Install new controller

The current firmware version of the controller is also stored on the SD card used. If the SD card is inserted into a new device, the firmware version from the SD card is imported into the device automatically. This function ensures that the controller firmware and the boot project continue to match.
How to connect a new Controller:
1.
Insert the SD card of the previously removed controller into the new one.
 
2.
Mount the new Controller.
 
3.
If an I/O system 1000 (EPM-Sxxx) is connected to the controller:
 
a.
Mount and connect the electronic modules of the I/O system 1000 (EPM-Sxxx).
 
4.
Connect supply connections, bus connections and all other connections to the Controller.
 
5.
Switch on voltage supply.
The controller is mounted.
 
6.
The controller starts the automatic firmware update if required:
 
a.
The data of the SD card of the defective controller, such as an executable boot project and a visualization, is reused in the replacement device.
 
b.
The firmware update can be detected by the status LEDs of the controller. Details on the update are entered in the logbook. Logbook
 
 
 
 
A voltage failure during the update should be avoided.