ASM field controller

For a quick commissioning, the calculations and settings are made automatically during the motor calibration.
 
Preconditions
The field controller is only effective in the motor control type "Sensorless vector control (SLVC)".
 
Parameter
Address
Name / setting range / [default setting]
Information
0x29C0:001
Field controller settings: Gain
0.00 ... [59.68]* ... 50000.00 A/Vs
* Default setting dependent on the model.
Gain factor Vp of the field controller.
0x29C0:002
Field controller settings: Reset time
1.0 ... [45.5]* ... 6000.0 ms
* Default setting dependent on the model.
Reset time Tn of the field controller.