Additive voltage impression

This function serves to boost (or lower) the motor voltage from the process via an additive voltage setpoint in order to realise a load adjustment (for instance in case of winder applications).
 
The function is equally suitable for the closed loop V/f characteristic control.
 
 
NOTICE
A too high boost of the motor voltage may cause the motor to heat up strongly due to the resulting current.
▶
Avoid a too high boost of the motor voltage!
 
 
 
Details
At a constant field frequency, the output voltage of the inverter can be changed within a wide range.
Example: Adaptation of the voltage characteristic in case of V/f characteristic control as a function of the load:
–
Forward (CW) is operation in motor mode: Boost voltage.
 
–
Reverse (CCW) is operation in generator mode: Lower voltage.
 
①
Selecting an additive voltage setpoint
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2B13:001
Additive voltage impression: Enable Function
1 = enable function.
0
Disable
1
Enable
0x2B13:002
Additive voltage impression: Setpoint source
Selection of the source for specifying the additive voltage setpoint.
–
100 % = Rated voltage 0x2C01:007
 
1
Analog input 1
2
Analog input 2
3
Network
The additive voltage setpoint is defined via the mappable NetWordIN5 0x4008:005data word.
210
IOL1 AI1 scaled value
Value is specified as process data object via IO-Link.
–
The function assignment of the connectors must be configured accordingly.
 
–
The IO-Link ports are only available on the inverter with Application-I/O.
 
211
IOL1 AI2 scaled value
212
IOL2 AI1 scaled value
213
IOL2 AI2 scaled value
214
IOL3 AI1 scaled value
215
IOL3 AI2 scaled value
216
IOL4 AI1 scaled value
217
IOL4 AI2 scaled value
230
Scaling1 value
Output values of the "Analog signal scaling" function. This function is used to scale internal analog signals (analog parameter values) for use within the inverter.
231
Scaling2 value
0x2B13:003
Additive voltage impression: Actual voltage
–
Read only: x V
 
Display of the current (boosted or lowered) voltage.
0x2B13:004
Additive voltage impression: Ramp time
0.0 ... [0.0] ... 3600.0 s
Ramp time for ramping up the required additive voltage setpoint.
–
The ramp time is effective after each activation of the inverter.
 
–
The ramp time refers to the rated voltage 0x2C01:007.
 
 
Example: Using the function with a 400-V inverter
With the settings indicated below, the motor is accelerated after the start to 50 Hz. As the base frequency, however, is set very high (here: 599 Hz), the motor voltage at 50 Hz only amounts to 20 VAC.
Now, the network serves to change the motor voltage at constant frequency within a wide range:
①
Motor voltage
②
Selection of an additive voltage setpoint in percent via network
Parameter
Designation
Setting for this example
Frequency control: Default setpoint source
Frequency preset 1 [11]
Frequency setpoint presets: Preset 1
50 Hz
V/f shape data: Base frequency
599 Hz
Additive voltage impression: Enable Function
Enable [1]
Additive voltage impression: Setpoint source
Network [3]