Optimising the stalling behaviour

If the motor is driven with frequencies above the rated motor frequency, the operating point is shifted to the "field weakening range". In this range, the motor voltage does not increase proportionately to the output frequency anymore. As a consequence, the inverter automatically reduces the maximum current since the full torque is not available anymore at these frequencies.
For special motors which enable an operation in the field weakening range, the behaviour in the field weakening range can be adapted to the motor with 0x2B0C (P319.00).
 
DANGER!
Danger by incorrect parameterisation.
Possible consequences: Death, severe injuries or damage to property
▶
Only change the default setting (0 Hz) in 0x2B0C (P319.00) after consulting the motor manufacturer!
 
▶
Recommendation: Maintain default setting (0 Hz).
 
 
 
Preconditions
The function is only effective in the motor control type "V/f characteristic control (VFC open loop)".
 
Details
The operating range of an asynchronous motor consists of the voltage range ① and the field weakening range. The field weakening range is divided into two ranges:
–
In the first range ②, the power can be kept constant without the motor stalling.
 
–
The second field weakening range ③ is characterised by the fact that the maximum permissible stator current is decreased to prevent the motor from stalling .
 
Speed/torque curve of the asynchronous motor with two field weakening ranges
The override point (n2, M2) can be influenced with 0x2B0C (P319.00).
–
The maximum current characteristic is shifted to higher field frequencies by the frequency entered.
 
–
The maximum permissible current and the maximum torque increase in the field weakening range.
 
–
The risk of motor stalling increases.
 
–
The maximum current characteristic is shifted to lower field frequencies by the frequency entered.
 
–
The maximum permissible current and the maximum torque are reduced in the field weakening range.
 
–
The risk of motor stalling is reduced.
 
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2B0C
(P319.00)
Override field weakening
(Field weak thold)
-599.0 ... [0.0] ... 599.0 Hz
Offset of the override point for field weakening.
Override field weakening
(Field weak thold)
-599.0 ... [-40.0] ... 599.0 Hz