Information on the network
The inverter has various diagnostic parameters for displaying ...
–
the network status, the CAN master status and the status of various time monitors;
–
telegram counters.
The telegram counters are free-running, i. e. after reaching the maximum value
, the respective counter starts again at 0.
Parameter
|
Address
|
Name / setting range / [default setting]
|
Information
|
|
|
0x1001
|
Error register
–
Read only
|
Bit-coded error status.
–
Bit 0 is set if an error is active.
The other bits signalise which group the active error belongs to:
–
Bit 1: Current error
–
Bit 2: Voltage error
–
Bit 3: Temperature error
–
Bit 4: Communication error
–
Bit 5: Device profile-specific error
–
Bit 6: Reserved (always 0)
–
Bit 7: Manufacturer-specific error
|
|
|
0x2302:001
(P511.01)
|
Active CANopen settings: Active node ID
(CANopen diag.: Active node ID)
–
Read only
|
Display of the active node address.
|
|
|
0x2302:002
(P511.02)
|
Active CANopen settings: Active baud rate
(CANopen diag.: Active baud rate)
–
Read only
|
Display of the active baud rate.
|
|
|
0
|
Automatic
|
||
|
1
|
20 kbps
|
||
|
2
|
50 kbps
|
||
|
3
|
125 kbps
|
||
|
4
|
250 kbps
|
||
|
5
|
500 kbps
|
||
|
6
|
800 kbps
|
||
|
7
|
1 Mbps
|
||
|
0x2307
(P515.00)
|
CANopen time-out status
(Time-out status)
–
Read only
|
Bit-coded status display of the CAN time monitoring functions.
|
|
|
Bit 0
|
RPDO1-Timeout
|
1 = RPDO1 was not received within the monitoring time or not with the sync configured.
–
Status is reset automatically after the RPDO has been received again.
–
Setting of monitoring time for RPDO1 in 0x1400:005 (P540.05).
|
|
|
Bit 1
|
RPDO2-Timeout
|
1 = RPDO2 was not received within the monitoring time or not with the sync configured.
–
Status is reset automatically after the RPDO has been received again.
–
Setting of monitoring time for RPDO2 in 0x1401:005 (P541.05).
|
|
|
Bit 2
|
RPDO3-Timeout
|
1 = RPDO3 was not received within the monitoring time or not with the sync configured.
–
Status is reset automatically after the RPDO has been received again.
–
Setting of monitoring time for RPDO3 in 0x1402:005 (P542.05).
|
|
|
Bit 8
|
Heartbeat-Timeout Consumer 1
|
1 = within the "Heartbeat Consumer Time", no heartbeat telegram was received from node 1 to be monitored.
–
Status can only be reset by mains switching or error reset.
–
"Heartbeat Consumer Time" setting in 0x1016:001 (P520.01).
|
|
|
Bit 9
|
Heartbeat-Timeout Consumer 2
|
1 = within the "Heartbeat Consumer Time", no heartbeat telegram was received from node 2 to be monitored.
–
Status can only be reset by mains switching or error reset.
–
"Heartbeat Consumer Time" setting in 0x1016:002 (P520.02).
|
|
|
Bit 10
|
Heartbeat-Timeout Consumer 3
|
1 = within the "Heartbeat Consumer Time", no heartbeat telegram was received from node 3 to be monitored.
–
Status can only be reset by mains switching or error reset.
–
"Heartbeat Consumer Time" setting in 0x1016:003 (P520.03).
|
|
|
Bit 11
|
Heartbeat-Timeout Consumer 4
|
1 = within the "Heartbeat Consumer Time", no heartbeat telegram was received from node 4 to be monitored.
–
Status can only be reset by mains switching or error reset.
–
"Heartbeat Consumer Time" setting in 0x1016:004 (P520.04).
|
|
|
0x2308
(P516.00)
|
CANopen status
(CANopen status)
–
Read only
|
Display of the current state.
|
|
|
0
|
Initialisation
|
Initialisation active.
–
The initialisation is started automatically at mains connection. During this phase, the inverter us not involved in the data exchange process on the CAN bus.
–
All CAN-relevant parameters are initialised with the saved settings.
–
When the initialisation process has been completed, the inverter automatically adopts the "Pre-Operational" state.
|
|
|
1
|
Reset node
|
"Reset Node" NMT command active.
–
All parameters are initialised with the saved settings (not only the CAN-relevant parameters).
|
|
|
2
|
Reset communication
|
"Reset Communication" NMT command active.
–
Initialization of all CANopen-relevant parameters with the saved settings.
|
|
|
4
|
Stopped
|
"Stop remote node" NMT command active.
–
Only network management telegrams can be received.
|
|
|
5
|
Operational
|
Parameter data and process data can be received. If defined, process data is sent as well.
|
|
|
127
|
Pre-Operational
|
Parameter data can be received, process data are ignored.
|
|
|
0x2309
(P517.00)
|
CANopen controller status
(CAN contr.status)
–
Read only
|
Status display of the internal CANopen controller.
|
|
|
1
|
Error active
|
The inverter is a fully-fledged communication node
at the CANopen network. It is able to transmit and receive data
and to report faults.
|
|
|
2
|
Error passive
|
The inverter can only passively indicate faulty reception via
the ACK field.
|
|
|
3
|
Bus off
|
The inverter is electrically separated from the CANopen network.
In order to exit this state, the
CANopen interface must be reset. An automatic restart is implemented.
|
|
|
0x230A:000
|
CANopen statistics: Highest subindex
–
Read only
|
Number of frame and error counters.
|
|
|
0x230A:001
(P580.01)
|
CANopen statistics: PDO1 received
(CAN statistics: PDO1 received)
–
Read only
|
Display of the number of PDO1 telegrams received.
|
|
|
0x230A:002
(P580.02)
|
CANopen statistics: PDO2 received
(CAN statistics: PDO2 received)
–
Read only
|
Display of the number of PDO2 telegrams received.
|
|
|
0x230A:003
(P580.03)
|
CANopen statistics: PDO3 received
(CAN statistics: PDO3 received)
–
Read only
|
Display of the number of PDO3 telegrams received.
|
|
|
0x230A:005
(P580.05)
|
CANopen statistics: PDO1 transmitted
(CAN statistics: PDO1 transmitted)
–
Read only
|
Display of the number of PDO1 telegrams sent.
|
|
|
0x230A:006
(P580.06)
|
CANopen statistics: PDO2 transmitted
(CAN statistics: PDO2 transmitted)
–
Read only
|
Display of the number of PDO2 telegrams sent.
|
|
|
0x230A:007
(P580.07)
|
CANopen statistics: PDO3 transmitted
(CAN statistics: PDO3 transmitted)
–
Read only
|
Display of the number of PDO3 telegrams sent.
|
|
|
0x230A:009
(P580.09)
|
CANopen statistics: SDO1 telegrams
(CAN statistics: SDO1 counter)
–
Read only
|
Display of the number of SDO1 telegrams.
|
|
|
0x230A:010
(P580.10)
|
CANopen statistics: SDO2 telegrams
(CAN statistics: SDO2 counter)
–
Read only
|
Display of the number of SDO2 telegrams.
|
|
|
0x230B
(P518.00)
|
CANopen error counter
(CAN errorcounter)
–
Read only
|
Display of the total number of CAN faults that have occurred.
|
|