Setting
Functional sequence and error response have no adjustable parameters.
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2024:002
Special settings: Configure STO
0 ... [0] ... 65535
–
Setting can only be changed if the inverter is disabled.
 
Different drive behaviour with reference to the CiA402 state machine.
Bit 0
Activate STO locked
0 = After "STO active", the inverter is in the "Ready to switch on [4]" device status.
1 = After "STO active", the inverter is in the "Switch on disabled [3]" device status.
In order to restart the inverter from this device state, the following conditions must be met:
–
No STO activation AND
 
–
Transition (FALSE
↗
TRUE) of the configured start signal
 
0 = standard behavior:
After STO is activated, the device status changes to “Switched on”.
1 = Behavior as with the i700 servo inverter:
After STO is activated, the device status changes to “Switch-on disabled”.