Manual jog parameters

Parameter
Address
Name / setting range / [default setting]
Information
0x2836:001
Manual control mode: Current setpoint
0 ... [30] ... 200 %
Setting of the current setpoint value for manual control.
–
100 % ≡ Rated current (0x2DDF:001)
 
0x2836:002
Manual control mode: Frequency
-1000.0 ... [0.0] ... 1000.0 Hz
Setting of the frequency for manual control.
0x2836:003
Manual control mode: Ramp time (current)
0 ... [0] ... 1000 ms
Setting of the period of time during which the current setpoint value is achieved from zero onwards.
0x2836:004
Manual control mode: Ramp time (frequency)
0 ... [500] ... 10000 ms
Setting of the period of time during which the frequency is achieved from zero onwards.
The frequency ramp only starts up when the current ramp has reached the value configured in 0x2836:001 (Current setpoint).
0x2836:005
Manual control mode: Time monitoring (frequency)
0 ... [2500] ... 100000 ms
Setting of the time period for time monitoring.
–
The manual control features a time monitoring function which is coupled to a write access to 0x2836:002 (Frequency).
 
–
If no write access to 0x2836:002 takes place within the time period set here, the frequency is moved to zero via the parameterised ramp. When the 0 Hz have been reached, the inverter changes to the error status and is inhibited. After acknowledging the error, the CiA402 state machine must be switched from "Switch-on inhibited" back to the "Operation enabled" state before proceeding with manual control.
 
0x2836:006
Manual control mode: Current controller gain
0.00 ... [20.00] ... 750.00 V/A
Setting of the current controller gain.
0x2836:007
Manual control mode: Current controller reset time
0.01 ... [20.00] ... 2000.00 ms
Setting of the current controller reset time.