Status LEDs
The "MS" LED indicate the CIP module status.
|
LED "MS" (green/red)
|
CIP module status
|
Status/meaning
|
|
off
|
Nonexistent
|
The network option is not supplied with voltage.
|
|
On (green)
|
Operational
|
The network option works correctly.
|
|
Blinking green
|
Standby
|
The network option is not configured completely or the configuration is incorrect.
|
|
Blinking red
|
Major recoverable fault
|
The network option contains a correctable error.
|
|
on (red)
|
Major unrecoverable fault
|
The network option contains a non-correctable error.
|
|
Blinking green/red
|
Device self testing
|
The network option executes a self-test.
|
The "NS" LED indicate the CIP network status.
|
LED "NS" (green/red)
|
CIP network status
|
Status/meaning
|
|
off
|
No IP address
|
The network option is not supplied with voltage or has not received an IP address yet.
|
|
On (green)
|
Connected
|
The network option works correctly and has established a connection to the scanner.
|
|
Blinking green
|
No connections
|
The network option
–
works correctly,
–
has been assigned to an IP address,
–
has not been implemented into the network yet by the scanner.
|
|
Blinking red
|
Connection timeout
|
A time-out has occurred.
|
|
on (red)
|
Duplicate IP
|
The network option cannot access the network (IP address conflict).
|
|
Blinking green/red
|
Device self testing
|
The network option executes a self-test.
|
The "L/A" LEDs indicate the connection status of ports X396 and X397.
|
LED "L/A"
|
Status
|
Meaning
|
|
off
|
Not connected
|
Network not available
|
|
on
|
Connected
|
Network available
No data transfer
|
|
blinking
|
Traffic
|
Data transfer
|