Additive voltage impression
This function serves to boost (or lower) the motor voltage from the process via an additive voltage setpoint in order to realise a load adjustment (for instance in case of winder applications).
NOTICE
A too high boost of the motor voltage may cause the motor to heat up strongly due to the resulting current.
▶
Avoid a too high boost of the motor voltage!
Details
At a constant field frequency, the output voltage of the inverter can be changed within a wide range.
Example: Adaptation of the voltage characteristic in case of V/f characteristic control as a function of the load:
–
Forward (CW) is operation in motor mode: Boost voltage.
–
Reverse (CCW) is operation in generator mode: Lower voltage.
|
|
|
|
①
|
Selecting an additive voltage setpoint
|
Parameter
|
Address
|
Name / setting range / [default setting]
|
Information
|
|
|
0x2B13:001
|
Additive voltage impression: Enable Function
–
From version 02.00
|
1 = enable function.
|
|
|
0
|
Disable
|
||
|
1
|
Enable
|
||
|
0x2B13:002
|
Additive voltage impression: Setpoint source
–
From version 02.00
|
Selection of the source for specifying the additive voltage setpoint.
|
|
|
1
|
Analog input 1
|
||
|
2
|
Analog input 2
|
||
|
3
|
Network
|
The additive voltage setpoint is defined via the mappable NetWordIN5 0x4008:005 (P590.05)data word.
|
|
|
201
|
Internal value
|
Internal values of the manufacturer.
|
|
|
202
|
Internal value
|
||
|
203
|
Internal value
|
||
|
204
|
Internal value
|
||
|
205
|
Internal value
|
||
|
206
|
Internal value
|
||
|
0x2B13:003
|
Additive voltage impression: Actual voltage
–
Read only: x V
–
From version 02.00
|
Display of the current (boosted or lowered) voltage.
|
|
|
0x2B13:004
|
Additive voltage impression: Ramp time
0.0 ... [0.0] ... 3600.0 s
–
From version 06.02
|
Ramp time for ramping up the required additive voltage setpoint.
–
The ramp time is effective after each activation of the inverter.
–
The ramp time refers to the rated voltage 0x2C01:007 (P320.07).
|
|
Example: Using the function with a 400-V inverter
With the settings indicated below, the motor is accelerated after the start to 50 Hz. As the base frequency, however, is set very high (here: 599 Hz), the motor voltage at 50 Hz only amounts to 20 VAC.
Now, the analog input 1 serves to change the motor voltage at constant frequency within a wide range:
|
|
|
|
①
|
Motor voltage
|
|
②
|
Selection of an additive voltage setpoint in percent via analog input 1
The setting range (here: 0 ... 100 %) can be adapted via the parameters "Min PID value" and "Max PID value".
|
|
Parameter
|
Designation
|
Setting for this example
|
|
Analog input 1: Min PID value
|
0 %
|
|
|
Analog input 1: Max PID value
|
100 %
|
|
|
Frequency control: Default setpoint source
|
Frequency preset 1 [11]
|
|
|
Frequency setpoint presets: Preset 1
|
50 Hz
|
|
|
V/f shape data: Base frequency
|
599 Hz
|
|
|
Additive voltage impression: Enable Function
|
Enable [1]
|
|
|
Additive voltage impression: Setpoint source
|
Analog input 1 [1]
|