Additive voltage impression

This function serves to boost (or lower) the motor voltage from the process via an additive voltage setpoint in order to realise a load adjustment (for instance in case of winder applications).
 
NOTICE
A too high boost of the motor voltage may cause the motor to heat up strongly due to the resulting current.
▶
Avoid a too high boost of the motor voltage!
 
 
 
Details
At a constant field frequency, the output voltage of the inverter can be changed within a wide range.
Example: Adaptation of the voltage characteristic in case of V/f characteristic control as a function of the load:
–
Forward (CW) is operation in motor mode: Boost voltage.
 
–
Reverse (CCW) is operation in generator mode: Lower voltage.
 
①
Selecting an additive voltage setpoint
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2B13:001
Additive voltage impression: Enable Function
–
From version 02.00
 
1 = enable function.
0
Disable
1
Enable
0x2B13:002
Additive voltage impression: Setpoint source
–
From version 02.00
 
Selection of the source for specifying the additive voltage setpoint.
–
100 % = Rated voltage 0x2C01:007 (P320.07)
 
1
Analog input 1
2
Analog input 2
3
Network
The additive voltage setpoint is defined via the mappable NetWordIN5 0x4008:005 (P590.05)data word.
201
Internal value  
Internal values of the manufacturer.
202
Internal value  
203
Internal value  
204
Internal value  
205
Internal value  
206
Internal value  
0x2B13:003
Additive voltage impression: Actual voltage
–
Read only: x V
 
–
From version 02.00
 
Display of the current (boosted or lowered) voltage.
0x2B13:004
Additive voltage impression: Ramp time
0.0 ... [0.0] ... 3600.0 s
–
From version 06.02
 
Ramp time for ramping up the required additive voltage setpoint.
–
The ramp time is effective after each activation of the inverter.
 
–
The ramp time refers to the rated voltage 0x2C01:007 (P320.07).
 
 
Example: Using the function with a 400-V inverter
With the settings indicated below, the motor is accelerated after the start to 50 Hz. As the base frequency, however, is set very high (here: 599 Hz), the motor voltage at 50 Hz only amounts to 20 VAC.
Now, the analog input 1 serves to change the motor voltage at constant frequency within a wide range:
①
Motor voltage
②
Selection of an additive voltage setpoint in percent via analog input 1
The setting range (here: 0 ... 100 %) can be adapted via the parameters "Min PID value" and "Max PID value".
Parameter
Designation
Setting for this example
Analog input 1: Min PID value
0 %
Analog input 1: Max PID value
100 %
Frequency control: Default setpoint source
Frequency preset 1 [11]
Frequency setpoint presets: Preset 1
50 Hz
V/f shape data: Base frequency
599 Hz
Additive voltage impression: Enable Function
Enable [1]
Additive voltage impression: Setpoint source
Analog input 1 [1]