Secure device reset for downgrade

The "Safe device reset for downgrade" device command allows for a secure downgrade to an unsecured firmware version.
 
For the i550/i650 motec, firmware < V05.00 is classified as unsafe firmware.
 
Details
1.
This device command deletes all user data and the installed firmware, leaving only the Lenze device information stored on the device.
 
2.
After the device command is executed, the device triggers a reset.
 
3.
The reset starts the secure boot loader in communication mode.
 
4.
The secure boot loader detects that all user-specific data is missing and allows the download of unsecure firmware (unsigned legacy firmware).
 
5.
After downloading the firmware: If the secure boot loader detects legacy firmware, it boots it without performing a signature check.
 
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2022:053
Device commands: Secure device reset for downgrade
–
Setting can only be changed if the inverter is disabled.
 
1 = Reset a secure device with secure firmware to a state that allows for a secure downgrade to insecure firmware.
0
Off / ready
Only status feedback
1
On / start
Execute device command
2
In progress
Only status feedback
3
Action cancelled
4
No access