Brake energy management

When braking electrical motors, the kinetic energy of the drive train is fed back regeneratively to the DC bus. This energy causes a DC-bus voltage boost. If the energy fed back is too high, the inverter reports an error.
 
Several different strategies can serve to avoid DC-bus overvoltage:
–
Stopping the deceleration ramp function generator when the active voltage threshold for the brake operation is exceeded
 
–
Use of the "Inverter motor brake" function
 
–
Combination of the above named options
 
 
Details
The voltage threshold for braking operation results on the basis of the rated mains voltage set:
Rated mains voltage (0x2540:001)
Voltage thresholds for braking operation
Braking operation on
Braking operation off
230 V
390 V DC
380 V DC
400 V
725 V DC
710 V DC
480 V
780 V DC
765 V DC