Data mapping

The process of data mapping is used for defining which Modbus registers read or write to which inverter parameters.
 
–
There are pre-defined Modbus registers for common control and status words, which are located in coherent blocks, in order to facilitate communication with OPC servers and other Modbus masters. In order to access all relevant data of the inverter, only a minimum number of commands is required.
 
–
In addition, 24 registers are provided for variable mapping, i. e. free assignment to inverter parameters.
 
 
Predefined Modbus control registers
–
These registers are provided with write and read access.
 
–
The cross-reference in column 2 leads to the detailed parameter description.
 
Modbus registers
Permanently assigned parameter
Address
Designation
42101
AC Drive control word
42102
Network setpoint frequency (0.01)
42103
NetWordIN2
42104
NetWordIN3
42105
PID setpoint
42106
Set torque
42107
NetWordIN1
42108
NetWordIN4
42109 ... 42121
-
Reserved
 
Predefined Modbus status registers
–
These registers are only provided with read access.
 
–
The cross-reference in column 2 leads to the detailed parameter description.
 
Modbus registers
Permanently assigned parameter
Address
Designation
42001
AC Drive status word
42002
Frequency (0.01)
42003
Error code
42004
Drive status
42005
Motor voltage
42006
Motor current
42007
Actual current
42008
Apparent power
(42008 = High Word, 42009 = Low Word)
42009
42010
Heatsink temperature
42011
DC-bus voltage
42012
Digital input status (only bit 16 ... bit 31)
42013
Actual torque
42014 ... 42021
-
Reserved
 
Variable mapping
–
Via 0x232B:001 ... 0x232B:024 (P530.01 ... 24), 24 registers can be mapped to parameters of the inverter. Format:
0xiiiiss00
(iiii = index hexadecimal,
ss = subindex hexadecimal)
 
–
The display of the internal Modbus register numbers in 0x232C:001 ... 0x232C:024 (P531.01 ... 24) is generated automatically. Since 32-bit parameters require two registers, there is no 1:1 assignment.
 
–
For the mappable registers, a CRC (Cyclic Redundancy Check) is executed. The checksum determined is displayed in 0x232D (P532.00). The user can read this "validation code" and use it for comparison in the Modbus master. In this way it can be checked whether the inverter currently queried is configured correctly for the respective application.
 
 
 
Parameter
Address
Name / setting range / [default setting]
Information
0x232B:001 ... 0x232B:024
(P530.01 ... 24)
Modbus parameter mapping: Parameter 1 ... Parameter 24
(Para. mapping: Parameter 1 ... Parameter 24)
0x00000000 ... [0x00000000] ... 0xFFFFFF00
Mapping entries for the variable mapped Modbus registers.
–
Format: 0xiiiiss00 (iiii = index, ss = subindex)
 
0x232C:001 ... 0x232C:024
(P531.01 ... 24)
Modbus register assignment: Register 1 ... Register 24
(Reg. assigned: Register 1 ... Register 24)
–
Read only
 
Display of the internal Modbus register number starting from which the parameter mapped in 0x232B:001 ... 0x232B:024 (P530.01 ... 24) is stored.
–
For the first parameter mapped, always 2500.
 
–
From the second parameter mapped, 2500 + offset. The offset results from the data types of the previously mapped parameters.
 
0x232D
(P532.00)
Modbus verification code
(Verificationcode)
–
Read only