Mains failure control

This function can decelerate the drive in the event of a mains voltage failure and use its kinetic energy to maintain the DC-bus voltage for a certain period of time. This makes it possible to keep the drive running during a brief failure of the mains voltage or, in the event of a longer failure, to run it to a standstill in a guided manner.
 
Details
The mains failure control is activated when the mains failure monitoring has detected a mains failure.
In the default setting, the mains failure control is switched off. Activate mains failure control 
Controlled regenerative operation raises the DC-bus voltage. This can trigger an overvoltage fault. If an overvoltage fault is to be reliably excluded, the excess energy must be dissipated by a brake resistor.
 
 
Functional description of the mains failure monitoring
The mains failure monitoring compares the currently measured DC-bus voltage with the filtered DC-bus voltage.
If the measured DC-bus voltage 0x6079 is smaller than the filtered DC-bus voltage 0x2D66:014 and smaller than 90 % of the nominal DC-bus voltage, a mains failure is detected.
The mains failure is signaled in status word 2 of the inverter: 0x2833, bit 14 (Mains failure detected)
If a lot of kinetic energy is fed back into the DC bus during a mains failure, the mains failure monitoring will only respond with a delay or possibly not at all due to the DC-bus voltage not dropping.
 
Fig. 1: Function of the mains failure monitoring
 
Functional description of the mains failure control
Setting 0x2833, bit 14 (Mains failure detected) activates the mains failure control if it is enabled. (0x2D66:001 = 2):
–
The motor control switches to speed control with setpoint 0 rpm.
 
–
The deceleration torque ramps up from a starting value to the parameterized maximum value.
 
–
Maximum value: 0x2D66:012
 
–
Ramp time: 0x2D66:013
 
–
The ramp time determines the jerk of the deceleration.
 
 
–
The starting value depends on the current operating mode of the drive:
 
–
Operation in motor mode: Starting torque = 0 Nm.
 
–
Operation in generator mode: Starting torque = 0x6077 (Actual torque)
 
 
–
After the drive has come to a standstill, the 0x3181 (Mains failure) error message is output.
 
–
The original motor control is reactivated with the parameterized values.
 
If undervoltage occurs during mains failure control, the controller is disabled.
 
Fig. 2: Sequence of mains failure control in motor operation
 
Activate mains failure control
How to set up the mains failure control:
1.
Define filter time for the DC-bus voltage:
 
a.
0x2D66:011 = 0.00 s (no filtering):
The current DC-bus voltage is compared with the nominal DC-bus voltageRated mains voltage (0x2540:001) x √2.
Note the following when making this setting:
The usual short-term fluctuations of the mains voltage can already trigger the mains failure control.
 
 
b.
0x2D66:011 > 0.00 s (filtering active):
The current DC-bus voltage is compared with the filtered DC-bus voltage 0x2D66:014 weighted with factor 0x2D66:002.
Note the following when making this setting:
The usual short-term fluctuations of the mains voltage cannot trigger the mains failure control.
 
 
2.
Set the activation threshold: 0x2D66:002 (= weighting for forming the comparison value).
Recommended setting: 75%
With the setting 75 %, the mains failure control is activated if the current DC-bus voltage is more than 25 % below the comparison value.
For high values for the activation threshold, note the following:
The higher the value, the sooner a mains failure is detected due to a sudden drop in DC-bus voltage.
The higher the value, the more energy reserve is available for the guided shutdown in the DC bus.
If the value is too high, there is a risk of false tripping.
For low values for the activation threshold, note the following:
If the value is too low, the energy reserve in the DC bus may be too low.
An undervoltage fault would interrupt the guided shutdown.
 
 
3.
Activate mains failure control: 0x2D66:001 = 2 (Enabled).
 
The mains failure control becomes active with these settings when the DC-bus voltage falls below the comparison values.
 
Behavior in case of mains recovery
The mains failure control is not terminated when the mains returns.
To switch to normal operation immediately, the mains failure control must be terminated via the control word:
 Inverter control word 0x2830, bit 11 = 1 (Stop mains failure control)
 
 
 
 
Deactivate mains failure control
These events terminate the mains failure control:
–
Lock mains failure control 0x2D66:001 = 0 (Disabled)
 
–
Exit via Inverter control word 0x2830, bit 11 = 1 (Stop mains failure control)
 
–
Inverter disable
 
–
Inverter disable due to an error (e.g. undervoltage)
 
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2D66:001
Mains failure control: Enable function
Enable mains failure control.
0
Disabled
Operation without mains failure control.
2
Enabled
Operation with mains failure control.
0x2D66:002
Mains failure control: DC-bus activation level
60 ... [75] ... 90 %
Weighting of the source of the comparison value
Recommended setting: 75%
If the DC-bus voltage falls below the comparison value, the mains failure control is triggered:
–
0x2D66:011 = 0.00 s (no filtering): Comparison value = nominal DC-bus voltage (0x2540:001 x √2) x 0x2D66:002.
 
–
0x2D66:011 > 0.00 s (filtering active): Comparison value = filtered DC-bus voltage (0x2D66:014) x 0x2D66:002.
 
0x2D66:011
Mains failure control: Filter time
0.00 ... [0.00] ... 60.00 s
Filter time for filtering the measured DC-bus voltage. 0x6079
0.00 s = no filtering
The setting also determines the source of the comparison value for detecting the mains failure:
–
0x2D66:011 = 0.00 s (no filtering): Source = nominal DC-bus voltage (0x2540:001 x √2).
 
–
0x2D66:011 > 0.00 s (filtering active): Source = filtered DC-bus voltage (0x2D66:014).
 
0x2D66:012
Mains failure control: Ramp max. torque
0.0 ... [30.0] ... 3276.7 %
Maximum torque of the torque ramp for braking the drive to standstill.
Reference: Rated motor torque (0x6076)
0x2D66:013
Mains failure control: Ramp time
0.00 ... [1.00] ... 5.00 s
Ramp time for reaching the maximum torque.
Reference: Torque change 0 Nm → maximum torque
0x2D66:014
Mains failure control: Actual DC bus voltage (filtered)
–
Read only: x.xxx V
 
Display of the filtered DC-bus voltage.