AC drive status word

Parameter
Address
Name / setting range / [default setting]
Information
0x400C:001
Process output data: AC Drive status word
–
Read only
 
Mappable status word with bit assignment in compliance with EtherNet/IP™ AC drive profile.
Bit 0
Fault/Trip active
Bit 1
Warning active
Bit 2
Running forward
Bit 3
Running reverse
Bit 4
Ready
Bit 5
Network control active
Bit 6
Network setpoint active
Bit 7
At Reference
Bit 8
Profile-State bit 0
The drive status is coded as follows:
0: Manufacturer-specific (reserved)
1: Startup (drive initialisation)
2: Not_Ready (mains voltage switched off)
3: Ready (mains voltage switched on)
4: Enabled (drive has received run command)
5: Stopping (drive has received stop command and is stopped)
6: Fault_Stop (drive is stopped due to a fault)
7: Faulted (faults have occurred)
Bit 9
Profile-State bit 1
Bit 10
Profile-State bit 2
Bit 11
Profile-State bit 3
Bit 12
Process controller active
Bit 13
Torque mode active
Bit 14
Current limit reached
Bit 15
DC braking active