Required commissioning steps

1.
Activate motor control type: 0x2C00 (P300.00) = "V/f characteristic control (VFC open loop) [6]".
 
2.
Set limiting factors for the V/f characteristic:
 
1.
Rated mains voltage 0x2540:001 (P208.01)
 
2.
Minimum frequency 0x2915 (P210.00)
 
3.
Maximum frequency 0x2916 (P211.00)
 
 
3.
Set V/f characteristic data:
 
1.
 
2.
Base frequency 0x2B01:002 (P303.02)
 
 
4.
Select a characteristic shape suitable for the application in 0x2B00 (P302.00).
 
5.
 
6.
Optional: carry out optimisation of the control circuits.
 
–
An optimisation of the control circuits is not mandatory for this motor control type but may lead to better control operation. The control parameters should always be calculated if the motor power does not correspond to the inverter power in order to achieve optimum performance from the slip compensation. (It is sufficient to carry out the "NonEnergized" calculation.)
 
–