Set voltage boost

The parameterisable voltage boost makes it possible to improve the starting performance for applications requiring a high starting torque.
 
The function is equally suitable for the closed loop V/f characteristic control.
 
 
Details
–
In 0x2B12:001, a permanent voltage boost can be set. ①
 
–
In 0x2B12:002, an additional voltage boost can be set for acceleration processes ②
 
–
Reference for the percentage setting of the voltage boost is the base voltage 0x2B01:001.
 
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2B12:001
V/f voltage boost: Fixed boost
0.0 ... [0.0] ... 20.0 %
Constant voltage boost for V/f characteristic control without feedback.
–
100 % = V/f base voltage 0x2B01:001
 
–
For the purpose of optimizing the start behavior for applications requiring a high starting torque.
 
0x2B12:002
V/f voltage boost: Boost at acceleration
0.0 ... [0.0] ... 20.0 %
Additional voltage boost for V/f characteristic control without feedback.
–
100 % = V/f base voltage 0x2B01:001
 
–
This voltage boost is only active while the motor is accelerated. It then acts in addition to the fixed voltage boost set in 0x2B12:001.