à
Functional safety".Safe inputs
|
Function included in variant:
|
Basic Safety - STO
|
|
Extended Safety - ST
|
The components used must comply with the risk reduction required for the
application.
Passive sensors
Passive sensors are two-channel, contact-based switching elements.
Please note the following:
–
The switches must be wired according to the closed-circuit principle.
–
Passive sensors are connected to the inverter via a safety switching device.
With Extended Safety - ST, the safety component takes over the role of the safety relay.
With Extended Safety - ST, the safety component takes over the role of the safety relay.
–
An external safety component must monitor the connection cables and the function of the sensors if complete exclusion of faults cannot be guaranteed.
The contacts must switch at the same time (equivalent). Safety functions are triggered when only one channel is activated. If only one channel is active, this indicates a faulty sensor or an incorrect wiring configuration.
Examples of passive sensors:
–
Door contact switch
–
Emergency stop control units
Active sensors
Active sensors are devices with two-channel semiconductor outputs (OSSD outputs).
Test pulses for monitoring the outputs and cables are permissible.
P/M-switching sensors switch the positive and negative cable or the signal and ground cable of a sensor signal. P/M-switching sensors are supported only in Basic Safety - STO.
Please note the following:
–
The maximum permissible connection capacity of the outputs.
–
Active sensors are connected directly to the inverter.
–
Monitoring for short circuits must be carried out by the active sensor.
The outputs must switch at the same time (equivalent). Safety functions are triggered when only one channel is activated. If only one channel is active, this indicates a sensor malfunction or improper wiring.
Examples of active sensors:
–
Lightgrid
–
Laser scanner
–
Controllers
Further information
Information on the electrical connection can be found in the corresponding project planning document in the chapter "Electrical installation