Status LEDs
Information about the CAN bus status can be obtained quickly via the
"CAN-RUN" and "CAN-ERR" LED displays on the front of the inverter.
The meaning can be seen from the tables below.
Inverter not active on the CAN bus (yet)
|
LED "CAN-RUN"
|
LED "CAN-ERR"
|
Meaning
|
|
off
|
off
|
Inverter is not active on the CAN bus.
|
|
on
|
"Bus Off" state.
|
|
|
Both LEDs are flickering alternately
|
Automatic baud rate detection active.
|
|
Inverter active on the CAN bus
The green "CAN-RUN" LED indicates the CANopen state:
|
LED "CAN-RUN"
|
CANopen state
|
|
blinking fast (2.5 Hz)
|
Pre-Operational
|
|
on
|
Operational
|
|
blinking 1x, then goes off for 1 s
|
Stopped
|
The red "CAN-ERR" LED indicates a CANopen error:
|
LED "CAN-ERR"
|
CANopen error
|
|
blinking 1x, then goes off for 1 s
|
Warning Limit reached
|
|
blinking 2x, then goes off for 1 s
|
Heartbeat Event
|
|
blinking 3x, then goes off for 1 s
|
Sync message error (only possible in the "Operational" state)
|
|
blinking 4x, then goes off for 1 s
|
Event-timer error (only possible in the "Operational" state)
|