ASM field weakening controller (extended)
For a quick commissioning, the calculations and settings are
made automatically during the motor calibration.
Preconditions
The field weakening controller is only effective in the motor control type "Sensorless vector control (SLVC)".
Parameter
|
Address
|
Name / setting range / [default setting]
|
Information
|
|
|
0x29E2
|
DC-bus filter time
1.0 ... [25.0] ... 1000.0 ms
|
Filter time for the current DC-bus voltage used for field weakening.
|
|
|
0x29E3
|
Motor voltage filter time
1.0 ... [25.0] ... 1000.0 ms
|
Filter time for the current motor voltage used for field weakening.
|
|
|
0x29E4
(P354.00)
|
Voltage reserve range
(Voltage reserve)
0 ... [5] ... 20 %
|
Voltage reserve at the transition point to the field weakening, with reference to the current value of the DC-bus voltage.
Wirkt bei Sensorless control (SL PSM) (0x2C00 (P300.00) = 3) und bei Sensorless vector control (SLVC) (0x2C00 (P300.00) = 4).
|
|