Process controller diagnostics

The following parameters serve to diagnose the process controller.
 
Parameter
Address
Name / setting range / [default setting]
Information
0x401F:001
Process controller diagnostics: Current setpoint
–
Read only: x.xx PID unit
 
Display of the current reference value (setpoint) for the process controller.
0x401F:002
Process controller diagnostics: Current process variable
–
Read only: x.xx PID unit
 
Display of the current controlled feedback variable (actual value) for the process controller.
0x401F:003
Process controller diagnostics: Status
–
Read only
 
Bit-coded status display of the process controller.
Bit 0
Process controller off
Bit 1
PID output set to 0
Bit 2
PID I-component inhibited
Bit 3
PID influence active
Bit 4
Setpoint = actual value
Bit 5
Sleep mode active
Bit 6
Max. alarm
Bit 7
Min. alarm
0x401F:004
Process controller diagnostics: PID control value
–
Read only: x.x Hz
 
Display of the output frequency after the PID controller, but without any influencing factor.
0x401F:005
Process controller diagnostics: PID Feedforward value
–
Read only: x.x Hz
 
Display of the feedforward control value for the process controller.
0x401F:006
Process controller diagnostics: PID output value
–
Read only: x.x Hz
 
Display of the current process controller setpoint that is internally transferred to the motor control (considering the feedforward control value).
0x401F:007
Process controller diagnostics: PID error value
–
Read only: x.xx PID unit
 
Display of the difference between reference value (setpoint) and feedback variable (actual value) of the process controller.