Commissioning

The steps required to control the device as an EtherNet/IP adapter with a Rockwell EtherNet/IP scanner are described below.
 
Preconditions
–
The inverter is provided with EtherNet/IP.
 
–
The inverter is networked as EtherNet/IP Adapter with an EtherNet/IP Scanner and, if necessary, further EtherNet/IP nodes.
 
–
Typically, an EtherNet/IP network consists of segments that contain point-to-point connections in a star configuration.
 
–
See also "Typical topologies" under: EtherNet/IP 
 
 
–
An Engineering PC with the software »Studio 5000 Logix Designer®« (from version 30) is connected to the Scanner.
 
–
Current device description files for EtherNet/IP are available.
 
–
 
–
The files are installed via the "EDS Hardware Installation Tool" of the »Studio 5000 Logix Designer®«.
 
–
Allen-Bradley control systems do not need any EDS files to add devices to their configuration.
 
 
–
An »Studio 5000 Logix Designer®« project has been created and is in the offline state.
 
–
The CPU and Ethernet adapter of the PLC (Scanner) have been configured.
 
–
All EtherNet/IP nodes are supplied with voltage and are switched on.
 
 
 
An internal web server is supported. It can be accessed via the IP address defined in the parameter 0x23A1:001 (P510.01). Protect access to the web server with e.g. a "firewall" and follow your internal IT security guidelines.
 
 
A firmware download from the PLC to the inverter via the network (also via FTP) only takes place under the following conditions:
• Required firmware version 05.01.x.x or higher
• Bootloader version 00.00.00.18 or higher
 
 
Commissioning with »Studio 5000 Logix Designer®« (from version 30)
How to configure the network:
Configure IP communication
1.
Make IP basic settings at the Engineering PC.
The PC with the software »Studio 5000 Logix Designer®« must be in the same network as the devices to be configured.
 
2.
Set IP address of the inverter (adapter) via rotary encoder switch and parameter 0x23A1:001 (P510.01).
 
3.
Set subnet mask: 0x23A1:002 (P510.02)
 
4.
Set gateway address: 0x23A1:003 (P510.03)
The configuration of the IP communication is now completed.
 
 
Activate network control in the inverter
1.
Activate network control: 0x2631:037 (P400.37) = "Network control active [114]"
 
2.
Set network as standard setpoint source: 0x2860:001 (P201.01) ="Network [5]"
If another default setpoint source is set, switching to the network setpoint is possible via the AC drive control word 0x400B:001 (P592.01) when network control is activated.
The network control is now activated.
 
3.
Save parameter settings: 0x2022:003 (P700.03) = "On / start [1]"
 
 
Execute I/O configuration with »Studio 5000 Logix Designer®«
1.
Start the »Studio 5000 Logix Designer®«.
 
2.
Open or recreate a »Studio 5000 Logix Designer®« project.
 
3.
Configure the cyclic data transfer (Implicit Messaging).
Process data transfer 
 
4.
Configure the acyclic data transfer (Explicit Messaging).
Parameter data transfer 
The configuration of the network is now completed.
 
 
Save »Studio 5000 Logix Designer®« project
1.
Click ""File"" in the upper toolbar.
 
2.
Execute the "Save" menu command.
The configuration is saved in a file on your PC.
 
 
Load configuration into the scanner:
1.
Click "Communications" in the upper toolbar.
 
2.
Execute the "Download" menu command.
The "Download" dialog box is opened.
 
3.
Click "Download".
The configuration is loaded into the Scanner. If the download has been completed successfully, »Studio 5000 Logix Designer®« changes to the online mode. The I/O-OK field in the upper left area of the screen is green.
 
 
Complete the commissioning
1.
Restart communication, when the EtherNet/IP configuration has been changed:
 
a.
Switch inverter off and on again or
 
b.
Set 0x23A0 (P508.00) = "Restart with current values [1]".
 
 
Commissioning is completed.
 
Control the inverter via the network
In the default setting, the digital input DI1 is assigned the "Run" function. If the network control is activated, this function serves as "start enable" for start commands via network. Hence, the digital input DI1 must be set to the HIGH level in order that the motor can be started via the network.
 
In order that the inverter can be controlled via the network, activate the network control: 0x2631:037 (P400.37) = "Network control active [114]"
Select "Network [5]" in 0x2860:001 (P201.01) to use the network generally as a standard setpoint source. If another standard setpoint source is set, a change-over to the network setpoint via the AC Drive control word 0x400B:001 (P592.01) is possible in case the network control is activated:
Change-over to network setpoint
The network setpoint is activated via bit 6 (NetRef) of the AC Drive control word:
Bit 6
Selection:
0
Standard setpoint source selected in 0x2860:001 (P201.01).
1
Network setpoint
Note!
In order that the activation via bit 6 works, the selection "Network setpoint active [116]" must be set in 0x2631:017 (P400.17).
Optionally, a change-over from the standard setpoint source to the network setpoint is also possible via a digital input:
–
Set a standard setpoint source different than Network" [5]" in 0x2860:001 (P201.01).
 
–
Set the desired digital input in 0x2631:017 (P400.17) via which the change-over to the network setpoint is to take place.
 
 
Bits 5 (NetCtrl) and 6 (NetRef) of byte 0 in the assembly output objects 21 and 23 must be transmitted to the inverter in order that control and speed reference commands are accepted by the network.
If the network control is active (0x400B:001 (P592.01)/bit 5 = 1 and 0x2631:037 (P400.37) = 114), all bits of the AC drive control word (0x400B:001 (P592.01)) are processed.
If the network control is not active (0x400B:001 (P592.01)/bit 5 = 0 or 0x2631:037 (P400.37) = 0), the control bits 0, 1, 12, 13, 14, 15 are not processed. Their states are ignored and the drive is in local control.