Information on the network

The inverter has various diagnostic parameters for displaying ...
–
the network status, the CAN master status and the status of various time monitors;
 
–
telegram counters.
 
The telegram counters are free-running, i. e. after reaching the maximum value , the respective counter starts again at 0.
 
Parameter
Address
Name / setting range / [default setting]
Information
0x1001
Error register
–
Read only
 
Bit-coded error status.
–
Bit 0 is set if an error is active.
 
The other bits signalise which group the active error belongs to:
–
Bit 1: Current error
 
–
Bit 2: Voltage error
 
–
Bit 3: Temperature error
 
–
Bit 4: Communication error
 
–
Bit 5: Device profile-specific error
 
–
Bit 6: Reserved (always 0)
 
–
Bit 7: Manufacturer-specific error
 
0x2302:001
(P511.01)
Active CANopen settings: Active node ID
(CANopen diag.: Active node ID)
–
Read only
 
Display of the active node address.
0x2302:002
(P511.02)
Active CANopen settings: Active baud rate
(CANopen diag.: Active baud rate)
–
Read only
 
Display of the active baud rate.
0
Automatic  
1
20 kbps
2
50 kbps
3
125 kbps
4
250 kbps
5
500 kbps
6
800 kbps
7
1 Mbps
0x2307
(P515.00)
CANopen time-out status
(Time-out status)
–
Read only
 
Bit-coded status display of the CAN time monitoring functions.
Bit 0
RPDO1-Timeout
1 = RPDO1 was not received within the monitoring time or not with the sync configured.
–
Status is reset automatically after the RPDO has been received again.
 
–
Setting of monitoring time for RPDO1 in 0x1400:005 (P540.05).
 
Bit 1
RPDO2-Timeout
1 = RPDO2 was not received within the monitoring time or not with the sync configured.
–
Status is reset automatically after the RPDO has been received again.
 
–
Setting of monitoring time for RPDO2 in 0x1401:005 (P541.05).
 
Bit 2
RPDO3-Timeout
1 = RPDO3 was not received within the monitoring time or not with the sync configured.
–
Status is reset automatically after the RPDO has been received again.
 
–
Setting of monitoring time for RPDO3 in 0x1402:005 (P542.05).
 
Bit 8
Heartbeat-Timeout Consumer 1
1 = within the "Heartbeat Consumer Time", no heartbeat telegram was received from node 1 to be monitored.
–
Status can only be reset by mains switching or error reset.
 
–
"Heartbeat Consumer Time" setting in 0x1016:001 (P520.01).
 
Bit 9
Heartbeat-Timeout Consumer 2
1 = within the "Heartbeat Consumer Time", no heartbeat telegram was received from node 2 to be monitored.
–
Status can only be reset by mains switching or error reset.
 
–
"Heartbeat Consumer Time" setting in 0x1016:002 (P520.02).
 
Bit 10
Heartbeat-Timeout Consumer 3
1 = within the "Heartbeat Consumer Time", no heartbeat telegram was received from node 3 to be monitored.
–
Status can only be reset by mains switching or error reset.
 
–
"Heartbeat Consumer Time" setting in 0x1016:003 (P520.03).
 
Bit 11
Heartbeat-Timeout Consumer 4
1 = within the "Heartbeat Consumer Time", no heartbeat telegram was received from node 4 to be monitored.
–
Status can only be reset by mains switching or error reset.
 
–
"Heartbeat Consumer Time" setting in 0x1016:004 (P520.04).
 
0x2308
(P516.00)
CANopen status
(CANopen status)
–
Read only
 
Display of the current state.
0
Initialisation
Initialisation active.
–
The initialisation is started automatically at mains connection. During this phase, the inverter us not involved in the data exchange process on the CAN bus.
 
–
All CAN-relevant parameters are initialised with the saved settings.
 
–
When the initialisation process has been completed, the inverter automatically adopts the "Pre-Operational" state.
 
1
Reset node
"Reset Node" NMT command active.
–
All parameters are initialised with the saved settings (not only the CAN-relevant parameters).
 
2
Reset communication
"Reset Communication" NMT command active.
–
Initialization of all CANopen-relevant parameters with the saved settings.
 
4
Stopped
"Stop remote node" NMT command active.
–
Only network management telegrams can be received.
 
5
Operational
Parameter data and process data can be received. If defined, process data is sent as well.
127
Pre-Operational
Parameter data can be received, process data are ignored.
0x2309
(P517.00)
CANopen controller status
(CAN contr.status)
–
Read only
 
Status display of the internal CANopen controller.
1
Error active
The inverter is a fully-fledged communication node at the CANopen network. It is able to transmit and receive data and to report faults.
2
Error passive
The inverter can only passively indicate faulty reception via the ACK field.
3
Bus off
The inverter is electrically separated from the CANopen network. In order to exit this state, the CANopen interface must be reset. An automatic restart is implemented.
0x230A:000
CANopen statistics: Highest subindex
–
Read only
 
Number of frame and error counters.
0x230A:001
(P580.01)
CANopen statistics: PDO1 received
(CAN statistics: PDO1 received)
–
Read only
 
Display of the number of PDO1 telegrams received.
0x230A:002
(P580.02)
CANopen statistics: PDO2 received
(CAN statistics: PDO2 received)
–
Read only
 
Display of the number of PDO2 telegrams received.
0x230A:003
(P580.03)
CANopen statistics: PDO3 received
(CAN statistics: PDO3 received)
–
Read only
 
Display of the number of PDO3 telegrams received.
0x230A:005
(P580.05)
CANopen statistics: PDO1 transmitted
(CAN statistics: PDO1 transmitted)
–
Read only
 
Display of the number of PDO1 telegrams sent.
0x230A:006
(P580.06)
CANopen statistics: PDO2 transmitted
(CAN statistics: PDO2 transmitted)
–
Read only
 
Display of the number of PDO2 telegrams sent.
0x230A:007
(P580.07)
CANopen statistics: PDO3 transmitted
(CAN statistics: PDO3 transmitted)
–
Read only
 
Display of the number of PDO3 telegrams sent.
0x230A:009
(P580.09)
CANopen statistics: SDO1 telegrams
(CAN statistics: SDO1 counter)
–
Read only
 
Display of the number of SDO1 telegrams.
0x230A:010
(P580.10)
CANopen statistics: SDO2 telegrams
(CAN statistics: SDO2 counter)
–
Read only
 
Display of the number of SDO2 telegrams.
0x230B
(P518.00)
CANopen error counter
(CAN errorcounter)
–
Read only
 
Display of the total number of CAN faults that have occurred.