Safe output

Function included in variant:
Extended Safety - ST
 
Via the safe output O1A/O1B information can be output to a higher-level unit (e .g. safety PLC) or external switching elements (actuators) can be controlled.
 
For an application according to category 3 or category 4, the use of both output channels (O1A and O1B) is required.
 
 
–
The status of the safe output is controlled by two ways:
 
–
directly from the integrated safety technology (parameterization required)
 
–
via a safety bus
 
 
–
The safe output is not potential-free.
 
–
The safe output is PP switching, i e. two plus channels are switched.
 
–
The safe output in ON state is cyclically tested by quick LOW switching.
 
–
The channels A and B are tested with a time offset, in cycles of approx. 2 s, with test pulses of < 1 ms.
 
–
When selecting the downstream control elements, ensure that the test pulses will not be detected as LOW level.
 
 
–
Through parameterization, the status of the safety functions can be assigned to the safe output.
 
 
These errors will be detected and set the output to OFF state:
–
Short circuit to the supply voltage.
 
–
In the ON state: Short circuit between the output signals.
 
–
In the ON state: Missing 24-V voltage supply at connections 24E and GND is detected as "Stuck-at-Low" error.
 
These errors are not detected:
–
In the OFF state: Short circuit between the output signals.
 
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2120:001
SD-Out: SD-Out1 source S-Bus
–
Safety parameter (Safety parameter list)
 
Selection of the safety bus as the trigger source for the function.
0
Deactivated
1
Activated
0x2121:001
SD-Out: SD-Out1 logic function
–
Safety parameter (Safety parameter list)
 
Logical function for linking the switching conditions for SD-Out1.
0
OR
1
AND
0x2121:002
SD-Out: "Error active" - Output
Select the safe output for the "Error Active" feedback signal.
0
Disabled
1
SD-Out1 positive logic
2
SD-Out1 negative logic
0x2122
Output image
–
Read only
 
Bit-coded display of the status of the output channels
Logic: 1 = channel active
Bit 0
SD-Out1 channel A
Bit 1
SD-Out1 channel B