Safe output
|
Function included in variant:
|
|
|
Extended Safety - ST
|
Via the safe output O1A/O1B information can be output to a higher-level unit (e .g. safety PLC) or external switching elements (actuators) can be controlled.
For an application according to category 3 or category 4, the use of both output channels (O1A and O1B) is required.
–
The status of the safe output is controlled by two ways:
–
directly from the integrated safety technology (parameterization required)
–
via a safety bus
–
The safe output is not potential-free.
–
The safe output is PP switching, i e. two plus channels are switched.
–
The safe output in ON state is cyclically tested by quick LOW switching.
–
The channels A and B are tested with a time offset, in cycles of approx. 2 s, with test pulses of < 1 ms.
–
When selecting the downstream control elements, ensure that the test pulses will not be detected as LOW level.
–
Through parameterization, the status of the safety functions can be assigned to the safe output.
These errors will be detected and set the output to OFF state:
–
Short circuit to the supply voltage.
–
In the ON state: Short circuit between the output signals.
–
In the ON state: Missing 24-V voltage supply at connections 24E and GND is detected as "Stuck-at-Low" error.
These errors are not detected:
–
In the OFF state: Short circuit between the output signals.