchange" state.
Associated event ID:
–
822313361 | 0x31038191 - Network - Disruption of cyclic data exchange
 
0
No response
1
Trouble
2
Warning
0x2859:003
Network monitoring: Invalid configuration
Selection of the response triggered by the reception of invalid configuration data.
Associated event ID:
–
822313607 | 0x31038287 - Network - Invalid configuration
 
0
No response
1
Trouble
2
Warning
0x2859:004
Network monitoring: Initialisation error
Selection of the response triggered by the occurrence of an error during the initialization of the network component.
Associated event ID:
–
822313362 | 0x31038192 - Network - Initialization error
 
0
No response
1
Trouble
2
Warning
0x2859:005
Network monitoring: Invalid process data
Selection of the response triggered by the reception of invalid process data.
Process data marked as invalid (IOPS is "BAD") are received by the IO Controller. Typically in case of
–
a PLC in STOP state,
 
–
alarms,
 
–
acyclic demand data.
 
Associated event ID:
–
822313363 | 0x31038193 - Network - Invalid cyclic process data
 
0
No response
1
Trouble
2
Warning