Data mapping
The process of data mapping is used for defining which Modbus registers read or write to which inverter parameters.
–
There are pre-defined Modbus registers for common control and status words, which are located in coherent blocks, in order to facilitate communication with OPC servers and other Modbus masters. In order to access all relevant data of the inverter, only a minimum number of commands is required.
–
In addition, 24 registers are provided for variable mapping, i. e. free assignment to inverter parameters.
Predefined Modbus control registers
–
These registers are provided with write and read access.
–
The cross-reference in column 2 leads to the detailed parameter description.
|
Modbus registers
|
Permanently assigned parameter
|
|
|
Address
|
Designation
|
|
|
42101
|
AC Drive control word
|
|
|
42102
|
Network setpoint frequency (0.01)
|
|
|
42103
|
NetWordIN2
|
|
|
42104
|
NetWordIN3
|
|
|
42105
|
PID setpoint
|
|
|
42106
|
Set torque
|
|
|
42107
|
NetWordIN1
|
|
|
42108
|
NetWordIN4
|
|
|
42109 ... 42121
|
-
|
Reserved
|
Predefined Modbus status registers
–
These registers are only provided with read access.
–
The cross-reference in column 2 leads to the detailed parameter description.
|
Modbus registers
|
Permanently assigned parameter
|
|
|
Address
|
Designation
|
|
|
42001
|
AC Drive status word
|
|
|
42002
|
Frequency (0.01)
|
|
|
42003
|
Error code
|
|
|
42004
|
Drive status
|
|
|
42005
|
Motor voltage
|
|
|
42006
|
Motor current
|
|
|
42007
|
Actual current
|
|
|
42008
|
Apparent power
(42008 = High Word, 42009 = Low Word)
|
|
|
42009
|
||
|
42010
|
Heatsink temperature
|
|
|
42011
|
DC-bus voltage
|
|
|
42012
|
Digital input status (only bit 16 ... bit 31)
|
|
|
42013
|
Actual torque
|
|
|
42014 ... 42021
|
-
|
Reserved
|
Variable mapping
–
Via 0x232B:001 ... 0x232B:024 (P530.01 ... 24), 24 registers can be mapped to parameters of the inverter. Format:
0xiiiiss00
(iiii = index hexadecimal,
ss = subindex hexadecimal)
0xiiiiss00
(iiii = index hexadecimal,
ss = subindex hexadecimal)
–
The display of the internal Modbus register numbers in 0x232C:001 ... 0x232C:024 (P531.01 ... 24) is generated automatically. Since 32-bit parameters require two registers, there is no 1:1 assignment.
–
For the mappable registers, a CRC (Cyclic Redundancy Check) is executed. The checksum determined is displayed in 0x232D (P532.00). The user can read this "validation code" and use it for comparison in the Modbus master. In this way it can be checked whether the inverter currently queried is configured correctly for the respective application.
Parameter
|
Address
|
Name / setting range / [default setting]
|
Information
|
|
|
0x232B:001 ... 0x232B:024
(P530.01 ... 24)
|
Modbus parameter mapping: Parameter 1 ... Parameter 24
(Para. mapping: Parameter 1 ... Parameter 24)
0x00000000 ... [0x00000000] ... 0xFFFFFF00
|
Mapping entries for the variable mapped Modbus registers.
–
Format: 0xiiiiss00 (iiii = index, ss = subindex)
|
|
|
0x232C:001 ... 0x232C:024
(P531.01 ... 24)
|
Modbus register assignment: Register 1 ... Register 24
(Reg. assigned: Register 1 ... Register 24)
–
Read only
|
Display of the internal Modbus register number starting from which the parameter mapped in 0x232B:001 ... 0x232B:024 (P530.01 ... 24) is stored.
–
For the first parameter mapped, always 2500.
–
From the second parameter mapped, 2500 + offset. The offset results from the data types of the previously mapped parameters.
|
|
|
0x232D
(P532.00)
|
Modbus verification code
(Verificationcode)
–
Read only
|
||