Emergency telegram

If the error status changes when an internal device error occurs or is remedied, an emergency telegram is sent to the NMT master once.
 
Details
–
The identifier for the emergency telegram is fixedly defined and is shown in 0x1014.
 
–
In 0x1015, a blocking time can be set, in order to limit the bus load in the case of emergency telegrams following quickly in succession.
 
 
Parameter
Address
Name / setting range / [default setting]
Information
0x1014
COB-ID Emergency telegram (EMCY)
–
Read only
 
0x1015
Inhibit time EMCY
0.0 ... [0.0] ... 6553.5 ms
Blocking time which can be set in order to limit the bus load in the case of emergency telegrams following quickly in succession.