Commissioning

In the following, the steps required for controlling the inverter via CANopen are described.
 
Parameterization required
1.
Set the CANopen node address.
 
–
Each network node must be provided with a unique node address.
 
–
 
 
2.
Set the CANopen baud rate.
 
–
Default setting: 500 = kbit/s
 
–
 
 
3.
Optional: Configure inverter as "mini master".
 
–
Required if the initialization of the CANopen network and the associated status change
from "Pre-Operational" to "Operational" is not effected by a higher-level host system.
 
–
 
 
4.
Optional: Change the response of the inverter to the triggering of the RPDO time monitoring.
 
–
Default setting: In case of missing RPDOs, an error is triggered.
 
–
Details: Error responses 
 
 
5.
Save parameter settings: 0x2022:003 (P700.03) = "On / start = [1]".
 
6.
Switch the inverter off and then on again in order that the changed communication settings can get effective.
 
7.
Program the master so that the following SDO messages are sent to the inverter:
 
1.
0x2631:037 (P400.37) = 1 (activate network control)
 
2.
0x2860:001 (P201.01) = 5 (set network as standard setpoint source)
 
3.
PDO mapping and configuration of the process data objects RPDO1 and TPDO1 (see the sections "RPDO1 mapping modification" and "TPDO1 mapping modification").
 
 
8.
Control inverter via RPDO1 (and evaluate the current status via TPDO1).
 
–
For assignment of the control word and setpoint selection, see section "RPDO1 mapping modification".
 
–
For assignment of the status word and actual value output, see section "TPDO1 mapping modification".
 
–
Acceleration 0x2917 (P220.00) and deceleration 0x2918 (P221.00) can be set/changed via SDO messages.
 
 
In the default setting, the digital input DI1 is assigned the "Run" function. If the network control is activated, this function serves as "start enable" for start commands via network. Hence, the digital input DI1 must be set to the HIGH level in order that the motor can be started via the network.
 
 
RPDO1 mapping modification
The RPDO1 is used to control the inverter.
Changing the identifier (COB-ID) and the PDO mapping only allows the following procedure:
1.
Set RPDO1 to "invalid": Set bit 31 in the identifier 0x1400:001 (P540.01) = 1.
 
2.
Set RPDO1 mapping to "invalid": set 0x1600:000 = 0
 
3.
Map NetWordIN1 data word 0x4008:001 (P590.01) to RPDO1: set 0x1600:001 = 0x40080110.
 
4.
Network setpoint frequency (0.1) 0x400B:003 (P592.03) to RPDO1: set  0x1600:002 = 0x400B0310.
 
5.
Set RPDO1 mapping to "valid" again: set 0x1600:000 = 2 (number of mapped parameters).
 
6.
Optional: Set timeout time for monitoring the data reception in 0x1400:005 (P540.05) in [ms].
 
–
Default setting: 100 ms
 
 
7.
Change identifier for RPDO1 (optional) and set RPDO1 to "valid" again: Write the new identifier into 0x1400:001 (P540.01) and simultaneously set bit 31 to "0".
 
–
Default setting: 0x200 + node address (hex)
 
–
Example: Node address = 10 (0xA) and basic identifier = default setting:
Identifier to be written into  = 0x200 + 0xA = 0x20A = (0b0011 0000 1010)
 
 
Function assignment of the NetWordIN1 data word (byte 1+2 of the RPDO1)
Bit
Default setting
For details and configuration, see
0
Not active (reserve)
1
Not active (reserve)
2
Activate quick stop
3
Not active (reserve)
4
Run forward (CW)
5
Activate preset (bit 0)
6
Activate preset (bit 1)
7
Reset error
8
Not active (reserve)
9
Activate DC braking
10
Not active (reserve)
11
Not active (reserve)
12
Reverse rotational direction
13
Not active (reserve)
14
Not active (reserve)
15
Not active (reserve)
Specifying the frequency setpoint (byte 3+4 of the RPDO1)
–
The specification is made unsigned (independent of the direction of rotation) as integer in the resolution [0.1 Hz].
 
–
The direction of rotation is defined in the default setting via bit 12 of the NetWordIN1 data word.
 
–
Example: 456 = 45.6 Hz
 
 
TPDO1 mapping modification
The TPDO1 is used for the output of status information and the actual frequency value.
Changing the identifier (COB-ID) and the PDO mapping only allows the following procedure:
1.
Set TPDO1 to "invalid": Set bit 31 in the identifier 0x1800:001 (P550.01) = 1.
 
2.
Set TPDO1 mapping to "invalid": set 0x1A00:000 = 0.
 
3.
Map NetWordOUT1 data word 0x400A:001 (P591.01) to TPDO1: set 0x1A00:001 = 0x400A0110.
 
4.
Frequency (0.1) 0x400B:003 (P592.03) to TPDO1: set  0x1A00:002 = 0x400C0310.
 
5.
Set TPDO1 mapping to "valid" again: set 0x1A00:000 = 2 (number of mapped parameters).
 
6.
Option: Transmission type in 0x1800:002 (P550.02) Event timer in 0x1800:005 (P550.05).
 
–
Default setting: Cyclic transmission every 20 ms.
 
 
7.
Change identifier for TPDO1 (optional) and set TPDO1 to "valid" again: Write the new identifier into 0x1800:001 (P550.01) and simultaneously set bit 31 to "0".
 
–
Default setting: 0x40000180 + node address (hex)
 
–
Example: Node address = = 10 (0xA) and TPDO1 basic identifier = default setting:
Identifier to be written into 0x1800:001 (P550.01) = 0x40000180 + 0xA = 0x4000018A (0b0100 0000 0000 0000 0000 0001 1000 1010)
 
 
Status assignment of the NetWordOUT1 data word (byte 1+2 of the TPDO1)
Bit
Default setting
For details and configuration, see
0
Ready for operation
1
Not connected
2
Operation enabled
3
Fault active
4
Not connected
5
Quick stop active
6
Running
7
Device warning active
8
Not connected
9
Not connected
10
Setpoint speed reached
11
Current limit reached
12
Actual speed = 0
13
Rotational direction reversed
14
Release holding brake
15
Inverter disabled (safety)
Output of the actual frequency value (byte 3+4 of the TPDO1)
–
The output is made unsigned (independent of the direction of rotation) as integer in the resolution [0.1 Hz].
 
–
An active reversal is displayed via bit 13 of the NetWordOUT1 data word.
 
–
Example: 456 = 45.6 Hz
 
 
Restart of the communication
A restart of communication is required after changes of the interface configuration (e. g. node address and baud rate) in order that the changed settings become effective.
For restarting communication, there are two options:
a.
Switch inverter off and on again.
 
b.
0x2300 (P508.00) Set = "Restart with current values [1]".
 
 
The following parameter can be used to restart or stop communication.
Optionally it is also possible to reset all communication parameters to the default status.
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2300
(P508.00)
CANopen communication
(CANopen comm.)
–
Setting can only be changed if the inverter is disabled.
 
Restart / stop communication.
–
After successful execution, the value 0 is shown.
 
0
No action/no error
Only status feedback
1
Restart with current values
Restart communication with the current values of the CANopen parameters.
2
Restart with default values
Restart communication with the standard values of the CANopen parameters.
5
Stop network communication
Stop communication.
–
The "Stop Remote Node" NMT command is executed. After successful execution of this command, only the reception of network management frames is possible.
 
10
In progress
Only status feedback
11
Action cancelled
12
Fault