Sensor inputs
|
Function included in variant:
|
|
|
Extended Safety - ST
|
Contact function test
An internal contact function test is carried out at the safe inputs.
Safe input in the ON state
–
A LOW level on a channel sets the input to the OFF state; discrepancy monitoring starts at the same time.
–
A LOW level must be detected on both channels within the discrepancy time; if it is not, a discrepancy error is reported.
–
In order to be able to acknowledge a discrepancy error, a LOW level must previously have been detected on both channels.
Safe input in the OFF state
–
A HIGH level on a channel triggers discrepancy monitoring.
–
A HIGH level must be detected on both channels within the discrepancy time; if it is not, a discrepancy error is reported.
–
To be able to acknowledge the discrepancy error, a HIGH level must be detected before at both channels.
Fig. 1: Contact function test − state behavior
Fig. 2: Contact function test − error-free input signals
Fig. 3: Contact function test – faulty input signals
A, B
Safe input, channel A and channel B
C
Internal valuation of the safe input
D
Discrepancy monitoring
AIE
Error acknowledgement
①
Discrepancy monitoring active
②
Discrepancy monitoring time-out
③
Error acknowledgement impermissible
④
Error acknowledgement permissible
Parameter