Configuring the device as mini master
If the initialisation of the CANopen network and the associated status change from "Pre-Operational"
to "Operational" is not effected by a master (PLC), the inverter can instead
be defined as a "mini master” to execute
this task.
Details
The inverter is configured as mini master in 0x2301:003 (P510.03).
–
In the default setting, the inverter is configured as slave and waits for the NMT telegram "Start Remote Node" from the master (PLC) in the "Pre-Operational" state after being switched on.
–
Configured as mini master, the inverter changes to the "Operational" state after being switched on and sets all nodes connected to the CAN bus (broadcast telegram) to the "Operational" communication state using the "Start Remote Node" NMT telegram after the deceleration time set in 0x2301:004 (P510.04) has elapsed. Only this communication status enables data exchange via the process data objects.
The change of the master/slave operation only becomes effective
by renewed mains switching of the inverter
or
by sending the NMT telegram "Reset Node" or "Reset Communication"
to the inverter. Alternatively, the CAN communication can be restarted via 0x2300 (P508.00).
Parameter