Setting
Please note when setting the parameters:
–
Defining the stop time:
 
–
Consider the closing time of the brake.
 
–
For applications without an encoder, the stop time must be 0.5 s longer than the deceleration time parameterized in the inverter.
 
 
 
–
Depending on the selected operating mode (0x6060), the following quick stop delay is used to bring the drive to a standstill:
 
–
0x6060 = 2 (CiA: Velocity mode (vl)): Quick stop deceleration (0x6085)
 
–
0x6060 = -2, -1 (manufacturer-specific mode): Quick stop deceleration time (0x291C)
 
 
The execution of the quick stop delay is not safety-rated.
 
 
The mode of action of the parameters can be found in the dialog box for the function in the "Safety parameter list" in the engineering tool used.
 
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2894:001
SS1, SS2: Stopping time
0 ... [0] ... 30000 ms
–
Safety parameter (Safety parameter list)
 
Monitored stopping time for SS1 and SS2.
0x2895
SS1 Source SD-In
–
Safety parameter (Safety parameter list)
 
Selection of a safe input as a trigger source for the function.
0
Disabled
1
SD-In1
2
SD-In2
16
SD-In1-A
17
SD-In1-B
18
SD-In2-A
19
SD-In2-B
0x2896
SS1 Source S-Bus
–
Safety parameter (Safety parameter list)
 
Selection of the safety bus as the trigger source for the function.
0
Disabled
1
Activated
0x2897:001
SS1: Mode
–
Safety parameter (Safety parameter list)
 
Condition at which STO is triggered.
0
STO after stopping time
STO is only processed after the parameterized stopping time has elapsed.
1
STO at n=0
STO is already triggered after reaching n=0.
0x2898
SS1 "SS1 active" - Output
–
Safety parameter (Safety parameter list)
 
Selection of the safe output for the "SS1 active" feedback.
0
Disabled
1
SD-Out1 positive logic
2
SD-Out1 negative logic