Manual jog parameters
Parameter
|
Address
|
Name / setting range / [default setting]
|
Information
|
|
|
0x2836:001
|
Manual control mode: Current setpoint
0 ... [30] ... 200 %
|
Setting of the current setpoint value for manual control.
|
|
|
0x2836:002
|
Manual control mode: Frequency
-1000.0 ... [0.0] ... 1000.0 Hz
|
Setting of the frequency for manual control.
|
|
|
0x2836:003
|
Manual control mode: Ramp time (current)
0 ... [0] ... 1000 ms
|
Setting of the period of time during which the current setpoint value is achieved from zero onwards.
|
|
|
0x2836:004
|
Manual control mode: Ramp time (frequency)
0 ... [500] ... 10000 ms
|
Setting of the period of time during which the frequency is achieved from zero onwards.
The frequency ramp only starts up when the current ramp has reached the value configured in 0x2836:001 (Current setpoint).
|
|
|
0x2836:005
|
Manual control mode: Time monitoring (frequency)
0 ... [2500] ... 100000 ms
|
Setting of the time period for time monitoring.
–
The manual control features a time monitoring function which is coupled to a write access to 0x2836:002 (Frequency).
–
If no write access to 0x2836:002 takes place within the time period set here, the frequency is moved to zero via the parameterised ramp. When the 0 Hz have been reached, the inverter changes to the error status and is inhibited. After acknowledging the error, the CiA402 state machine must be switched from "Switch-on inhibited" back to the "Operation enabled" state before proceeding with manual control.
|
|
|
0x2836:006
|
Manual control mode: Current controller gain
0.00 ... [20.00] ... 750.00 V/A
|
Setting of the current controller gain.
|
|
|
0x2836:007
|
Manual control mode: Current controller reset time
0.01 ... [20.00] ... 2000.00 ms
|
Setting of the current controller reset time.
|
|